<strong>Medium</strong> <strong>voltage</strong> <strong>switchgear</strong> <strong>application</strong> <strong>guide</strong><br />

Appendix 1:<br />

transformer(cont’d)<br />

6 - SWITCHING CURRENT PEAK<br />

When peaks the are power produced. is switched on, very high signals or switching<br />

Ie<br />

I r<br />

date<br />

11/94<br />

- B•3•2 -<br />

revised<br />

05/2004<br />

transient state of the current during no-load transformer switching<br />

is They very may quickly be 14 absorbed. times greater The time than constant the rated of current. the damp This down switching depends current<br />

the winding resistance and the secondary load. The real values must beon<br />

requested from the manufacturer.<br />

Time constant and peak-switching current values depending on the immersed transformer power<br />

(high <strong>voltage</strong> switching).<br />

transformer<br />

power<br />

(kVA)<br />

n e = I e peak<br />

I r rms<br />

100 14 0.15<br />

160 12 0.20<br />

250 12 0.22<br />

400 12 0.25<br />

630 11 0.30<br />

800 10 0.30<br />

1000 10 0.35<br />

1250 9 0.35<br />

1600 9 0.40<br />

2000 8 0.45<br />

5000 8 0.50<br />

10000 8 0.50<br />

15000 8 0.50<br />

time<br />

constant<br />

(s)<br />

20000 8 0.50<br />

and In the the event time of constant low <strong>voltage</strong> divided switching, by 1.5 in the relation ratio neshould to the values be multiplied given in the by 2<br />

table These above.<br />

protection switching is defined. peaks must be taken into account when the type of<br />

The transformer may have its own optional devices.<br />

following: Depending on the type, the transformer’s own protective are the<br />

gas ■the leak, waterproof pressure protection and temperature unit for complete detector. filling transformer:<br />

■Buchholz gaz leak and protection pressure relay detector. for transformer fitted with a conservator:<br />

monitoring. ■thermostat, thermometer for immersed-type transformers: temperature<br />

■thermostatic probes for dry-type transformers: temperature control.<br />