TESTING & CERTIFICATION<br />
Furutec Busduct system has been tested and certified to IEC 60439-1<br />
and IEC 60439-2 certified by ASTA and TÜV SÜD PSB.<br />
PSB Singapore<br />
Verification of Temperature Rise Limit<br />
The following pictures illustrate some temperature rise tests successfully carried out on Furutec busduct system.<br />
Furutec Busduct System is capable of carrying full rated current continuously in ambient condition of 95% relative humidity and<br />
maximum ambient temperature of 40 o C. When busduct is installed in a higher ambient temperature, the busduct current ratings<br />
shall be derated according to the factors as illustrated in the table below.<br />
Ambient Temperature o C<br />
40<br />
45<br />
50<br />
55<br />
60<br />
65<br />
70<br />
Derating Factor<br />
1.00<br />
0.95<br />
0.90<br />
0.85<br />
0.80<br />
0.74<br />
0.67<br />
Verification of Dielectric Properties<br />
It comprises two tests, namely dielectric test voltage and impulse voltage withstand test. They are applied to all live parts and<br />
interconnected exposed conductive parts of the busduct system.<br />
For the impulse voltage withstand test, the busduct is tested with a test voltage of 7.4kVpk. The 1.2/50µs impulse voltage applied<br />
3 times at the interval of 1s minimum.<br />
For the dielectric test voltage, it is carried out after the type tests, such as temperature rise test, short circuit strength test, degree<br />
of protection test, structural strength test, crushing resistance test, etc in order to ensure that no electricity current leaking occurs.<br />
06 | TESTING & CERTIFICATION