EFFICIENCY AND DRIVE POWER<br />
SECTION 4331<br />
January, 1990<br />
The selection of a suitable size of prime mover for an a.c. generator is governed by the electrical power output<br />
supplied to the load and the efficiency of the a.c. generator. The relationship is given below:-<br />
Where:-<br />
kW drive input = kW output<br />
η a<br />
“kW drive input” defines the prime mover power rating in kilowatts<br />
“kW output” defines the electrical power supplied to the load (usually the continuous maximum industrial power rating<br />
of the a.c. generator).<br />
“ η a” is the efficiency in ‘per unit’ of the a.c. generator.<br />
To convert kW input into Horsepower (h.p.) or Cheval Vapeur (C.V.)/Pfedestarke (PS) the following conversations<br />
constants should be used.<br />
h.p. = kW input<br />
0.746<br />
C.V. or PS = kW input<br />
0.735<br />
In special circumstances the prime mover size may need to be larger than specified above, to copy with particular<br />
overload or transient conditions. Consideration of motor load starting torque can be especially relevant when determining<br />
prime mover size.<br />
The efficiencies of Stamford a.c. generators are given in individual data sheets in Section 6.