Measure Information Template Page 22<br />

o<br />

Add: (a) Nonresidential Occupancies. Buildings with building category designated as<br />

“restaurant” or area category as “dining”and a total square footage (conditioned floor<br />

area & non-conditioned floor area) of 12,500, may install a natural gas water heater if<br />

the water heater is located within the building envelope and the minimum percent of<br />

the energy for water heating is provided by a passive or active solar system as specified<br />

in Table__:<br />

Climate<br />

Zone<br />

<strong>Solar</strong><br />

Fraction<br />

Table __<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />

.34 .37 .36 .38 .38 .37 .38 .38 .39 .39 .39 .37 .38 .4 .42 .37<br />

Climate<br />

Zone<br />

<strong>Solar</strong><br />

Fraction<br />

Table __<br />

Buildings with building category designated as “restaurant” or area category as<br />

“dining”and a total square footage (conditioned floor area & non-conditioned floor<br />

area) of 1,500, may install an electric storage water heater if the water heater is located<br />

within the building envelope and the minimum percent of the energy for water heating<br />

is provided by a passive or active solar system as specified in Table __.<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />

A service water heating system installed in this building type and all nonresidential<br />

buildings complies with this section if it also complies with the applicable<br />

requirements of Sections (111,113 and 123).<br />

NON-RESIDENTIAL COMPLIANCE MANUAL:<br />

● Section 4.7<br />

o Modify: All of the requirements for service hot water are mandatory measures, except<br />

for restaurants and dining facilities that must comply with §145(a), and high-rise<br />

residential, hotels and motels that must comply with the l Residential Standards<br />

§151(f)8. These requirements are described in the Residential Compliance Manual.<br />

Section 4.7.1.<br />

o Insert: Natural Gas Storage Restaurants or Dining<br />

§145(a)<br />

Buildings with building category designated as “restaurant” or area category as<br />

“dining”and a total square footage (conditioned floor area & non-conditioned floor<br />

area) of 12,500, may install a natural gas water heater if the water heater is located<br />

2013 California Building Energy Efficiency Standards March 2011