Fire Resistance Test<br />

Furutec Fire Rated Busduct is designed for essential electrical services. It is tested to JIS A 1304, BS 6387 (Adoption)<br />

and IEC 60331 (Adoption)<br />

Polyester Film<br />

Mica Tape<br />

Mylar Polyester Film<br />

Conductor<br />

Fire-Rated Mica Tape<br />

Conductor<br />

Resistance to Fire Alone<br />

IEC 60331 : 3 hours at 750°C<br />

BS 6387 Category ‘C’ : 3 hours at 950°C<br />

JIS A 1304 : 30 mins at 840°C<br />

Resistance to Fire with Water<br />

BS 6387 Category ‘W’ : 15 mins at 650°C (with water spray 15 mins)<br />

JIS A1304<br />

Fire resistance test has been conducted on Furutec busduct system with joint<br />

section in an independant testing authority.<br />

Flame Temperature : 840°C<br />

Test Voltage<br />

: 660 V<br />

Test Duration<br />

: 30 mins<br />

Test Furnace<br />

: Large scale fire resistant furnace, where the busduct<br />

is heated up to 840°C from all directions.<br />

BS 6387:1994 Category ‘C’<br />

Resistance to fire alone test has been conducted on Furutec busduct feeder<br />

and joint section in an independant testing authority.<br />

Flame Temperature : 950 °C<br />

Test Voltage<br />

: 660V<br />

Test Duration<br />

: 3 hours<br />

12 | TESTING & CERTIFICATION