<strong>Alco</strong> <strong>Controls</strong><br />
Technical Data<br />
Supply Voltage Nominal 24 Vdc Sensor lifetime<br />
Range (polarity protected) 8... 30 Vdc at full stroke at 25°C > 5.000.000 cycles<br />
Operating current max. 20 mA output Burst pressure >150 bar<br />
Protection class acc. to EN 60529 IP65 Medium compatibility HFC, HCFC<br />
Load resistance<br />
U B<br />
- 8.0V<br />
not suitable for ammonia and<br />
R L<br />
≤<br />
0.02A<br />
inflammable refrigerants!<br />
Temperatures<br />
Materials<br />
Operating ambient housing -40.....80 °C Housing cover, pressure connector, Stainless steel<br />
Medium -50...135 °C diaphragm with medium contact 1.4435 / AISI 316L<br />
Transportation and storage -40.....85 °C Vibration at 10 ... 2000 Hz max. 4 g<br />
Accuracy Performance<br />
Temperature range Total error*<br />
PT4-07M -40 ... +80°C ≤ ± 1 % FS<br />
PT4-18M -20 ... +80°C ≤ ± 1 % FS<br />
PT4-30M 0 ... +40°C ≤ ± 1 % FS<br />
-20 ... +60°C ≤ ± 2 % FS<br />
-40 ... +80°C typically ≤ ±2 % FS<br />
PT4-50M 0 ... +40°C ≤ ± 1 % FS<br />
-20 ... +60°C ≤ ± 2 % FS<br />
-30 ... +80°C typically ≤ ±2 % FS<br />
*) Total error includes non-linearity, hysteresis, repeatability as well as offset and span<br />
drift due to the temperature changes.<br />
Note: % FS is related to Percentage of Full sensor Scale.<br />
Electrical connection<br />
Pressure transmitters PT4 with current output (2-wire connection)<br />
offer following advantages:<br />
1. More suitable for signal transmission over long<br />
distances<br />
2. Higher immunity to electromagnetic interference<br />
Note: Changing the length of the electrical connection<br />
lead beyond 1.5 m can have a negative impact on electromagnetic<br />
compatibility. Additional protection may be<br />
required.<br />
Electronic Controller<br />
BN = brown, supply voltage 24V<br />
WH = white, output signal 4 … 20mA<br />
(5) = Electronic Controller e.g. EC2 & EC3 Series<br />