Bharat Sanchar Nigam Limited - Chennai Telephones - BSNL
Bharat Sanchar Nigam Limited - Chennai Telephones - BSNL
Bharat Sanchar Nigam Limited - Chennai Telephones - BSNL
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Name of Work: Replacement of Class B & B+ C Surge Protection Devices in First Floor at<br />
TE MM Nagar.<br />
Technical Specifications of Surge Protection Devices (SPDs) for 415V AC 50<br />
Hz Power Supply<br />
Applicable Standards<br />
IEC 62305 : Protection against Lightning<br />
Part 1: Basic Principles<br />
Part 2: Risk Assessment<br />
Part 3: Protection of structures<br />
Part 4: Electrical & Electronic equipments within structures<br />
Note: IEC 61024 & IEC 61312 are old standards and are replaced by IEC 62305.<br />
IEC 61643-1: - Surge Protective Devices Connected to Low-Voltage Power Systems:<br />
Performance requirements and testing methods.<br />
IEC 61643-12: - Surge Protective Devices Connected to Low-Voltage Power<br />
Systems:<br />
Selection and application principles<br />
Type of Network – 415V AC 3 phase, 4 wire.<br />
Mains Incoming Panel<br />
Protection at the main incomer of the power supply system – i.e. at the Main Distribution Board<br />
(after the incoming breaker)<br />
Class B/Class I (according to IEC 61643)<br />
3 numbers of lightning arrester for the connection between Phase and Neutral and<br />
one number of lightning arrester between Neutral and Earth with the following<br />
ratings:<br />
Sl.<br />
Specifications<br />
Parameters<br />
No<br />
Line to Neutral Neutral to Earth<br />
1. Type Encapsulated/Non-exhausting Spark<br />
Gap<br />
2. Nominal Voltage, Un 230V, 50/60 Hz<br />
3. Maximum Continuous operating ≥ 255 V<br />
255 V<br />
Voltage Uc<br />
4. Lightning Impulse Current 50 kA (10/350<br />
sec)<br />
≥ 100 kA(10/350<br />
sec)<br />
5. Voltage Protection Level, Up < 1.3 KV<br />
6. Response Time < 100 nano seconds<br />
7. Operating temperature range -40C to +85C<br />
8. Mounting on DIN Rail<br />
9. Degree of Protection IP 20<br />
10. Max. Back-up fuse 500 A gL/gG NA<br />
11. Local Indication LED Indication NA<br />
Contractor Internet Downloaded copy Executive Engineer (E)<br />
Page No. 39 of 40