Appendix 1:<br />
transformer(cont’d)<br />
6 - SWITCHING CURRENT PEAK<br />
When peaks the are power produced. is switched on, very high signals or switching<br />
Ie<br />
I r<br />
date<br />
11/94<br />
- B•3•2 -<br />
revised<br />
05/2004<br />
transient state of the current during no-load transformer switching<br />
is They very may quickly be 14 absorbed. times greater The time than constant the rated of current. the damp This down switching depends current<br />
the winding resistance and the secondary load. The real values must beon<br />
requested from the manufacturer.<br />
Time constant and peak-switching current values depending on the immersed transformer power<br />
(high <strong>voltage</strong> switching).<br />
transformer<br />
power<br />
(kVA)<br />
n e = I e peak<br />
I r rms<br />
100 14 0.15<br />
160 12 0.20<br />
250 12 0.22<br />
400 12 0.25<br />
630 11 0.30<br />
800 10 0.30<br />
1000 10 0.35<br />
1250 9 0.35<br />
1600 9 0.40<br />
2000 8 0.45<br />
5000 8 0.50<br />
10000 8 0.50<br />
15000 8 0.50<br />
time<br />
constant<br />
(s)<br />
20000 8 0.50<br />
and In the the event time of constant low <strong>voltage</strong> divided switching, by 1.5 in the relation ratio neshould to the values be multiplied given in the by 2<br />
table These above.<br />
protection switching is defined. peaks must be taken into account when the type of<br />
The transformer may have its own optional devices.<br />
following: Depending on the type, the transformer’s own protective are the<br />
gas ■the leak, waterproof pressure protection and temperature unit for complete detector. filling transformer:<br />
■Buchholz gaz leak and protection pressure relay detector. for transformer fitted with a conservator:<br />
monitoring. ■thermostat, thermometer for immersed-type transformers: temperature<br />
■thermostatic probes for dry-type transformers: temperature control.<br />
t<br />
page 3