Appendix 1:<br />

transformer<br />

A transformer is defined by its rated power, its rated primary and<br />

secondary currents, its rated primary and secondary <strong>voltage</strong>s, its<br />

insulation level, its short-circuit <strong>voltage</strong> and its coupling.<br />

The peak-switching current is also a parameter that should not be<br />

forgotten in the determination of protective <strong>switchgear</strong>.<br />

1 - RATED POWER<br />

The<br />

S = U<br />

rated power (S in kVA or MVA) of a transformer is equal to:<br />

• 3 • I r<br />

2 - RATED CURRENT OF ONE WINDING<br />

The rated current Inis equal to:<br />

I r = 3 S •U<br />

3 - RATED VOLTAGE AND INSULATION LEVEL OF ONE WINDING<br />

This in “no-load” is the specified operating <strong>voltage</strong> between to be the applied terminals (primary) of one or transformer developed (secondary)<br />

The rated primary <strong>voltage</strong> must be higher than or equal to that of the winding. network.<br />

rated<br />

<strong>voltage</strong><br />

U r (kV)<br />

insulation level<br />

rms kV (50 Hz - 1 mn) kV impulse (1.2/50 µs)<br />

7.2 20 60<br />

12 28 75<br />

17.5 38 95<br />

24 50 125<br />

36 70 170<br />

4 - SHORT-CIRCUIT VOLTAGE<br />

The short-circuit short-circuit current <strong>voltage</strong> to be (expressed calculated. in %) allows the transformer’s secondary<br />

The short-circuit current is given in the following equation:<br />

•<br />

I k =In<br />

Uk: Ir: rated<br />

U<br />

100<br />

short-circuit current<br />

k<br />

andP k =U r •I k • 3<br />

in <strong>voltage</strong> Ampsin %<br />

given The usual in the Ukvalues tables on depending the following on transformer page. <strong>voltage</strong> and power are<br />

The real values must be requested from the manufacturer.<br />

date<br />

11/94<br />

- B•3•2 -<br />

revised<br />

05/2004<br />

page 1