20.01.2015 Views

IVS Sensorless Pump Commissioning Check ... - Armstrong Pumps

IVS Sensorless Pump Commissioning Check ... - Armstrong Pumps

IVS Sensorless Pump Commissioning Check ... - Armstrong Pumps

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FILE NO.: 94.202<br />

DATE: Sep. 14, 2010<br />

SUPERSEDES: 94.202<br />

DATE: June 2, 2010<br />

<strong>IVS</strong> <strong>Sensorless</strong> <strong>Pump</strong> <strong>Commissioning</strong> <strong>Check</strong> Sheet<br />

The following is a step-by-step guide to starting up and commissioning an <strong>Armstrong</strong> <strong>IVS</strong> <strong>Sensorless</strong> <strong>Pump</strong>. One check sheet is to<br />

be completed per pump! You must follow and fill out all fields below to ensure that all aspects of the pump are checked and setup<br />

for proper operation. This sheet must be returned to <strong>Armstrong</strong> along with the “<strong>IVS</strong> Startup Data Sheet” for the startup to be<br />

considered as complete! Once complete, this sheet requires that end-user / general contractor sign off on the work rendered as<br />

final approval that the pumps function as intended. Please submit this commissioning check sheet along with your work invoice /<br />

startup claim in order to ensure prompt and timely payment of work rendered!<br />

NO CHECK SHEET + STARTUP DATA SHEET = INCOMPLETE STARTUP!<br />

UNLESS STATED OTHERWISE ALL FIELDS ARE MANDATORY!<br />

ONE SET PER DRIVE+PUMP!<br />

Project Name:<br />

Building Address:<br />

Contractor Name:<br />

Site Contact Name: Site Contact Tel. #:<br />

Your Company:<br />

Your Name:<br />

<strong>Pump</strong> Model: <strong>Pump</strong> Tag #:<br />

<strong>Pump</strong> Serial #: Sales Order #:<br />

NOTES:<br />

- GC = General Contractor<br />

- BAS = Building Automation System<br />

Pre-Startup Package:<br />

Yes No N/A<br />

Do you have the pump Order Annexe<br />

Do you have the pump-specific variable speed curve with duty point indicated<br />

Do you have the <strong>Sensorless</strong> VFD setup file<br />

Do you have the <strong>Sensorless</strong> Datafile (csv file)<br />

OPTIONAL: Do you have the pump Installation & Operation Manual<br />

Pre-Startup Arrangements:<br />

Yes No N/A<br />

Verify with GC that water and power is available and ready to the pump<br />

Verify with GC that piping system valves can be opened to 100% to simulate full load<br />

Verify with GC that pumps can be run without damage to system<br />

Verify with GC that BAS is wired to drive and ready to go (IF APPLICABLE)<br />

Verify with GC that BAS contractor will be there on site to meet you (IF APPLICABLE)<br />

Before Power Up <strong>Check</strong>list:<br />

Done<br />

<strong>Check</strong> pump installation for proper mounting as per <strong>Pump</strong> Installation & Operation Manual instructions<br />

<strong>Check</strong> incoming voltage across the lines and record here: L1 ________ L2 ________ L3 ________<br />

Note: Voltage should be no more than +/- 10% of design voltage<br />

<strong>Check</strong> if pump is to be controlled remotely by BAS start / stop contact with BAS contractor:<br />

Option #1: If yes, check if BAS contact is wired across terminals 12 & 18 on VFD<br />

Option #2: If no, check if factory jumper is wired across terminals 12 & 18 on VFD<br />

Note: Contacts close = pump runs. Contacts open = pump stops.<br />

Open up and bleed pump seal flush line to verify no air is locked inside seal / seal lines<br />

<strong>Check</strong> alignment of pump (horizontally mounted pumps only)<br />

<strong>Check</strong> if piping system valves are opened to 100% to simulate full design load and that they stay that way<br />

Unit is now safe to turn power on.<br />

Page 1 of 3


Startup <strong>Check</strong>list:<br />

Done<br />

Verify <strong>IVS</strong> drive has completed proper bootup sequence<br />

Verify <strong>IVS</strong> drive is in the OFF mode (if not – place in OFF mode)<br />

Note: If this is a Dual Arm, make sure both <strong>IVS</strong> drives are in OFF!<br />

<strong>Check</strong> parameter 20-69.0 through 20-69.9 to verify if <strong>Sensorless</strong> data is programmed (it will show pump<br />

size, serial number, etc.)<br />

Put pump in HAND mode and run at 15Hz and looking from the top of the motor down, verify motor<br />

rotation as per the sticker on the motor (should be clockwise from top of the motor looking down)<br />

Open up and bleed pump seal flush line again to verify no air has travelled into seal / seal lines<br />

Change parameter 0-22 (default value is option 1610 – “Power [kW]”) to option 1654 “Feedback 1 [Unit]”<br />

to display <strong>Sensorless</strong> pressure readout on the top right corner of screen<br />

FOR DUAL ARMS: Close and secure the flapper valve so that it isolates the pump you are not using<br />

Close the discharge valve at the immediate outlet of the pump to deadhead pump<br />

With pump in HAND mode, increase the speed of the pump to the design speed as per the duty curve in<br />

your startup package. Eg: If your duty speed is 1550 RPM and you have a 1740 RPM, 60Hz motor, you<br />

will need to run at: 1550/1740 x 60Hz = 53.4 Hz<br />

Record the readout from suction and discharge gauges (include units)<br />

SUCTION = DISCHARGE =<br />

Verify the pump dP on deadhead (discharge valve is shut) is the same as shown on the duty curve<br />

Record VFD <strong>Sensorless</strong> pressure readout (include units)<br />

SENSORLESS PRESSURE =<br />

Verify that VFD <strong>Sensorless</strong> pressure readout is within +/- 5% compared to gauge readout<br />

Change parameter 0-22 back to option 1610 – “Power [kW]”<br />

Put pump into AUTO mode. The pump should maintain the no-flow pressure as per parameter 22-87<br />

Record VFD <strong>Sensorless</strong> pressure readout when pump is ramped down to no flow speed.<br />

Reopen discharge valve to 100% open. The pump should now ramp up to design flow and head.<br />

When pump is stabilized, record pump speed, <strong>Sensorless</strong> pressure, <strong>Sensorless</strong> flow on startup data sheet<br />

Reopen discharge valve to 100% open. The pump should now ramp up to pressure setpoint in the drive<br />

on parameter 20-21<br />

If the pump goes to full speed and does not hit the pressure setpoint, this is most likely because the<br />

system is oversized and has less resistance than designed for.<br />

Option #1: Work with general contractor and engineer to determine whether more flow and less head is<br />

acceptable. If this is, change parameter 20-21 to the new pressure setpoint, parameter 22-87 to a value<br />

that is 40% of the new setpoint and parameter 22-89 to the new flow based on the pressure setpoint<br />

according to the duty curve. RECORD THESE VALUES ON THE STARTUP DATA SHEET.<br />

Option #2: If available, try to balance the system using an <strong>Armstrong</strong> FlowTrex Valve on discharge of the<br />

pump to increase backpressure and put the pump back on the design curve<br />

Notes Regarding Dual Arm <strong>Pump</strong>s:<br />

If parameter # 5-31 on <strong>Pump</strong> #1 / Master is set to “Running / No Warning” and if both pumps are set to AUTO<br />

mode, putting one of the pumps in OFF mode will start the other pump up.<br />

If pump overlap is required when switching duty / standby pumps, go to SETUP #2 on both pumps and increase<br />

the ramp down time on parameter # 3-42. Default time is 60 seconds.<br />

<strong>Check</strong>ing for resonance:<br />

If you notice piping or accessories attached to the pump are vibrating at a specific frequency / speed of the pump, you<br />

can adjust the <strong>IVS</strong> drive to bypass this frequency by giving it a range of frequencies it needs to skip.<br />

Set the beginning of the range in parameter # 4-61 “Bypass Speed From” and the end of the range on parameter # 4-<br />

62 “Bypass Speed To”. RECORD THESE VALUES IN THE STARTUP DATA SHEET.<br />

Keep in mind that the drive does not “jump” past this range. It will just not stay within it (it will still move through it).<br />

Page 2 of 3


PID Loop Autotuning:<br />

Done<br />

Place the pump in OFF mode<br />

Verify all system valves are at 100% or a 100% load situation is recreated and nothing will change during<br />

this tuning.<br />

Change parameter 0-22 (default value is option 1610 – “Power [kW]”) to option 1654 “Feedback 1 [Unit]”<br />

to display <strong>Sensorless</strong> pressure readout on the top right corner of screen<br />

Record parameter 20-93 “PID Proportional Gain” in the Startup Data Sheet<br />

Record parameter 20-94 “PID Integral Time” in the Startup Data Sheet<br />

Verify parameter 20-95 “PID Differentiation Time” is set to “OFF”<br />

Go to parameter 20-79 “PID Auto Tuning” and change this to “ENABLE”. Follow the on-screen<br />

instructions.<br />

When the screen asks you to select a run speed where to auto tune the VFD to, use the<br />

UP/DOWN/LEFT/RIGHT keys to enter a speed where the <strong>Sensorless</strong> pressure readout (on the top right<br />

corner of the screen) is the same as the desired setpoint in parameter 20-21<br />

Press OK to begin the auto tune procedure (this can take 2-5 minutes)<br />

Press OK when auto tune is complete to accept new PID loop tuning<br />

Record NEW value in parameter 20-93 “PID Proportional Gain” in the Startup Data Sheet<br />

Record NEW value in parameter 20-94 “PID Integral Time” in the Startup Data Sheet<br />

Verify parameter 20-95 “PID Differentiation Time” is set to “OFF”<br />

Change parameter 0-22 back to option 1610 – “Power [kW]”<br />

Place the pump back into AUTO mode and then open / close discharge isolation valves to test new pump<br />

ramp up / down speeds. If acceptable, move on.<br />

BAS / BMS Communications: Yes – Type: ________________ No<br />

If the BAS/BMS is communicating to the drive via Modbus, Metasys or FLN:<br />

<strong>Check</strong> parameter # 8-30 and change it accordingly to the BAS / BMS comm. Type<br />

<strong>Check</strong> parameter # 8-31, 8-32 and 8-33 and change the address, baud rate and parity/stop bits in accordance to<br />

the BAS/BMS contractor instructions<br />

If the BAS/BMS is communicating to the drive via Lonworks or BACNet RTU, the drive is factory up already and good<br />

to go.<br />

SIGNOFF:<br />

By signing off on this startup checklist, both parties hereby accept that the equipment listed in this checklist has been<br />

properly verified to be fully operational and functioning as per the sales order for the equipment listed.<br />

Startup Technician Name (Please print):<br />

Startup Technician Signature:<br />

Customer Name (Please print):<br />

Customer Signature:<br />

Date (mm/dd/yyyy):<br />

/ / / /<br />

Date (mm/dd/yyyy):<br />

Submit complete documents to <strong>Armstrong</strong> via fax at 416-759-9101 or via email at warrantyclaims@armlink.com.<br />

S. A. <strong>Armstrong</strong> Limited <strong>Armstrong</strong> <strong>Pump</strong>s Inc. <strong>Armstrong</strong> Integrated Limited<br />

23 Bertrand Avenue 93 East Avenue Wenlock Way<br />

Toronto, Ontario North Tonawanda, New York Manchester<br />

Canada, M1L 2P3 U.S.A. 14120-6594 United Kingdom, M12 5JL<br />

T: 416-755-2291 T: 716-693-8813 T: +44 (0) 8444 145 145<br />

F: 416-759-9101 F: 716-693-8970 F: +44 (0) 8444 145 146 © S.A. <strong>Armstrong</strong> Limited 2010<br />

Page 3 of 3<br />

For <strong>Armstrong</strong> locations worldwide, please visit www.armstrongintegrated.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!