TESTING & CERTIFICATION<br />

Furutec Busduct system has been tested and certified to IEC 60439-1<br />

and IEC 60439-2 certified by ASTA and TÜV SÜD PSB.<br />

PSB Singapore<br />

Verification of Temperature Rise Limit<br />

The following pictures illustrate some temperature rise tests successfully carried out on Furutec busduct system.<br />

Furutec Busduct System is capable of carrying full rated current continuously in ambient condition of 95% relative humidity and<br />

maximum ambient temperature of 40 o C. When busduct is installed in a higher ambient temperature, the busduct current ratings<br />

shall be derated according to the factors as illustrated in the table below.<br />

Ambient Temperature o C<br />

40<br />

45<br />

50<br />

55<br />

60<br />

65<br />

70<br />

Derating Factor<br />

1.00<br />

0.95<br />

0.90<br />

0.85<br />

0.80<br />

0.74<br />

0.67<br />

Verification of Dielectric Properties<br />

It comprises two tests, namely dielectric test voltage and impulse voltage withstand test. They are applied to all live parts and<br />

interconnected exposed conductive parts of the busduct system.<br />

For the impulse voltage withstand test, the busduct is tested with a test voltage of 7.4kVpk. The 1.2/50µs impulse voltage applied<br />

3 times at the interval of 1s minimum.<br />

For the dielectric test voltage, it is carried out after the type tests, such as temperature rise test, short circuit strength test, degree<br />

of protection test, structural strength test, crushing resistance test, etc in order to ensure that no electricity current leaking occurs.<br />

06 | TESTING & CERTIFICATION