Fire Resistance Test<br />
Furutec Fire Rated Busduct is designed for essential electrical services. It is tested to JIS A 1304, BS 6387 (Adoption)<br />
and IEC 60331 (Adoption)<br />
Polyester Film<br />
Mica Tape<br />
Mylar Polyester Film<br />
Conductor<br />
Fire-Rated Mica Tape<br />
Conductor<br />
Resistance to Fire Alone<br />
IEC 60331 : 3 hours at 750°C<br />
BS 6387 Category ‘C’ : 3 hours at 950°C<br />
JIS A 1304 : 30 mins at 840°C<br />
Resistance to Fire with Water<br />
BS 6387 Category ‘W’ : 15 mins at 650°C (with water spray 15 mins)<br />
JIS A1304<br />
Fire resistance test has been conducted on Furutec busduct system with joint<br />
section in an independant testing authority.<br />
Flame Temperature : 840°C<br />
Test Voltage<br />
: 660 V<br />
Test Duration<br />
: 30 mins<br />
Test Furnace<br />
: Large scale fire resistant furnace, where the busduct<br />
is heated up to 840°C from all directions.<br />
BS 6387:1994 Category ‘C’<br />
Resistance to fire alone test has been conducted on Furutec busduct feeder<br />
and joint section in an independant testing authority.<br />
Flame Temperature : 950 °C<br />
Test Voltage<br />
: 660V<br />
Test Duration<br />
: 3 hours<br />
12 | TESTING & CERTIFICATION