31.12.2014 Views

Elekta Neuromag® Site Planning Guide for MaxShield - Psychology

Elekta Neuromag® Site Planning Guide for MaxShield - Psychology

Elekta Neuromag® Site Planning Guide for MaxShield - Psychology

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Elekta</strong> Neuromag<br />

<strong>Elekta</strong> Neuromag ®<br />

<strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong><br />

<strong>MaxShield</strong><br />

June 2006<br />

—DRAFT—


DRAFT<br />

NOTICE<br />

This document contains copyrighted and possibly confidential<br />

in<strong>for</strong>mation and is intended <strong>for</strong> the exclusive use of customers<br />

having <strong>Elekta</strong> Neuromag products and authorized representatives<br />

of <strong>Elekta</strong> Neuromag Oy. Disclosure to others or other use is<br />

strictly prohibited without the express written authorization of<br />

<strong>Elekta</strong> Neuromag Oy.<br />

<strong>Elekta</strong> Neuromag Oy reserves the right to make changes in the<br />

specifications or data shown herein at any time without notice or<br />

obligation. <strong>Elekta</strong> Neuromag Oy denies any responsibility <strong>for</strong><br />

damage to apparatus or persons due to improper use or service<br />

per<strong>for</strong>med by unauthorized persons. <strong>Elekta</strong> Neuromag Oy assumes<br />

no liability <strong>for</strong> damage and/or failure of equipment caused<br />

by faulty site preparation.<br />

REVISION HISTORY<br />

- 15.11.2004 Preliminary draft edition<br />

- 30.6.2006 First release (final draft <strong>for</strong> review)<br />

© Copyright <strong>Elekta</strong> Neuromag Oy, Helsinki, Finland<br />

Printed in Finland.<br />

All rights reserved. Reproduction in any <strong>for</strong>m without the written<br />

permission of <strong>Elekta</strong> Neuromag Oy is strictly prohibited.<br />

2 NM21643A


DRAFT<br />

1<br />

CONTENTS<br />

1. MAGNETIC REQUIREMENTS ............................................................................... 5<br />

1.1. Sources of magnetic interference...................................................... 5<br />

1.2. Measurement of magnetic interference ............................................. 5<br />

1.3. Residual magnetic field inside the magnetically shielded room ........... 6<br />

2. MAXSHIELD MAGNETICALLY SHIELDED ROOM CHARACTERISTICS ......................... 8<br />

2.1. Dimensions .................................................................................... 8<br />

2.2. Feedthroughs ................................................................................. 8<br />

2.3. Door .............................................................................................. 9<br />

2.4. Inside / outside décor , lights, and accessories ................................... 9<br />

3. CLIMATIC REQUIREMENTS ............................................................................... 10<br />

3.1. Room temperature in the shielded room, equipment area and operator<br />

area ............................................................................................. 10<br />

3.2. Relative humidity in the shielded room, equipment area and operator<br />

area ............................................................................................. 11<br />

4. POWER SUPPLY AND GROUNDING REQUIREMENTS ............................................ 12<br />

4.1. Power Requirements ..................................................................... 12<br />

4.2. Connection to the building’s power lines, power requirements .......... 13<br />

4.3. Grounding .................................................................................... 14<br />

5. VIBRATION CONSIDERATIONS.......................................................................... 15<br />

5.1. General Recommendations ............................................................ 15<br />

5.2. Recommendations <strong>for</strong> allowable vibration ...................................... 15<br />

5.3. Measurement of vibration.............................................................. 16<br />

6. BUILDING REQUIREMENTS .............................................................................. 17<br />

6.1. Floor space requirements and layout considerations ........................ 17<br />

6.2. Load distribution .......................................................................... 20<br />

6.3. Free ceiling height requirements .................................................... 21<br />

6.3. Exhaust vents................................................................................ 21<br />

6.4. Transportation and access during installation .................................. 21<br />

6.5. Dimensions of the main components of the MEG system ................... 22<br />

6.6. Other considerations ..................................................................... 22<br />

7. TELECOMMUNICATION FACILITIES ON SITE ........................................................ 23<br />

APPENDIX............................................................................................................. 24<br />

MEG-MRI layout considerations ...................................................... 24<br />

NM21643A 3


DRAFT<br />

4 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

1<br />

1. MAGNETIC REQUIREMENTS<br />

1.1. Sources of magnetic interference<br />

1.2. Measurement of magnetic interference<br />

A site survey must be conducted to define the location of the<br />

<strong>Elekta</strong> Neuromag® system. The goal is to find an environment in<br />

which the magnetic disturbances are at a level low enough to be<br />

effectively compensated <strong>for</strong> by the shielded room and the active<br />

compensation systems.<br />

Obvious sources of magnetic interference are elevators, electrical<br />

trans<strong>for</strong>mers, power cables, mechanical/plant rooms, cars, parking<br />

lots, subways, subway stations, trains, street cars, MRI and<br />

CT scanners, and linear accelerators. <strong>Elekta</strong> should be contacted<br />

if any doubt exists regarding the effects of magnetic interference<br />

sources.<br />

Large volume/area ferromagnetic objects, e.g. steel-covered doors,<br />

walls, floors, and furniture should not be located in the vicinity of<br />

the shielded room because they may intensify the interference fields<br />

and cause movement artefacts. If in doubt, contact <strong>Elekta</strong>.<br />

Magnetic interference can also be generated by mechanical vibrations<br />

if the sensors move in the remanent field inside the room.<br />

For detailed discussion see Chapter 5.<br />

The level of magnetic interference is defined by measuring at<br />

different times of the day the three components of the ambient<br />

magnetic field (= B amb<br />

) as functions of time, and calculating the<br />

corresponding spectra. A three-head flux gate connected to a<br />

spectrum analyzer is used <strong>for</strong> this purpose. The measurement is<br />

carried out by <strong>Elekta</strong> or by an employee of a vendor of magnetically<br />

shielded rooms.<br />

If an MRI or CT unit or related equipment (see 1.1. above) is in close<br />

vicinity of the measurement point, the measurements should be<br />

carried out both with the equipment on and with the equipment off.<br />

For measurement of vibration, see Chapter 5.<br />

NM21643A 5


DRAFT<br />

1 Magnetic requirements <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

1.3. Residual magnetic field inside the magnetically shielded room<br />

The spectral density of the residual magnetic field B res<br />

inside the<br />

shield is calculated in the following way:<br />

B res<br />

= B amb<br />

(f)/S(f),<br />

where<br />

B amb<br />

(f) = the spectral density of the ambient magnetic field<br />

at frequency f (from the site survey). Usually, all<br />

three orthogonal directions are treated separately.<br />

It is also common to consider the vector sum of<br />

the x-, y-, and z-components.<br />

S(f) = the combined attenuation factor of the<br />

magnetically shielded room (MSR) and active<br />

compensation systems at frequency f. Note: in<br />

general, the shielding factor depends also on the<br />

location inside the room and on the direction. For<br />

simplicity, however, an average value of all<br />

directions in the middle of the room is often used.<br />

At DC, the state of static magnetization of the shielded room<br />

normally determines the remanent DC-field B rem<br />

in the room. In<br />

such a case the remanent field can be reduced by proper demagnetization.<br />

To obtain optimum per<strong>for</strong>mance of the magnetometer channels,<br />

the value of B amb<br />

, as a function of frequency, and the spectral<br />

density of the remanent DC-field B rem<br />

should not exceed the<br />

following values:<br />

Ambient magnetic field outside, Spectral density:<br />

B amb<br />

≤ 100 nT/ Hz at 0.1 Hz<br />

B amb<br />

≤ 10 nT/ Hz at 1 Hz<br />

B amb<br />

≤ 1 nT/ Hz above 10 Hz<br />

Remanent DC-field inside:<br />

B rem<br />

≤ 50 nT<br />

During MEG-measurements, the magnetometer channels must<br />

not saturate. The residual peak-to-peak fluctuation B res<br />

(0) p-p<br />

at<br />

very low frequencies is given by<br />

B res<br />

(0) p-p<br />

= B amb<br />

(0) p-p<br />

/S(0),<br />

6 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Magnetic requirements 1 1<br />

where<br />

B amb<br />

(0) p-p<br />

= the p-p fluctuation of the ambient field at very low<br />

frequencies as determined from at least 30 min long<br />

DC-coupled recordings during site survey, and<br />

S(0) = the low frequency limiting value of S(f).<br />

To guarantee operation, B amb<br />

(0) p-p<br />

should not exceed<br />

P-P range of ambient field:<br />

B amb<br />

(0) p-p<br />

≤ 2 µT<br />

If the above limits are exceeded, additional shielding might be<br />

necessary.<br />

NM21643A 7


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

2<br />

2. MAXSHIELD MAGNETICALLY SHIELDED ROOM CHARACTERISTICS<br />

2.1. Dimensions<br />

2.2. Feedthroughs<br />

External floor space:<br />

External height:<br />

Door opening:<br />

Door swing radius:<br />

3.2 m × 4.2 m (without exterior finish)<br />

2.6 m<br />

1.0 m × 2.0 m<br />

1.3 m<br />

The following 6 holes <strong>for</strong> technical feedthroughs are required <strong>for</strong><br />

the basic system:<br />

• 2 × φ85 mm <strong>for</strong> filter unit (feedthrough type A)<br />

• φ85 mm <strong>for</strong> stimulus cabinet (feedthrough type A)<br />

• φ35 mm <strong>for</strong> measurement unit movement control (feedthrough<br />

type B)<br />

• φ35 mm <strong>for</strong> helium boil-off (feedthrough type B)<br />

• φ100 <strong>for</strong> helium safety vent (feedthrough type C)<br />

Additional holes :<br />

• φ100 mm feedthrough <strong>for</strong> visual stimulus projector, center<br />

height 1000 mm above MSR inner floor (feedthrough type<br />

D). The visual stimulus projector is available as an option.<br />

• φ60 mm feedthrough <strong>for</strong> the optional intercom loudspeaker<br />

(feedthrough type E)<br />

.• φ35 mm hole <strong>for</strong> the optional CCTV camera (feedthrough<br />

type B)<br />

• Two φ120 mm holes / rectangular openings <strong>for</strong> ventilation<br />

(feedthrough type F)<br />

• φ35 mm hole <strong>for</strong> the lighting<br />

• One or two φ50 mm additional feedthroughs can be optionally<br />

provided <strong>for</strong> medical gases and patient monitoring devices<br />

such as a pulse oximeter. Alternatively, these feedthroughs<br />

can be fitted to the stimulus cabinet.<br />

The optimum hole locations vary according to the site. For<br />

details, contact <strong>Elekta</strong> representative, see also Section 6.1.<br />

User-supplied TV monitoring (CCTV) systems are not recommended<br />

to avoid RF-leakage via the camera and its cables.<br />

8 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> <strong>MaxShield</strong> shielded droom 1 2<br />

2.3. Door<br />

Doorstep:<br />

0.13 m. A ramp (approx. 1 m length, slope < 10°) is provided to<br />

ensure easy access <strong>for</strong> both the subjects during MEG-measurements<br />

and <strong>for</strong> the LHe storage container during a re-fill operation.<br />

Door mechanism:<br />

2.4. Inside / outside décor , lights, and accessories<br />

Mechanical, can be manually opened both from inside and<br />

outside. The door is provided with a stopper to limit the opening<br />

to approximately 90°. For possible door locations, see Sect. 6.1.<br />

Inside wall coverage<br />

Provided with light, sound-absorbing and electrically insulating<br />

material.<br />

Outside wall coverage<br />

Outside coverage is not provided as standard part as it normally<br />

needs to be matched with the style and look of the surroundings.<br />

A dry-wall made of light electrically insulating material and built<br />

on site after shielded room installation is recommended. The<br />

outside coverage must not be attached to the shielded room wall.<br />

Inside floor<br />

Provided with easy to clean laminate resistent to eventual minor<br />

leakage of condensation water from the He-cooled pipes inside<br />

the gantry.<br />

Loads on ceiling and walls<br />

Additional load to unsupported magnetic shield material must<br />

not be applied. Light objects can be attached to inside décor.<br />

Interior lighting<br />

Adjustable and dimmable halogen spots (DC operated)<br />

Accessories<br />

All accessories brought inside the room should be of nonmagnetic<br />

material. Large metallic conducting objects (area > 0.25 m 2 ) must<br />

be avoided.<br />

NM21643A 9


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

3<br />

3. CLIMATIC REQUIREMENTS<br />

Maintaining the specified environmental conditions is essential<br />

to ensure the stable functioning of the system. Note that the<br />

relative humidity requirements have to be taken into account<br />

simultaneously with the temperature.<br />

NOTE:<br />

During transportation and storage, the temperature of the <strong>Elekta</strong><br />

Neuromag MEG system must be between 0 – 40 ºC, and the<br />

relative humidity between 10 – 95 %, non-condensing.<br />

3.1. Room temperature in the shielded room, equipment area and operator area<br />

Excessively high room temperatures may cause overheating of<br />

the power components thus reducing component lifetimes.<br />

Requirement <strong>for</strong> the ambient temperature outside the shielded<br />

room including the equipment area and the operator area:<br />

T amb<br />

= 20 – 24 ºC.<br />

Approximate heat load in the equipment area is 2 kW and in the<br />

operator area 3 kW (not including stimulators). Exact heat load<br />

depends on system configuration. Refer to Section 4 <strong>for</strong> more<br />

in<strong>for</strong>mation on power consumption.<br />

Requirement <strong>for</strong> the air temperature inside the shielded room:<br />

T MSR<br />

= 20 – 28 ºC.<br />

Approximate heat load due to electronics inside the shielded<br />

room is 0.3 kW. Addtional heat is generated by the lights (0.2 kW<br />

at full brightness) and persons inside (0.1 kW per person). The<br />

heat transfer through the MSR wall depends on the wall covering,<br />

which effectively acts as thermal insulation. There<strong>for</strong>e, ventilation<br />

in the room should be designed to carry the heat away.<br />

NOTE:<br />

To maintain the temperature inside the shielded room below 28 ºC,<br />

cooling of the input air may be needed. The minimum capacity of<br />

the air input 30 liters/s, corresponding to temperature difference<br />

of 8 °C.<br />

10 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Climatic requirements 1 3<br />

3.2. Relative humidity in the shielded room, equipment area and operator area<br />

Excessive air humidity promotes oxidation of metals, can be<br />

detrimental to electric circuits and computers and increase leakage<br />

currents as well as may cause water to condense on the cold<br />

parts of the system. Low humidity in turn increases static electricity,<br />

which can interfere with the SQUID detectors and damage<br />

electronic circuits. It also causes discom<strong>for</strong>t to the users.<br />

Relative humidity limits:<br />

RH = 40% – 70%.<br />

To maintain the humidity within limits, humidification/dehumidication<br />

systems are normally necessary. Natural air humidity<br />

can vary substantially depending on local climate, from 10 % to<br />

over 90 %.<br />

NM21643A 11


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

4<br />

4. POWER SUPPLY AND GROUNDING REQUIREMENTS<br />

4.1. Power Requirements<br />

The power requirements of the system units are listed in Table 1.<br />

The applicable standard line voltages (RMS) are: 100, 115, 120,<br />

200, 215, 220, 230, and 240 V. The recommended voltages are 200,<br />

230, and 240 V. The nominal line frequency should be 50 or 60 Hz.<br />

Table 1. Power consumption of system units.<br />

The total consumption depends on system configuration.<br />

U nit<br />

P ower [W]<br />

Appar.<br />

[VA]<br />

Notes<br />

Main<br />

electronics cabinet<br />

1700/1900<br />

1800/2000<br />

64 ch EEG / 128 ch EEG<br />

Lifting<br />

unit<br />

10/750<br />

20/1200<br />

Idle/working (20 s / run)<br />

3-D digitizer<br />

40<br />

60<br />

Acq.<br />

workstation, 2 TFT monitors (typ.) 400<br />

Anal.<br />

workstation, 2 TFT monitors (typ.) 400<br />

Trigger<br />

I/O unit (2 pcs, total)<br />

20<br />

Voice<br />

intercom (typ.)<br />

10<br />

CCTV video monitoring (typ.)<br />

50<br />

Finger<br />

response pad<br />

10<br />

DAT drive (typ.)<br />

100<br />

MOD drive (typ.)<br />

100<br />

Color<br />

printer (typ.)<br />

250<br />

/1650<br />

Norm./max.<br />

Monochrome<br />

printer (typ.)<br />

30/600<br />

Idle/printing<br />

Video<br />

projector (typ.)<br />

800<br />

Electrical<br />

stimulator (typ.)<br />

10<br />

Audiovisual<br />

stimulus system (typ.)<br />

200<br />

Feed-<strong>for</strong>ward<br />

active compensation<br />

200<br />

Shielded<br />

room lights<br />

200<br />

Note 1<br />

Note 2<br />

Stimulus cabinet not included as a unit since the consumption depends on the equipment used. Max 10 A.<br />

Ratings marked with "typ." are representative values only, actual values depend on the exact model used<br />

NOTE: Power requirements <strong>for</strong> lighting outside the shielded<br />

room, air conditioning, and general purpose outlets are not<br />

included.<br />

12 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Power supply and grounding 1 4<br />

4.2. Connection to the building’s power lines, power requirements<br />

Separate power lines from the building’s main trans<strong>for</strong>mer and<br />

system isolation trans<strong>for</strong>mers are required, see Fig. 1. The isolation<br />

trans<strong>for</strong>mers (T 1<br />

and T 2<br />

) are provided by <strong>Elekta</strong>. They comply<br />

with the medical standards EN 60601-1 and EN 61558-2-15<br />

EN60742). The distance of the isolation trans<strong>for</strong>mers from the<br />

shielded room should normally be more than 3 m. For details,<br />

contact <strong>Elekta</strong>.<br />

At sites where the mains voltage is less than 230 V~ the lifting unit<br />

is connected to main using a portable step-up trans<strong>for</strong>mer provided<br />

with the system (plug connection).<br />

Power lines etc. cabling carrying substantial currents, power<br />

supplies, fluorescent lamps or other electric equipment should<br />

not be mounted on the shielded room walls or directly above the<br />

shielded room roof.<br />

MAINS<br />

L<br />

N<br />

PE<br />

S1<br />

S2<br />

F1<br />

L<br />

N<br />

PE<br />

L<br />

N<br />

PE<br />

Sockets <strong>for</strong><br />

workstations and<br />

other equipment<br />

(min. 10)<br />

System grounding point<br />

Filter Unit<br />

Grounding terminal in the<br />

trans<strong>for</strong>mer room<br />

S3<br />

100/115/120/<br />

200/230/240 V 230V<br />

T1<br />

F2 L<br />

N<br />

L1<br />

0<br />

L2<br />

F3<br />

S4<br />

F4<br />

Magnetically shielded room<br />

RF Filter Sockets<br />

L1<br />

S7<br />

L2<br />

PE<br />

S5<br />

0 S6<br />

N<br />

F7<br />

L = mains live<br />

L2<br />

N = mains neutral<br />

PE = protective earth (ground)<br />

L1 and L2 = isolated power terminals (symmetiric with respect to ground)<br />

Switches S7 and S8 are inside cabinets (max. 10A), supplied by <strong>Elekta</strong><br />

Secondary fuses (F3,F4,F6, F7) and switches (S4, S6) are optional<br />

F5<br />

L<br />

1:1<br />

T2<br />

L1<br />

F6<br />

Main electronics cabinet<br />

RF Filter Sockets<br />

L1<br />

S8<br />

L2<br />

PE<br />

Stimulus cabinet<br />

Figure 1. Connection to building’s power lines and grounding<br />

arrangements. The isolation trans<strong>for</strong>mers (T1–T2) and<br />

components inside cabniets are provided by <strong>Elekta</strong>.<br />

NM21643A 13


DRAFT<br />

4 Power supply and grounding <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

4.3. Grounding<br />

Proper grounding is essential in order to maintain shielding<br />

integrity. The guidelines listed below must be carefully followed.<br />

The magnetically shielded room (MSR) is grounded at one point<br />

only using a separate grounding cable connected to the common<br />

grounding terminal of the building trans<strong>for</strong>mer providing power<br />

to the <strong>Elekta</strong> Neuromag® system. The grounding cable should<br />

have a cross-section of 50 mm 2 or larger and it should be stranded<br />

(preferably fine-stranded) to ensure low inductance path to ground.<br />

The wire is connected to the M8 grounding bolt at the feedthrough<br />

filter unit during installation of the MEG system. The connection<br />

must be made in such a way that it can be disconnected when the<br />

isolation of the magnetically shielded room is measured. The<br />

isolation resistance between the disconneted shielded room and<br />

the end of the grounding cable must be more than 1 kΩ. The walls<br />

of the MSR must be electrically isolated from all building parts<br />

including the air conditioning ducts and helium exhaust pipes.<br />

All components of the electronics must be grounded to the same<br />

single point as the magnetically shielded room, see Figure 1.<br />

NOTE:<br />

A dedicated grounding electrode separate from the grounding<br />

terminal of the building trans<strong>for</strong>mer can be used but is not<br />

recommended.<br />

14 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

5<br />

5. VIBRATION CONSIDERATIONS<br />

5.1. General Recommendations<br />

Generally, the magnetically shielded room should be located at<br />

a place where low frequency vibrations are as small as possible.<br />

Thus, basements are preferred to upper floors.<br />

NOTE:<br />

Spring type suspension designs of the room are not recommended<br />

since they may cause low frequency oscillation.<br />

5.2. Recommendations <strong>for</strong> allowable vibration<br />

Magnetic interference signals due to mechanical vibrations are<br />

generated by the relative motion of the magnetic sensors with<br />

respect to the remanent field inside the room. A typical value of<br />

remanent field is ≤ 50 nT (see chapter 2.1.1). The magnetometers<br />

are more sensitive to the vibration than the gradiometers.<br />

General criteria <strong>for</strong> maximum allowable vibration observed in a<br />

site survey are difficult to define in practice. Vibration artefacts<br />

have often prominent peaks and if they happen to match with<br />

natural structural resonances of the room, the effect of building<br />

floor vibration may be augmented. Moreover, air pressure variations<br />

e.g. caused by ventilation can produce vibration artifacts.<br />

Magnetic artefact caused by vibration as such are relatively<br />

uni<strong>for</strong>m and is thus they are effectively reduced by software noise<br />

reduction based on spatial filtering like signal space projection<br />

and MaxFilter.<br />

The spectral density of the magnetic interference signal B vibr<br />

in a<br />

magnetometer channel due vibration is given by<br />

B vibr<br />

(f) ≤ X(f) B rem<br />

/ L 1<br />

,<br />

where<br />

X(f) = displacement spectrum of the magnetometer in the<br />

units of m/ Hz<br />

B rem<br />

L 1<br />

= remanent field inside the MSR (≤ 50 nT)<br />

= Characteristic length associated with the first<br />

gradient of the remanent magnetic field, typically<br />

L 1<br />

= 10 m.<br />

NM21643A 15


DRAFT<br />

5 Vibration considerations <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

5.3. Measurement of vibration<br />

The following conservative recommendations <strong>for</strong> the spectral<br />

density of the displacement spectrum at the site of the shielded<br />

room X amb<br />

are based on an assumption that disturbance due to<br />

vibrations is not seen in the magnetometer output spectrum when<br />

noise reduction techniques are not used.<br />

Displacement, Spectral Density (conservative recommendation)<br />

X amb<br />

≤ 20 µm/ Hz at 0.1 to 1 Hz<br />

X amb<br />

≤ 2 µm/ Hz at 1 to 10Hz<br />

X amb<br />

≤ 1 µm/ Hz above 10 Hz<br />

In case the readout of the vibration analyzer is in units of velocity,<br />

V amb<br />

, the corresponding criteria are:<br />

Velocity, Spectral Density (conservative recommendation)<br />

V amb<br />

≤ 12 (µm/s)/ Hz at 0.1 to 1 Hz<br />

V amb<br />

≤ 12 (µm/s)/ Hz at 1 to 10Hz<br />

V amb<br />

≤ 60 (µm/s)/ Hz ) at 10 Hz<br />

With proper signal-space noise reduction or by application of<br />

MaxFilter these values can be relaxed considerably. Thus<br />

exceeding these limits, especially only at certain frequencies, is<br />

not necessarily detrimental.<br />

The level of vibration is defined by measuring at different times<br />

of the day the displacement or velocity as functions of time, and<br />

calculating the corresponding spectra. If obvious sources of vibrational<br />

interference are in close vicinity of the measurement point, the<br />

measurements should be carried out both with the equipment on and<br />

with the equipment off.<br />

16 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

6<br />

6. BUILDING REQUIREMENTS<br />

6.1. Floor space requirements and layout considerations<br />

The minimum floor space requirement <strong>for</strong> the complete system<br />

is about 40 m 2 . Anyhow, it is recommended, if possible, to<br />

reserve an area of 60–70 m 2 to ensure optimal conditions to<br />

operate the system from both operator’s and patient’s/subject’s<br />

point of view. Examples of site layouts are shown in Figs. 2 and<br />

3. For other possibilities, contact <strong>Elekta</strong> representative. See also<br />

discussion below.<br />

Outer dimensions of a <strong>MaxShield</strong> shielded room are given in<br />

chapter 2. The exact dimension will depend on the exterior<br />

finish.<br />

9000<br />

Isolation<br />

trans<strong>for</strong>mers<br />

Storage <strong>for</strong><br />

liquid Helium<br />

etc.<br />

Printer<br />

Analysis<br />

PC<br />

MEG Equipment area<br />

Electr.<br />

cabinet<br />

Feedthrough<br />

Lifting<br />

unit<br />

filter<br />

1500<br />

PC<br />

Acquisition<br />

Stimulus control<br />

Stimulus<br />

cabinet<br />

6500<br />

Ramp<br />

HPI chair<br />

Patient preparation<br />

and head digitization<br />

MSR<br />

equipment<br />

area<br />

Video<br />

projector<br />

Figure 2. Example layout of a large <strong>Elekta</strong> Neuromag® site. The<br />

office furniture, PCs, peripherals, stimulation equipment, and<br />

liquid Helium containers shown <strong>for</strong> illustrational purposes in the<br />

figure are not part of the standard system. Another example<br />

layout <strong>for</strong> a smaller site is shown in Fig. 3.<br />

NM21643A 17


DRAFT<br />

6 Building requirements <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

The door can be either on the shorter or on the longer side in any<br />

corner, subject to the following constraints:<br />

• distance from nearest outside corner to free opening is approx.<br />

0.5 m, depending on exterior finish thickness (see Fig.<br />

4)<br />

• handedness of the door is selectable<br />

• the door opening should be as far from the sensor unit as<br />

possible.<br />

• there should be enough space in front of the shielded room<br />

door <strong>for</strong> the door to open, to position the ramp and transfer<br />

in and out the bed, chair, and and helium storage vessels etc.<br />

The electronics is preferably located at the shorter side of the<br />

room behind the sensor unit. If space does not permit, alternative<br />

locations are possible as illustrated in Fig. 5. The following<br />

constraints must, however, be met:<br />

• free access to the the feedthrough filter unit is needed from all<br />

three sides not facing the shielded room wall (min. 0.3 m<br />

space)<br />

• both front and back doors of the main electronics cabinet<br />

need to be accessed and opened<br />

7000<br />

Analysis<br />

Printer<br />

MEG Equipment area<br />

Electr.<br />

cabinet<br />

Feedthrough<br />

filter<br />

Lifting<br />

unit<br />

1500<br />

Isolation<br />

trans<strong>for</strong>mers<br />

Stimulus control<br />

Acquisition<br />

Stimulus<br />

cabinet<br />

6500<br />

Ramp<br />

Patient preparation<br />

and head digitization<br />

HPI chair<br />

Storage <strong>for</strong><br />

liquid Helium<br />

etc.<br />

Video<br />

projector<br />

Figure 3. Example layout <strong>for</strong> a small <strong>Elekta</strong> Neuromag® site.<br />

18 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Building requirements 1 6<br />

0.5 m<br />

0.5 m<br />

Figure 4. Possible door locations. For further details, see text.<br />

800<br />

Feedthrough<br />

filter<br />

Lifting unit<br />

500<br />

Lifting unit<br />

Electr.<br />

cabinet<br />

Electr.<br />

cabinet<br />

Feedthrough<br />

filter<br />

Stimulus<br />

cabinet<br />

Stimulus<br />

cabinet<br />

Video<br />

projector<br />

Video<br />

projector<br />

VARIANT A<br />

VARIANT B<br />

Figure 5. Examples of alternative electronics locations. For further<br />

details, see text.<br />

NM21643A 19


DRAFT<br />

6 Building requirements <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

6.2. Load distribution<br />

• main electronics cabinet and feedthrough filter unit must be<br />

adjacent due to cable length restriction<br />

• exact feedthrough hole locations are subject to constraints<br />

due to support structures of the room. Feedthrough filter unit<br />

is centered with respect to the signal feedthrough holes<br />

• the lifting unit must be near the room corner in order to avoid<br />

too steep curves of the Bowden cable transmitting the movement<br />

• the cabinets and the lifting unit are not symmetric<br />

The <strong>MaxShield</strong> shielded room can even be directly located<br />

against a wall at two sides. Such configuration may, however,<br />

require special arrangements.<br />

An adequate space <strong>for</strong> liquid Helium storage container must be<br />

reserved. An easy access from the storage area to the shielded<br />

room should be ensured as well. The diameter of a typical 100-<br />

liter storage Dewar is 0.6–0.7 m and height 1.3–1.5 m.<br />

It is advisable to have an area <strong>for</strong> changing clothes and <strong>for</strong> waiting<br />

available in the near vivinity (not necessarily adjacent ot the MEG<br />

equipment area.<br />

Head digitization station should be near the data acquisition<br />

workstation or a dedicated additional terminal (PC). The analysis<br />

workstation does not need to have to be in the same area as the<br />

acquisition but it can also be remotely located.<br />

The total weight of the <strong>MaxShield</strong> shielded room with the<br />

system inside is typically 5000 kg. The weight is distributed<br />

approximately as follows:<br />

• Room floor and measurement unit: 1500 kg distributed<br />

evenly over the room area (12 m 2 )<br />

• Room walls and roof: 3500 kg distributed evenly on a 70 mm<br />

wide edge around the room area<br />

The room may be assembled on an underlayment (e.g. plywood)<br />

to distribute the load more evenly. In addition, the electronics<br />

cabinets need to be taken into account as approximately pointlike<br />

loads. For details, see Table 2.<br />

Conventionally, the load is expressed as the intensity of distributed<br />

load (average floor load). It is determined by calculating the<br />

intensity of a load evenly distributed over the whole external floor<br />

base plate which results in equal maximum deflection or maxi-<br />

20 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Building requirements 1 6<br />

6.3. Free ceiling height requirements<br />

6.3. Exhaust vents<br />

6.4. Transportation and access during installation<br />

mum principal bending moment as the load under investigation.<br />

Generally, the simple calculation of dividing the shielded room<br />

total mass by the shielded room area gives a too high value; <strong>for</strong><br />

proper determination the base plate properties need to be taken<br />

into account.<br />

The room can optionally be secured to the floor if required by<br />

local regulations (e.g. as a precaution <strong>for</strong> earthquakes).<br />

The installation of the <strong>MaxShield</strong> shielded room requires a<br />

clearance of 50 mm above the room exterior height.<br />

A free height of 1.50 m above the top opening of the liquid He<br />

storage containers should be available in the vicinity of the<br />

shielded room <strong>for</strong> the insertion of the LHe transfer siphon. If a<br />

siphon extention is used the length of the extension (0.22 m <strong>for</strong> the<br />

standard extension) should be added. The minimum area <strong>for</strong> this<br />

height is 1 m 2 . In operator area and equipment area there are no<br />

other special requirements.<br />

Provision must be made <strong>for</strong> a φ100 mm safety exhaust duct<br />

directly to the outside of the building.<br />

An area to unload the crates and an adequate access to the<br />

unloading area and from unloading area to the site must be<br />

provided during the installation of the system. The access route<br />

should not contain steps as many components are so heavy that<br />

<strong>for</strong>klifts (pallet jacks) must be used. Any door openings, corridors<br />

etc. should be wide and high enough that the crates and unloaded<br />

components can be transferred.<br />

All crates are to be transported in their original orientation whilst<br />

the components can be carried in any orientation (vertical/horisontal)<br />

which is convenient <strong>for</strong> access. The only exception is the<br />

MEG measurement unit which must always be kept in vertical<br />

orientation. Thus, a minimum height clearance of 2.00 m is<br />

required all the way, including all door openings.<br />

The largest crates <strong>for</strong> the LMSR are 3.2 m × 0.9 m × 0.9 m, 2.6 m<br />

× 1.8 m × 0.7 m, and 5.0 m × 0.3 m × 0.3 m, 7 crates total.<br />

Correspondingly, the largest crates <strong>for</strong> MEG components are 1.6<br />

m × 1.2 m × 2.3 m and 2.5 m × 0.9 m × 1.1 m (LxWxH), 7 crates<br />

total.<br />

NM21643A 21


DRAFT<br />

6 Building requirements <strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

Largest single shielded room elements that need to be transported<br />

from the unloading area to site are 1.6 m × 0.3 m × 2.3 m and 2.4<br />

m × 0.6 m × 0.1 m, and largest MEG components are 1.0 m x 1.3<br />

m x 2.0 m and 0.6 m × 0.8 m × 2.1 m.<br />

6.5. Dimensions of the main components of the MEG system<br />

6.6. Other considerations<br />

The dimensions of the main components of the system are listed<br />

in Table 2.<br />

A water faucet and sink is recommended in the patient preparation<br />

are.<br />

When designing the MEG area local regulations must be taken<br />

into account. These may include building, electrical and HVAC<br />

regulations as well as and possible requirements <strong>for</strong> hospital<br />

environment and occupational health.<br />

A smoke detector should be installed in the ventilation exhaust<br />

duct to monitor the inside of the shielded room. Installation of a<br />

fire detector inside the room is not recommended to prevent RF<br />

leakage through the detector cabling.<br />

Table 2. The dimensions of the components of the <strong>Elekta</strong><br />

Neuromag® system.<br />

Unit<br />

Width<br />

(cm)<br />

Depth<br />

(cm)<br />

Height<br />

(cm)<br />

Weight<br />

(kg)<br />

Measurement<br />

unit (supine/upright) 96<br />

128/160<br />

198/223<br />

350<br />

Patient<br />

bed (bed surface/maximum) 75<br />

230<br />

60/76<br />

75<br />

Patient<br />

chair<br />

70<br />

135<br />

78<br />

80<br />

Filter<br />

unit (adjustable height)<br />

100<br />

40<br />

150-190<br />

150<br />

MEG electronics cabinet<br />

60<br />

80<br />

212<br />

250<br />

Stimulus<br />

electronics cabinet<br />

60<br />

80<br />

202<br />

100<br />

Data<br />

acquisition workstation (min./typ.) 44/70<br />

57/75<br />

68<br />

25<br />

Data<br />

analysis workstation (min./typ.) 44/70<br />

57/75<br />

68<br />

20<br />

Monitors<br />

(typical 19" TFT, four pcs.) 41<br />

20<br />

46<br />

4 x 9<br />

Gantry<br />

lifting unit<br />

37<br />

64<br />

37<br />

30<br />

HPI<br />

chair + digitizing unit<br />

54<br />

56<br />

98<br />

10<br />

Back-projection<br />

screen<br />

118<br />

33/<br />

6 186<br />

35<br />

22 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

7<br />

7. TELECOMMUNICATION FACILITIES ON SITE<br />

For software installation and upgrades, possible troubleshooting,<br />

and maintenance, the site should be equipped with a remote<br />

access over tcp/ip -connection or with an ISDN line. Proper data<br />

security precautions such as dedicated firewall setups etc. should,<br />

however, be implemented.The data connection is needed already<br />

during the installation, as well as an ordinary telephone line.<br />

Computers of the MEG system are connected to ethernet network<br />

with twisted pair (UTP, CAT 5) cable. The cabling and<br />

location <strong>for</strong> network switch should be ready be<strong>for</strong>e the installation<br />

starts. For best per<strong>for</strong>mance the network should be a separate<br />

subnet. Following in<strong>for</strong>mation is needed <strong>for</strong> installation: the<br />

intended IP addresses of all devices, the network mask, the IP<br />

address of the gateway to external networks, the domain name<br />

and the IP address of the domain name server.<br />

If an official registered network is unavailable, the network<br />

addresses can be selected from non-routed internal network<br />

addresses. For details contact <strong>Elekta</strong>.<br />

NM21643A 23


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong><br />

A<br />

APPENDIX<br />

MEG-MRI layout considerations<br />

The following discussion illustrates the issues that have to be<br />

taken into account when locating the MEG unit and an MRI unit<br />

close to each other.<br />

In an ideal situation the axis of the bore of the MRI unit should<br />

be parallel to the longer wall of the shielded room of the MEG<br />

unit. Additionally, the electronics cabinets of the MRI device<br />

should be as far away from the MEG unit as possible, as shown<br />

in Figs. A1 and A2. The purpose of these arrangements is to<br />

minimize, inside the magnetically shielded room, the effect of fast<br />

switching electromagnetic pulses of the MRI unit that are due to<br />

the gradient amplifiers. The permanent magnetic field generated<br />

by the MRI is not considered harmful to the operations of the<br />

MEG unit as long as we are beyond the 50-mT (0.5 G) line.<br />

Equipment area<br />

of the MEG unit<br />

RF-shield<br />

Magnetically<br />

shielded room<br />

MEG<br />

MRI<br />

Equipment area<br />

of the MRI unit<br />

Recommended minimum distance 10 meters<br />

Figure A1. The axis of the bore of t he MRI unit should preferably<br />

be parallel to the longer wall of the magnetically shielded room.<br />

If this is not possible, an alternative layout is shown in Fig. A2. It<br />

is recommended to locate the equipment area of the MRI unit as<br />

far away from the magnetically shielded room as possible.<br />

24 NM21643A


DRAFT<br />

<strong>Elekta</strong> Neuromag® <strong>Site</strong> <strong>Planning</strong> <strong>Guide</strong> <strong>for</strong> <strong>MaxShield</strong> Appendix 1 A<br />

Equipment area<br />

of the MEG unit<br />

Magnetically<br />

shielded room<br />

MEG<br />

Recommended minimum distance 10 meters<br />

MRI<br />

RF-shield<br />

Equipment area<br />

of the MRI unit<br />

Recommended minimum distance 10 meters<br />

Figure A2. Recommended layout if the axis of the MRI unit is not<br />

parallel to the longer wall of the magnetically shielded room. As<br />

in the previous layout above it is recommended to locate the<br />

equipment area of the MRI unit as far away from the magnetically<br />

shielded room as possible.<br />

NM21643A 25


<strong>Elekta</strong> Neuromag Oy<br />

P.O. Box 68<br />

FIN-00511 Helsinki, Finland<br />

Tel: +358 9 756 2400<br />

Fax: +358 9 756 24011<br />

E-mail: neuromag@elekta.com<br />

Web: www.elekta.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!