Measure Information Template Page 22<br />
o<br />
Add: (a) Nonresidential Occupancies. Buildings with building category designated as<br />
“restaurant” or area category as “dining”and a total square footage (conditioned floor<br />
area & non-conditioned floor area) of 12,500, may install a natural gas water heater if<br />
the water heater is located within the building envelope and the minimum percent of<br />
the energy for water heating is provided by a passive or active solar system as specified<br />
in Table__:<br />
Climate<br />
Zone<br />
<strong>Solar</strong><br />
Fraction<br />
Table __<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />
.34 .37 .36 .38 .38 .37 .38 .38 .39 .39 .39 .37 .38 .4 .42 .37<br />
Climate<br />
Zone<br />
<strong>Solar</strong><br />
Fraction<br />
Table __<br />
Buildings with building category designated as “restaurant” or area category as<br />
“dining”and a total square footage (conditioned floor area & non-conditioned floor<br />
area) of 1,500, may install an electric storage water heater if the water heater is located<br />
within the building envelope and the minimum percent of the energy for water heating<br />
is provided by a passive or active solar system as specified in Table __.<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />
A service water heating system installed in this building type and all nonresidential<br />
buildings complies with this section if it also complies with the applicable<br />
requirements of Sections (111,113 and 123).<br />
NON-RESIDENTIAL COMPLIANCE MANUAL:<br />
● Section 4.7<br />
o Modify: All of the requirements for service hot water are mandatory measures, except<br />
for restaurants and dining facilities that must comply with §145(a), and high-rise<br />
residential, hotels and motels that must comply with the l Residential Standards<br />
§151(f)8. These requirements are described in the Residential Compliance Manual.<br />
Section 4.7.1.<br />
o Insert: Natural Gas Storage Restaurants or Dining<br />
§145(a)<br />
Buildings with building category designated as “restaurant” or area category as<br />
“dining”and a total square footage (conditioned floor area & non-conditioned floor<br />
area) of 12,500, may install a natural gas water heater if the water heater is located<br />
2013 California Building Energy Efficiency Standards March 2011