15.01.2015 Views

GM 901 CO Analyzer for the Emission Monitoring and Process Control

GM 901 CO Analyzer for the Emission Monitoring and Process Control

GM 901 CO Analyzer for the Emission Monitoring and Process Control

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Product Publikationstyp<br />

In<strong>for</strong>mation<br />

<strong>GM</strong> <strong>901</strong><br />

<strong>CO</strong> <strong>Analyzer</strong> <strong>for</strong> <strong>the</strong> <strong>Emission</strong><br />

<strong>Monitoring</strong> <strong>and</strong> <strong>Process</strong> <strong>Control</strong><br />

Application<br />

The <strong>GM</strong> <strong>901</strong> <strong>Analyzer</strong> serves <strong>for</strong><br />

instant <strong>and</strong> non-contact measurements<br />

(cross stack) of carbon monooxide<br />

concentrations, <strong>for</strong> example, <strong>for</strong><br />

optimizing combustion processes. The<br />

<strong>GM</strong> <strong>901</strong> is available as a cross-stack<br />

or probe version. As a result it is suited<br />

to a broad range of applications<br />

– even <strong>for</strong> difficult measuring tasks<br />

such as high dust loads, overpressure,<br />

critical flow profiles or high measuring<br />

gas concentrations.<br />

Field of Applications<br />

■ Power plants<br />

■ Coal processing industry<br />

■ Cement industry<br />

■ Waste incineration plants<br />

■ Paper <strong>and</strong> pharmaceutical industry<br />

■ Steel <strong>and</strong> glass industry<br />

■ Chemical <strong>and</strong> food industry<br />

Device Overview<br />

■ <strong>GM</strong> <strong>901</strong> Cross stack with <strong>the</strong> components:<br />

– sender with wea<strong>the</strong>rproof cover<br />

– receiver with wea<strong>the</strong>rproof cover<br />

– evaluation unit<br />

■ <strong>GM</strong> <strong>901</strong> probe version with:<br />

– sender/receiver unit<br />

– GPP measuring probe (gas<br />

permea ble probe; verifiable<br />

using test gases) or<br />

– <strong>GM</strong>P probe (open aperture;<br />

purge air supply necessary)<br />

– evaluation unit<br />

■ Options:<br />

– PROFIBUS<br />

– optical alignment unit, <strong>CO</strong> test<br />

cells, mounting flange, PT 100<br />

sensor<br />

– purge air unit <strong>for</strong> cross-stack<br />

version <strong>and</strong> <strong>GM</strong>P probe <strong>for</strong><br />

cooling <strong>and</strong>/or protection of <strong>the</strong><br />

sender <strong>and</strong> receiver<br />

Key Features<br />

■ Rapid, easy installation, commission<br />

<strong>and</strong> project planning<br />

■ Verifiable with test gases (GPP<br />

probe) or filled test cells<br />

■ User-friendly operation directly<br />

on <strong>the</strong> evaluation unit<br />

■ Measuring values, measuring<br />

range <strong>and</strong> limit value indication<br />

directly on <strong>the</strong> graphical display<br />

■ Extremely low maintenance<br />

requirements<br />

■ No test gas necessary<br />

■ Evaluation unit can be installed<br />

up to a distance of 1,000 m<br />

(3,200 ft) from <strong>the</strong> measuring<br />

point (e.g. control room)


Measuring<br />

<strong>CO</strong><br />

Measuring<br />

<strong>CO</strong><br />

Operation<br />

Service<br />

Warning<br />

Malfunction<br />

<strong>GM</strong><strong>901</strong><br />

Evaluation Unit<br />

Operation<br />

<strong>GM</strong> <strong>901</strong><br />

Service<br />

Evaluation Unit<br />

Warning<br />

Malfunction<br />

<strong>GM</strong> <strong>901</strong> Cross stack<br />

Sender<br />

Receiver<br />

1)<br />

CAN bus: max. length<br />

1,000 m (3,200 ft)<br />

1245 ppm<br />

EVU<br />

Evaluation<br />

unit<br />

115/230 V power supply<br />

PROFIBUS<br />

Analog/binary signals<br />

1)<br />

CAN bus <strong>GM</strong> <strong>901</strong><br />

connection<br />

cable<br />

SLV 4<br />

purge air<br />

unit<br />

<strong>GM</strong> <strong>901</strong> Probe Version<br />

1)<br />

CAN bus: max. length<br />

1,000 m (3,200 ft)<br />

1245 ppm<br />

EVU<br />

Evaluation<br />

unit<br />

Sender/receiver unit<br />

115/230 V power supply<br />

PROFIBUS<br />

Analog/binary signals<br />

CAN bus 1)<br />

20 mA (temp.)<br />

GPP measuring probe<br />

115/230 V power supply<br />

Technical Data <strong>GM</strong> <strong>901</strong><br />

Measurement data <strong>GM</strong> <strong>901</strong> Cross stack <strong>GM</strong>P Measuring Probe GPP Measuring Probe<br />

Measuring principle<br />

Measuring range <strong>CO</strong><br />

■ minimum range<br />

■ maximum range<br />

Accuracy<br />

gas filter correlation<br />

0…500 ppm • m<br />

0…20,000 ppm • m<br />

± 5 % of measuring end value (full scale)<br />

Measuring distance <strong>GM</strong> <strong>901</strong>-05:<br />

0.5…8 m (1.6…26 ft)<br />

active aperture 200…700 mm (8…28 in)<br />

probe length 1.1 m (3.3 ft)<br />

0…100 ppm • m<br />

0…20,000 ppm • m<br />

Response time<br />

5…360 s (sec)<br />

Plant data <strong>GM</strong> <strong>901</strong> Cross stack <strong>GM</strong>P Measuring Probe GPP Measuring Probe<br />

Measuring gas temperature up to 250 °C (480 °F), st<strong>and</strong>ard;<br />

up 220 °C (430 °F) 3)<br />

max. 300 °C (570 °F); o<strong>the</strong>r on request<br />

max 260 °C (500 °F) 4)<br />

8 008 876/01-205 • DIV03/SM • Printed in Germany (11-2003) . Subject to change without prior notice<br />

Ambient temperature<br />

–20…+55 °C (–4…+133 °F)<br />

Measuring gas pressure dependent on purge air blower (