<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

Tenant Design Criteria<br />

Updated: September, 2008


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ADDENDUM LOG<br />

ADDENDUM DATE:<br />

April 9th, 2008<br />

September, 2008<br />

Entire Criteria<br />

Technical Criteria<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

Addendum Log<br />

2


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

TABLE OF CONTENTS<br />

I. GENERAL MALL INFORMATION<br />

Mission Statement .............................................................................. 4<br />

Vicinty Map, Site Plan, Mall Plan ....................................................... 5<br />

Site Plan, Center Plan (Design Key Plan)............................................ 6-7<br />

Contact Directory, Mall Contractors ................................................... 8-9<br />

Base Building & Code Information....................................................... 10<br />

Glossary ............................................................................................. 11-12<br />

Condition of Premises ....................................................................... 13<br />

<br />

II. ARCHITECTURAL DESIGN CRITERIA<br />

General Storefront Requirements ..................................................... 15<br />

Neutral Pier Details .......................................................................... 16<br />

Storefront Design .............................................................................. 17-20<br />

Windows & Glazing ........................................................... 17<br />

Overhangs/Umbrellas/Awnings ......................................... 18<br />

Materials & Details .............................................................. 19-20<br />

Interiors ............................................................................................. 21-24<br />

DCA, Ceilings .................................................................... 21<br />

Lighting, Walls/Partitions ................................................... 22<br />

Floor and Wall Base, Toilet Room ..................................... 23<br />

Exiting, Rear Doors ............................................................ 24<br />

III. IN-LINE FOOD TENANT CRITERIA<br />

General Requirements ...................................................................... 25<br />

Customer Service Area ..................................................................... 25-27<br />

Layout, Facade Materials .................................................. 25<br />

Neutral Piers & Demising Walls, Seating, Signage,<br />

Lighting, Flooring, Ceiling, Counters .................................. 26<br />

Rolling Grilles, Menu Board ............................................... 27<br />

Prep Area ......................................................................................... 27-29<br />

Lighting, Flooring ............................................................... 27<br />

Ceiling, Walls, Exit Door, Mechanical, Grease Exhaust,<br />

Fumes and Odors, Structural ............................................. 28<br />

Utilities ............................................................................... 28-29<br />

IV. SIGNAGE & GRAPHICS<br />

General Signage Requirements ......................................................... 30-31<br />

Primary Signage Design .................................................... 31<br />

Alternate Signage ............................................................................... 31-32<br />

Storefront Window Signs, Threshold Signs ........................ 31<br />

Awning Signage, Blade Signs ............................................ 32<br />

Prohibited Materials, Sign Area Calculation........................................ 32<br />

Plan Submittal Guidelines .................................................................. 33<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

Drawing Preparation, Review Process, Incomplete<br />

Submittals, Drawing Requirements .................................... 33<br />

Sign Construction/Installation, Insurance Requirements,<br />

Exterior Sign Criteria, Construction Requirements for<br />

Exterior Signage ................................................................. 34<br />

Height of Exterior Signs/Logos ........................................... 35<br />

V. TECHNICAL CRITERIA<br />

Mechanical/Plumbing Summary ......................................................... 36<br />

Restaurant Tenants:Landlord Provided, Tenant<br />

Provided ............................................................................. 36<br />

In-Line Tenants: Tenants:Landlord Provided, Tenant<br />

Provided ............................................................................. 36<br />

Electrical/Plumbing Criteria ................................................................ 37<br />

In-Line and Restaurant Tenants: Landlord Provided,<br />

Tenant Provided ................................................................. 37<br />

HVAC Systems ................................................................................... 38-40<br />

Codes and Standards, General Requirements ................. 38<br />

Restaurant Exhaust Requirements, Odor Control Exhaust<br />

Requirements .................................................................... 39<br />

<br />

Electrical Criteria ................................................................................ 41-44<br />

General Design/Construction Coordination, Power<br />

Source, Main Switch & Conduits ........................................ 41<br />

Maximum Loads, Telephone Service, Lightning, Wire and<br />

Disconnect Sizing ............................................................... 42<br />

Tenat Construction Requirements ...................................... 43-44<br />

Plumbing Criteria ................................................................................ 45-47<br />

Codes and Standards, General Requirements .................. 45<br />

<br />

Fire Protection .................................................................... 47<br />

Awning Signage, Blade Signs ............................................ 32<br />

Fire Alarm ........................................................................................... 48<br />

Structural Criteria......................................................................... 49<br />

PLEASE VISIT WWW.MACERICH.COM TO VIEW<br />

PLAN SUBMITTAL & APPROVAL PROCEDURES and<br />

CONTRACTOR’S RULE & REGULATIONS<br />

Table of Contents<br />

3


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

MISSION STATEMENT<br />

<br />

Overall setting (Mall common areas); and 2) Individual components<br />

(Tenant storefronts). Both affect the perception of <strong>Scottsdale</strong><br />

<strong>Fashion</strong> <strong>Square</strong> as a prime retail establishment.<br />

Generally, storefront design styles are the provenance of the<br />

-<br />

<br />

<br />

criteria.<br />

<br />

tions,<br />

the use of three-dimensional form, and proper material use.<br />

These criteria are intended to provide a basis for all storefronts to<br />

present merchandise in an exciting, promotional fashion.<br />

<br />

<br />

address storefront and interior design, materials, colors, signage,<br />

<br />

to various locations in the Mall, must be met.<br />

<br />

<br />

in this manual. The design criteria calls for a three-dimensional<br />

storefront that carries into the store sales area and is expressive<br />

of the merchandise sold.<br />

National and regional “standard” storefront concepts are<br />

-<br />

<br />

<br />

<strong>Square</strong> criteria. The same is true for proposed designs that are<br />

overly similar to a neighboring tenant’s storefront design. We<br />

<br />

<br />

design.<br />

<br />

to emphasize creative and dynamic forms and designs. Storefront<br />

elements shall de-emphasize linear or boxy forms by the<br />

use of recesses, angles, curves, gables and material changes in<br />

<br />

<br />

<br />

<br />

<br />

and governing. All tenants should refer to the Technical Criteria<br />

for electrical, mechanical, plumbing and life safety information.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

4


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

7014 E. Camelback Road<br />

<strong>Scottsdale</strong>, AZ 85251<br />

(480) 945-5495 Phone<br />

(480) 429-1455 Fax<br />

Mall Hours<br />

Monday - Saturday: 10:00 AM to 9:00 PM<br />

Sunday: 11:00 PM to 6:00 PM<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

5


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SITE PLAN<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

6


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

CENTER PLAN (DESIGN KEY PLAN)<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

7


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

CONTACT DIRECTORY<br />

Landlord/Owner:<br />

Westcor<br />

“<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong> Partnership”<br />

11411 N Tatum Blvd.<br />

Phoenix, AZ 85028<br />

Property Contact:<br />

Steve Helm, Sr. Property Manager<br />

Patrick Collins, Operations Manager<br />

<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

7014 E. Camelback Road, Suite 590<br />

<strong>Scottsdale</strong>, AZ<br />

(480) 945-5495 Phone<br />

(480) 423-1455 Fax<br />

Tenant Coordinator:<br />

Justin Lund<br />

11411 N. Tatum Blvd<br />

Phoenix, AZ 85028<br />

(602) 953-6776 Phone<br />

(602) 953-6449 Fax<br />

<br />

Building and Safety:<br />

City of <strong>Scottsdale</strong> Planning and Community<br />

Development<br />

7447 Indian School Road<br />

Suite 105<br />

<strong>Scottsdale</strong>, AZ 85251<br />

(480) 312-2500 Phone<br />

(480) 312-7088 Fax<br />

Fire Department:<br />

City of <strong>Scottsdale</strong> Fire Department<br />

8401 East Indian School Road<br />

<strong>Scottsdale</strong>, AZ 85251<br />

(480)312-1855 Phone (to call for inspection)<br />

GAS<br />

<br />

<br />

Phoenix, AZ 85029<br />

(602) 861-1999 Phone<br />

Leasing Agent:<br />

Shannon McMahon<br />

11411 N. Tatum Blvd<br />

Phoenix, AZ 85028<br />

(602) 953-6200 Phone<br />

(602) 953-6298 Fax<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

8


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

MALL REQUIRED CONTRACTORS<br />

FIRE SPRINKLERS<br />

Alliance Fire Protection<br />

2114 E. Cedar St.<br />

Tempe, AZ 85281<br />

(480) 966-9178 Phone<br />

FIRE ALARM<br />

Simplex/Grinnell<br />

Dave Collett<br />

4602 S. 36th St.<br />

Phoenix, AZ 85040<br />

(602) 243-6700 Phone<br />

ELECTRICIAN (FOR FINAL CONNECTIONS)<br />

Rehco Electric<br />

Rick or vern<br />

(480) 922-6257 Phone<br />

ROOFING<br />

TBD<br />

TELEPHONE<br />

<br />

1-800-603-6000<br />

(D-Mark located in <strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

<br />

<br />

access to the phone room. They are located<br />

on the upper level outside of Macy’s (480)<br />

949-0606<br />

<br />

make connection from D-Mark to Tenant’s<br />

<br />

Brothers 3 Communication<br />

Buddy Earle<br />

<br />

(602) 246-4334 - Fax<br />

(602) 432-9324 - Cell<br />

ENGINEERS OF RECORD<br />

STRUCTURAL ENGINEER<br />

<br />

4647 North 32 Street<br />

Suite 280<br />

Phoenix, AZ 85018<br />

(602) 265-4331 Phone<br />

(602) 970-3033 Fax<br />

ELECTRICAL ENGINEER<br />

Sparling<br />

Kimberely Krull<br />

Scott Ducich<br />

111 SW 5th Ave, Suite 1575<br />

Portland, OR 97204<br />

(503) 273-0600 Phone<br />

MECHANICAL/PLUMBING/HVAC<br />

<br />

Eugene Hall<br />

4140 Lemmon Ave<br />

Suite 275, LB 110<br />

Dallas, TX 75219-3738<br />

(214) 520-7799 Phone<br />

ARCHITECT<br />

Callison, LLC<br />

Charles H. Krimmert<br />

June Whipple<br />

1420 Fifth Ave Suite 2400<br />

Seattle, WA 98101-2343<br />

(206) 623-4646 Phone<br />

NOTE:<br />

Landlord reserves the right to require The<br />

tenant to use certain contractors for spe-<br />

<br />

<br />

-<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

9


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

BUILDING TYPE<br />

Multi-level regional shopping center.<br />

<br />

Covered center building type IIA construction,<br />

<br />

Occupancy Type: Mercantile (M)<br />

Construction Type:<br />

IIA, (Fully Sprinklered)<br />

Zoning: D/RCO-2 PBD/DO<br />

APN: 173-37-002-A<br />

BUILDING CODE INFORMATION<br />

<br />

applicable codes. It is the sole<br />

responsibility of the tenant’s architect,<br />

<br />

all applicable federal, state, local codes and<br />

ordinances for their occupancy type.<br />

Applicable Codes:<br />

Currently adopted edition of the Uniform<br />

Building Code as amended and adopted by<br />

<br />

-<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

-<br />

<br />

<br />

<br />

GOVERNING CODE<br />

<br />

<br />

and any other state and local codes having<br />

<br />

Building: IBC 2006 (City of <strong>Scottsdale</strong> Code,<br />

Chapter 31)<br />

Mechanical: IMC 2006 (City of <strong>Scottsdale</strong><br />

Code, Chapter 31)<br />

Plumbing:UPC 1994 (City of <strong>Scottsdale</strong> Code,<br />

Chapter 31)<br />

Electrical: NEC 2005 (City of <strong>Scottsdale</strong> Code,<br />

Chapter 31)<br />

Handicap: ADAAG<br />

Fire: IFC 2006 (City of <strong>Scottsdale</strong> Code,<br />

Chapter 36)<br />

Energy: IECC 2006 International Energy Conservation<br />

Code (2006 IBC)<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

10


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

GLOSSARY<br />

COMMON AREA<br />

<br />

DEMISING WALLS<br />

<br />

<br />

DESIGN CONTROL AREA “DCA” / DISPLAY AREA<br />

<br />

<br />

<br />

<br />

HAZARDOUS MATERIALS<br />

<br />

materials, paints, cleaning supplies, etc.<br />

LEASE LINE<br />

<br />

<br />

A.<br />

B.<br />

C.<br />

D.<br />

E.<br />

F.<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

LEASE OUTLINE DIAGRAM “LOD”<br />

<br />

-<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

11


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

GLOSSARY (Cont’d.)<br />

NEUTRAL PIERS / NEUTRAL STRIP<br />

<br />

POINT OF CLOSURE “POC”<br />

A real or imaginary demarcation such as the center line of the Glass or any Entry Door(s) in their fully closed position.<br />

RECESSED STOREFRONT<br />

<br />

the design control area.<br />

SERVICE CORRIDORS<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

12


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

CONDITION OF PREMISES<br />

FIELD CONDITIONS<br />

Upon the Delivery Date, Tenant shall accept delivery of the Premises in an<br />

“As Is” condition and “With All Faults” and Landlord shall have no obligation<br />

<br />

<br />

<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

Tenant or its authorized representative has inspected the Premises and<br />

has made all inquiries, tests and studies that it deems necessary in<br />

<br />

<br />

<br />

respect to, the condition of the Premises and Tenant’s leasing thereof,<br />

and<br />

ties,<br />

express, implied or statutory by Landlord, or Landlord’s agents,<br />

<br />

<br />

The Work to be completed by Landlord, “Landlord’s Work” under the<br />

Tenant Lease shall be limited to that described in the foregoing sections.<br />

lord,<br />

shall be provided by the Tenant at Tenant’s expense and is herein<br />

referred to as “Tenant’s Work”.<br />

1.<br />

2.<br />

3.<br />

4.<br />

-<br />

<br />

<br />

<br />

<br />

ing<br />

the premises, the Tenant shall verify the accuracy of said installation and<br />

shall immediately advise Landlord of any discrepancies. Failure to so notify<br />

Landlord shall be deemed as acceptance by Tenant of said installation and<br />

layout.<br />

Landlord shall have the right to locate, both vertically and horizontally, utility<br />

<br />

<br />

<br />

equipment required by other tenants. Landlord shall also have the right to<br />

locate mechanical and other equipment on the roof over the premises.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

13


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

TENANT’S WORK DEFINED<br />

-<br />

<br />

<br />

A.<br />

B.<br />

C.<br />

D.<br />

Engaging the services of a licensed architect (“Tenant’s Architect”) to prepare the Preliminary Documents, Construction Documents and the As-Built Documents.<br />

Preparation of originals and copies of the Preliminary Documents, Construction Documents and As-Built Documents.<br />

<br />

<br />

<br />

are located.<br />

LANDLORD’S WORK DEFINED<br />

General<br />

<br />

<br />

Center<br />

Landlord or its predecessor-in-interest has constructed the Center, and the Building and other improvements upon the Center (exclusive of improvements constructed<br />

by or on behalf of each present and prior Occupant of the Center). Tenant has inspected the Center, the Building, the utilities, the types, quantities and qual-<br />

<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

I. General Mall Information<br />

14


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

GENERAL STOREFRONT REQUIREMENTS<br />

<br />

<br />

displays and signage.<br />

<br />

<br />

Storefronts must be of the highest caliber: expressing state of the art and material<br />

quality, and meeting or exceeding the very best examples. To achieve this goal,<br />

<br />

design.<br />

Materials used in the construction of storefronts shall be high quality,<br />

durable, authentically portrayed and code compliant. The entire storefront<br />

<br />

construction methods.<br />

<br />

<br />

<br />

and installation of materials for storefront construction. Proposed materials<br />

and colors are to be submitted on a color material sample board to the Land-<br />

<br />

SUBMITTAL & REVIEW PROCEDURES for more detailed requirements.)<br />

<br />

creative, dynamic forms and designs.<br />

The following criteria apply:<br />

1. dent<br />

of the building fascia and bulkhead structure. Storefronts may be braced<br />

<br />

<br />

2. Three dimensional articulations in both store front plan and height are required<br />

<br />

3. ing.<br />

4. Storefronts visible from the upper level must take special care that the tops<br />

<br />

<br />

<br />

match.<br />

5. -<br />

<br />

6. Stores less than eight hundred (800) square feet shall be required to have<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

15


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

NEUTRAL PIER<br />

1<br />

Pg. 16<br />

Neutral Pier Detail<br />

Scale: N.T.S.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

16


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

STOREFRONT DESIGN CRITERIA<br />

Storefront Windows and Glazing<br />

<br />

-<br />

-<br />

<br />

pattern should be carefully considered.<br />

The transparent surfaces of the storefront serve an important design role to the<br />

storefront and the interior by creating an architectural display area. The use of<br />

<br />

applies:<br />

1. <br />

2. <br />

properly supported.<br />

3. All glass shall be tempered.<br />

4. Stained, leaded, etched, beveled, fritted, glass block and other types of innovative<br />

glazing are encouraged.<br />

5. <br />

<br />

chamfered. Glazing channels at corner conditions must be mitered.<br />

6. Tenants may be required to provide seismic clips to stabilize tall expanses of<br />

<br />

7. <br />

not permitted on storefronts or in the storefront entry zone.<br />

8. Tenants are not restricted to asymmetrical design, particular proportions, sizes,<br />

or types of glazing systems.<br />

9. Tenants are encouraged to “open-up” their store front by extending their glazing<br />

to the extents of their leaseline.<br />

10. <br />

forms. Glass shall be clear polished plate or tempered glass as required by<br />

code.<br />

11. <br />

12. Glazing should be predominantly clear to emphasize merchandise<br />

display.<br />

13. Decorative glazing such as colored, beveled, sandblasted or etched<br />

glass may be used to create accent pattern and interest.<br />

14. <br />

<br />

15. Large panes of glass should be engineered by code requirements.<br />

Sections of glass are to be installed so that corners and abutting sections<br />

have no sash material providing separation or support.<br />

16. Weather tight conditions must be maintained.<br />

17. <br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

17


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

AWNINGS AND OVERHANGS<br />

Awning Type<br />

<br />

among Tenants.<br />

<br />

<br />

<br />

Creative, imaginative, unusual shapes<br />

Semi spherical<br />

Multiple<br />

<br />

by Landlord’s Tenant Coordinator.<br />

Awning Signage<br />

<br />

-<br />

<br />

ted.<br />

<br />

<br />

<br />

Tenant’s expense.<br />

Overhangs<br />

Overhangs are permitted in storefronts provided that they are an integral part<br />

<br />

architectural elements such as brackets, coffers or exposed beam-ends.<br />

Umbrellas<br />

<br />

<br />

in scale (maximum six feet in diameter) and no more that nine feet high<br />

<br />

for the umbrella structure. No insignia, graphics or text is permitted on the<br />

<br />

approved by Landlord’s Tenant Coordinator.<br />

Awning Logos<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

form<br />

to all applicable codes.<br />

<br />

<br />

-<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

18


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

MATERIALS<br />

General Material Requirements<br />

<br />

<br />

<br />

<br />

The use of natural materials is encouraged. All<br />

materials used in storefronts must be durable<br />

and non corrosive.<br />

<br />

differing materials is necessary. A carefully<br />

ferent<br />

materials and surfaces on the storefront,<br />

<br />

<br />

<br />

storefront point of closure shall be durable such<br />

as glass, tile, metal, stone, terrazzo, plaster,<br />

<br />

<br />

<br />

<br />

-<br />

<br />

Metals<br />

<br />

<br />

<br />

High quality is expected for all metal applications.<br />

Metal such as shop-painted aluminum<br />

and steel, stainless steel, solid brass, bronze,<br />

<br />

<br />

designed and detailed.<br />

<br />

<br />

corners are to be mitered or continuous break<br />

shaped.<br />

Fabrication must be either heavy gauge mate-<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

<br />

<br />

<br />

<br />

Stone<br />

rial or thinner gauge material shop laminated<br />

to solid backing. In no case is oil canning<br />

<br />

<br />

occlusions, visible seams or other imperfec-<br />

<br />

Sealants on natural metals are required to<br />

prevent tarnishing and must be maintained by<br />

Tenant at Tenant’s expense.<br />

Textured or brushed stainless steel, galvanized,<br />

sandblasted and etched metals are<br />

encouraged in creative applications.<br />

Unique treatments such as patina, rusted,<br />

<br />

<br />

Polished metals should be solid, not plated and<br />

limited to accent trim.<br />

<br />

and anodized aluminum are not permitted<br />

Granite, marble, limestone, slate, adoquin and other<br />

natural stone materials may be used in storefront<br />

applications. Stone may be polished, unpolished,<br />

<br />

Careful, craftsman like attention to detail is required<br />

at all connections and transitions to other materials.<br />

<br />

<br />

<br />

edges. Exposed edges must be quirk mitered,<br />

-<br />

<br />

<br />

<br />

<br />

Wood<br />

<br />

reveals.<br />

<br />

<br />

Natural stone must be protected against staining<br />

and discoloration by means of sealers<br />

appropriate to the material.<br />

<br />

rative<br />

trim or molding, and for solid areas, such as<br />

decorative bulkheads. In some cases, it may be<br />

used for larger architectural elements, such as columns<br />

and entablatures. Wood paneling and plank<br />

construction are not acceptable unless presented in<br />

a highly imaginative concept and approved by the<br />

Landlord.<br />

<br />

<br />

<br />

<br />

<br />

All detailing and construction is to be executed<br />

in a high quality, craftsman like manner.<br />

Wood used in the construction of the storefront<br />

<br />

<br />

(Class III 76-200).<br />

<br />

<br />

<br />

clear, preservative sealant.<br />

<br />

<br />

approved by Landlord’s Tenant Coordinator.<br />

II. Architectural Design<br />

19


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

MATERIALS (Cont’d.)<br />

Tile<br />

Tile may be used in diverse applications. Its use is<br />

encouraged to introduce light, decorative texture or<br />

graphic quality to a storefront.<br />

<br />

<br />

<br />

<br />

Porcelain, ceramic or glass tiles in glazed or<br />

<br />

<br />

large areas are expected to have a sophisti-<br />

<br />

Small and intricate mosaic tile patterns may be<br />

utilized for detail and accent only.<br />

All tiles must be carefully detailed at outside<br />

<br />

<br />

Grout color should match the background color<br />

of the tile so as not to emphasize a grid pattern.<br />

Pre-cast Stone and Concrete<br />

Many pre-cast stone and concrete products are<br />

currently available that may be acceptable for<br />

storefront applications. The use of these materials<br />

is at the discretion of the Landlord.<br />

Plaster<br />

Plaster, cement plaster (stucco), and Venetian<br />

<br />

<br />

<br />

-<br />

<br />

stone or metal and not be the primary storefront<br />

material.<br />

Faux Finishes<br />

<br />

discretion.<br />

<br />

<br />

<br />

submitted to the Landlord. Photographs of<br />

previous examples are helpful, but may not be<br />

substituted for an actual sample.<br />

cial<br />

artisan specializing in that medium.<br />

Painted Surfaces<br />

Any paint applied to the materials in the storefront<br />

<br />

Landlord’s Design Consultant. All paint should be<br />

<br />

<br />

<br />

<br />

<br />

pared<br />

and sealed prior to the application of a<br />

high grade enamel.<br />

Painted metal shall have a factory applied<br />

ment.<br />

<br />

<br />

exterior storefront.<br />

Prohibited Materials<br />

<br />

instances, special consideration may be given for<br />

the use of a prohibited material if its application is<br />

highly original, creative and essential to the theme<br />

or design concept of the storefront. Exceptions<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Plastic laminates.<br />

Glossy or large expanses of acrylic or Plexiglas<br />

Pegboard<br />

Mirror<br />

Highly polished or plated metals - except as<br />

trim<br />

<br />

Simulated materials such as brick, stone or<br />

<br />

<br />

<br />

Anodized aluminum<br />

<br />

<br />

Sheet or modular vinyl<br />

Luminous ceilings, including “egg crate”<br />

<br />

Shingles, shakes, rustic siding<br />

Other materials deemed unacceptable by the<br />

Landlord.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

20


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

INTERIORS<br />

Tenants are encouraged to produce high quality,<br />

<br />

unique, imaginative, and stylized.<br />

tion<br />

of the storefront in design and materials. Walls<br />

are to have modulation of display systems and built<br />

in architectural components that reinforce the store<br />

<br />

levels must provide sound isolation in demising<br />

ing<br />

partitions. Security devices are to be entirely<br />

<br />

-<br />

<br />

<br />

meet accessibility guidelines enforced by national<br />

<br />

Disabilities Act. All materials acceptable or prohibited<br />

at the storefront are applicable to the store<br />

interior.<br />

Design Control Area (DCA)<br />

The DCA is the area at the front of the Tenant<br />

space that extends from the point of closure to<br />

all points six feet (6’ -0”)into the space. The DCA<br />

<br />

<br />

<br />

DCA can be considered an extension of the storefront<br />

presentation and should convey a store’s<br />

merchandise identity and generate activity. It<br />

should convey excitement and give the consumer a<br />

reason to stop at the store. Proportion and scale of<br />

-<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

<br />

space around them. Incorporating elements that<br />

<br />

control the scale of the DCA. Pedestals to display<br />

<br />

<br />

ent<br />

from traditional and typical display zones.<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

plan. The layout plan shall have cut sheets<br />

<br />

photographs of any existing storefronts a<br />

<br />

plan. A rendering is required if photographs<br />

are not available.<br />

Displays shall be deliberate and designated as<br />

integrated elements of the storefront.<br />

Security devices must be concealed; freestanding<br />

pedestals are not permitted.<br />

Large temporary signs for special sales or<br />

clearances shall not be hung in the DCA<br />

including any signs taped or suction cupped to<br />

storefront glazing.<br />

<br />

kind may be placed in or extend into any part<br />

of the DCA.<br />

Ceilings<br />

<br />

may incorporate an open grid or be painted. Ceilings<br />

in all malls, public areas and corridors are<br />

as required by the building code of the City of<br />

<strong>Scottsdale</strong> and as designed by Landlord’s architect.<br />

Landlord guaranteed a clear ceiling height of 13’<br />

6” in the Tenant locations. Tenant installed ceilings<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Hard surface ceiling required through the<br />

entire storefront DCA. This distance shall be<br />

<br />

innermost point of closure line.<br />

Custom ceiling treatments are required. Multi<br />

<br />

decorative patterned ceiling panels and other<br />

“high-tech” materials are encouraged. The<br />

use of ceilings on a single plane is not permit-<br />

<br />

<br />

<br />

Fire sprinkler heads are to be fully recessed in<br />

hard or acoustical ceilings.<br />

Standard 24” x 48” acoustical panels are not<br />

<br />

Ceiling concepts implementing exposed structure,<br />

electrical and mechanical systems must<br />

<br />

technical and design requirements.<br />

<br />

<br />

<br />

II. Architectural Design<br />

21


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

INTERIORS (Cont’d.)<br />

<br />

<br />

<br />

<br />

<br />

All ceilings, related framing, blocking and<br />

accessories shall be noncombustible. No com-<br />

<br />

ceiling surfaces.<br />

Lighting<br />

Lighting can greatly contribute to the design of a<br />

Tenant’s store, emphasizing architectural forms,<br />

highlighting signage, and adding color and visual<br />

<br />

creative use of dramatic lighting is encouraged at<br />

<br />

<br />

<br />

<br />

<br />

The DCA of the Tenant space must employ<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

in DCA.<br />

Fixtures must be positioned so that bright glare<br />

is not directed onto the public areas.<br />

<br />

<br />

<br />

recessed.<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

may be used only in concealed areas and/or<br />

<br />

a maximum size of 2’ x 2’ and have silver<br />

<br />

<br />

label.<br />

Concealed light coves to highlight architec-<br />

<br />

encouraged.<br />

Wall sconces may be used to cast light onto<br />

storefront forms, provided that bare bulbs are<br />

<br />

-<br />

<br />

to be submitted if this light form is used.<br />

<br />

front<br />

design concept. Fixture cut sheets must<br />

<br />

<br />

by Landlord. Tenant is responsible for main-<br />

<br />

Premises.<br />

<br />

conservation and building codes.<br />

No strobe, spinner or chase type lighting shall<br />

be used.<br />

<br />

adequately lit and ventilated. Direct visual<br />

cent<br />

tubes is prohibited.<br />

Walls/Partitions<br />

<br />

<br />

<br />

<br />

<br />

<br />

Tenants and/or Tenant and exit/service corri-<br />

<br />

5/8” interior mechanically fastened steel studs<br />

<br />

<br />

tenancies, (provided by Landlord), and 5/8”,<br />

<br />

bottom of roof deck, or deck above (or as<br />

required by governing code) on each side (provided<br />

by Tenants). At Landlord’s option, demis-<br />

<br />

<br />

not designed to accommodate cantilevered<br />

or eccentric loads. If Tenant plans to use a<br />

<br />

<br />

tional<br />

steel studs or independent supports for<br />

the shelf standards.<br />

<br />

<br />

<br />

<br />

No plumbing, electrical, or telephone lines or<br />

<br />

height of eight and a half feet (8 1/2’) on the<br />

<br />

the back door.<br />

-<br />

<br />

<br />

insulated to achieve a minimum STC rating<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

22


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

INTERIORS (Cont’d.)<br />

<br />

<br />

<br />

<br />

<br />

<br />

noise, (including but not limited to music stores,<br />

arcades, etc.) at the Landlord’s discretion. The<br />

<br />

<br />

<br />

<br />

required.<br />

<br />

shops and all food preparation type Tenants:<br />

a. <br />

<br />

resistant 5/8” type “x” gypsum board.<br />

b. <br />

have sheet metal installed on studs,<br />

<br />

<br />

<br />

layers of 5/8” type “X” gypsum board to Tenants<br />

side of studs.<br />

Stockroom Partitions. When Tenant chooses<br />

room,<br />

Tenant shall extend the partition separating<br />

the stockroom from other areas of the<br />

store, to the underside of the structure above<br />

in order to isolate the stockroom from the sales<br />

area attic space.<br />

Wall Finishes. <br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Metal or plastic laminate inserts are required<br />

<br />

<br />

<br />

<br />

mounted systems.<br />

Floor and Wall Base<br />

<br />

-<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

the entire DCA, including any permitted pop out<br />

areas. Carpet, vinyl or rubber materials of any<br />

<br />

<br />

<br />

resistant surface.<br />

Ceramic, quarry and stone tile installations<br />

face.<br />

<br />

<br />

<br />

<br />

<br />

<br />

Carpet must be commercial grade and must<br />

<br />

<br />

<br />

areas. Note: Carpet may not be used at the<br />

<br />

Sheet or modular vinyl may be used in support<br />

or stock rooms not visible from the sales area.<br />

<br />

<br />

<br />

<br />

Tenants shall install vinyl composition tile in<br />

<br />

<br />

ishes<br />

must be submitted for approval and<br />

included in Tenant’s preliminary submissions.<br />

Toilet Room Requirements<br />

<br />

<br />

<br />

<br />

<br />

Toilet facilities shall be designed in compliance<br />

<br />

Codes.<br />

<br />

Each restroom must have an exhaust system.<br />

<br />

<br />

<br />

<br />

<br />

-<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

23


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

INTERIORS (Cont’d.)<br />

<br />

<br />

type “x” gypsum board applied to the interior side of<br />

<br />

<br />

<br />

<br />

urinal.<br />

The ceiling shall be a minimum of 8’-0” above the<br />

<br />

<br />

<br />

be connected to the Landlord’s exhaust system, or<br />

as pursuant to the Center equirements.<br />

Exiting<br />

<br />

premises if required by code and/or Landlord’s Tenant<br />

Coordinator. All exits must be engineered in compliance<br />

<br />

Rear Door<br />

Tenants must install a recessed door and vestibule in<br />

-<br />

<br />

<br />

<br />

<br />

<br />

<br />

condition into their vestibule area and maintain Landlord<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

II. Architectural Design<br />

24


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

GENERAL OVERVIEW<br />

-<br />

<br />

design criteria must modify their design from that<br />

normally used.<br />

<br />

addressed to the Landlord’s Tenant Coordinator.<br />

ing<br />

space conditions prior to submittal of plans.<br />

The “Food Tenant” design criteria is a sub section of<br />

ria’.<br />

The details and requirements described herein<br />

cally,<br />

although not exclusively, for Food Tenants.<br />

Other documents developed for the Mall and provided<br />

to the tenant under separate cover must also<br />

<br />

but are not limited to:<br />

The Lease and its exhibits<br />

Tenant Design and Construction Criteria<br />

Sign Design & Construction Criteria<br />

Construction Rules and Regulations for Tenant’s<br />

Contractor<br />

Exhaust information for Food Tenants<br />

<br />

Customer Service Area<br />

Prep Area<br />

Although the Landlord establishes criteria for the<br />

<br />

design, procurement,installation cost and operation<br />

of this area are the responsibility of the Tenant.<br />

A.<br />

CUSTOMER SERVICE AREA<br />

This area includes:<br />

<br />

Layout<br />

All areas visible to the public.<br />

Due to the high visibility of the Customer Service<br />

Area, particular attention is given to the design<br />

<br />

display cookery, food prep and cooking areas<br />

visible from the mall common area must meet the<br />

Customer Service Area criteria. Support rooms and<br />

<br />

part of the store may extend past the front lease<br />

line.<br />

<br />

Customer Service Area and Prep Area. Access to<br />

the Prep Area shall be via a self-closing door or<br />

<br />

Mall structural columns, excluding those treated as<br />

<br />

Zone or along the store frontage, must be integrated<br />

into the store design.<br />

All Tenant construction shall be self-supporting from<br />

<br />

fascia and bulkhead structure. Tenant Construction<br />

may be braced horizontally/laterally to the over-<br />

<br />

the tenant space as depicted on Tenant plans and<br />

approved by the Landlord.<br />

Facade Materials<br />

<br />

approval.<br />

<br />

Natural, polished or honed stone and/or procelain<br />

tile.<br />

All tile colors must be integral throughout the<br />

materials. (Glazed tiles are prohibited)<br />

<br />

<br />

<br />

<br />

materials:<br />

<br />

boards.<br />

Glazed tiles.<br />

Plastic spandrel panels or applied plastic laminated<br />

materials.<br />

Faux or plastic formed brick, block or stone.<br />

Clear anodized aluminum.<br />

12”x12” tiles.<br />

Other materials as deemed unacceptable by<br />

Landlord.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

III. In-Line Food<br />

25


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

CUSTOMER SERVICE AREA (Cont’d.)<br />

Neutral Piers & Demising Walls<br />

The Customer Service Area shall address the full<br />

tral<br />

Knee Walls on each side of the leased space<br />

<br />

<br />

Seating<br />

Tenants shall provide, place or install any seating,<br />

display carts, etc. inside or outside of the lease<br />

premises.<br />

Signage<br />

ments.<br />

Also refer to the “Sign Design & Construction<br />

Criteria”<br />

Lighting<br />

Recommended lighting approaches include but are<br />

not limited to:<br />

<br />

<br />

components.<br />

<br />

<br />

<br />

Indirect ceiling cove lighting system using<br />

<br />

lamps.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

Unacceptable lighting approaches include but are<br />

not limited to:<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

To create a consistent theme of lighting and appetizing<br />

color, lamp or “bulb” requirements must be<br />

<br />

<br />

<br />

<br />

Flooring<br />

The entire Lease Premises shall be completely and<br />

<br />

<br />

equal membrane type sealer approved by Landlord,<br />

rial.<br />

The membrane must be turned up all perimeter<br />

<br />

<br />

mall common areas.<br />

proof<br />

membrane throughout the entire premises.<br />

<br />

<br />

<br />

Vinyl<br />

Glazed ceramic tile<br />

Other non-integral colored materials, such as<br />

veneers, laminates, etc.<br />

Carpet<br />

Ceiling<br />

<br />

depicted on the Tenant’s plans, approved by the<br />

Landlord and be provided at the Tenant’s expense.<br />

Counters<br />

The form and materials used for counters<br />

shall be designed to be inviting to the public to<br />

help lure them to the space. Possible designs<br />

include counters that angle or arc slightly back<br />

into the space rather than running parallel to<br />

the lease line.<br />

<br />

is required. The face of the counter must be<br />

set back 6” from the lease line, or as needed<br />

so that the required cove lighting does not<br />

protrude past the lease line.<br />

The face of the front counter’s recessed toe<br />

kick material must be minimum 9” back from<br />

the front leaseline or as needed so that the<br />

required toe kick is recessed 3” behind the face<br />

of the counter.<br />

Counter tops must be “Corian” or similar solid<br />

surface materials, metal or stone. Tenant coun-<br />

III. In-Line Food<br />

26


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

CUSTOMER SERVICE AREA (Cont’d.)<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

ter and counter tops are to be custom designed<br />

and fabricated. Plastic laminate is prohibited.<br />

Maximum counter height is 3’6”. Counter<br />

<br />

accessibility guidelines enforced by national or<br />

abilities<br />

Act.<br />

Cash registers must be recessed so that they<br />

extend no more than 9 inches above the counter<br />

top.<br />

Condiment and utensil displays or dispensers<br />

must be fully recessed into the counter<br />

Fully-recessed counter-top trash receptacles<br />

<br />

near the condiment and utensil displays<br />

Tray rails, if used shall be integrated into the<br />

<br />

line, and incorporate the required cove lighting.<br />

Drink dispensers and other utilitarian kitchen<br />

<br />

from the entrance to the store.<br />

Sneeze guards shall be used above the front<br />

counters as required.<br />

<br />

<br />

be tempered or a safety type. Plexiglass is not<br />

permitted.<br />

<br />

<br />

Employee access through the counter front is not<br />

permitted. Back counters visible to the public must<br />

<br />

Rolling Grilles<br />

<br />

<br />

Menu Board<br />

B.<br />

All menu boards must be submitted to the<br />

<br />

of tenant construction.<br />

Menu boards shall be of an artisan type quality<br />

<br />

materials and combinations of material. Stan-<br />

<br />

Frames, holders, text, photo displays, lighting<br />

and materials MUST be creatively designed.<br />

Internally illuminated menu boards are not<br />

permitted<br />

PREP AREA<br />

This area includes:<br />

Kitchen and prep areas<br />

Storage<br />

<br />

Any areas that are not visible to the public<br />

Lighting<br />

Lighting may include, but is not limited to:<br />

<br />

<br />

<br />

preparation.<br />

Flooring<br />

The entire Lease Premises shall be completely and<br />

<br />

<br />

equal membrane type sealer approved by Landlord,<br />

rial.<br />

The membrane must be turned up all perimeter<br />

<br />

<br />

mall common areas.<br />

<br />

<br />

<br />

Quarry tile<br />

Porcelain ceramic tile<br />

<br />

Vinyl<br />

Glazed ceramic tile<br />

Carpet<br />

Any other material deemed unsuitable by the<br />

Landlord<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

III. In-Line Food<br />

27


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

PREP AREA (Cont’d.)<br />

Ceiling<br />

<br />

be permitted in storage areas so long as they are<br />

not visible to the customers.<br />

Walls<br />

<br />

<br />

codes.<br />

Exit Door<br />

<br />

recess dimensions, etc. shall be per Landlord criteria<br />

and conformant to local codes and ordinances.<br />

ALL ROOF WORK must be by the mall’s required<br />

<br />

The tenant is required to REMOVE ALL ROOF-<br />

MOUNTED EQUIPMENT AND ROOF PENETRA-<br />

<br />

build-out of the space. These shall be removed<br />

<br />

<br />

<br />

Do NOT attach, hang, suspend, laterally brace, or<br />

struction<br />

must be self supporting or may connect to<br />

unistrut attached to the mall structure but NOT TO<br />

THE ROOF DECK.<br />

Mechanical<br />

<br />

mechanical systems as required for their operation.<br />

Grease Exhaust<br />

A grease guard must be provided on all exhaust<br />

<br />

<br />

required for all kitchen exhaust or grease laden air<br />

removal.<br />

Fumes And Odors<br />

-<br />

<br />

must furnish and install in the Leased Premises for<br />

the elimination of fumes and odors due to Tenant<br />

operations:<br />

1.<br />

2.<br />

3.<br />

4.<br />

A separate exhaust system must be provided<br />

-<br />

<br />

<br />

<br />

all hours that Tenant is operating its business in<br />

the Leased Premises.<br />

<br />

additional make-up supply air to offset the<br />

quantity of air exhausted.<br />

<br />

contractor test the completed system and verify<br />

<br />

5.<br />

A copy of the air balancing report must be sub-<br />

<br />

and approval prior to opening for business.<br />

The combined HVAC and exhaust system per<br />

ation<br />

during all hours that Tenant is operating<br />

its business in the Leased Premises.<br />

Structural<br />

The structure or substructure that supports any<br />

<br />

<br />

or substructure, shall be designed, engineered and<br />

installed at Tenant’s sole cost and expense. Tenant<br />

shall provide structural engineering calculations and<br />

-<br />

<br />

<br />

installation of any such items or equipment.<br />

All equipment is to be installed over structural mem-<br />

<br />

in areas designated by Landlord.<br />

<br />

completion shall include the structural engineer’s<br />

embossed seal from the state.<br />

Utilities<br />

Electrical<br />

<br />

Tenant premises from the mall electrical room.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

III. In-Line Food<br />

28


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

PREP AREA (Cont’d.)<br />

Natural Gas<br />

Natural Gas service is available for Restaurant Ten-<br />

<br />

gas service from the gas company.<br />

Potable Water<br />

<br />

Landlord from the Landlord’s meter to each Tenant<br />

<br />

is accessible to mall management.<br />

Sanitary Waste<br />

<br />

each Tenant space by Landlord. Tenant shall route<br />

<br />

If any questions arise from the Tenant’s interpretation<br />

of the design and criteria information, the<br />

-<br />

<br />

GENERAL FLOOR PLAN<br />

GENERAL CEILING PLAN<br />

TENANT FLOOR PLAN<br />

TENANT CEILING PLAN<br />

TENANT ELEVATION FRONT COUNTER<br />

<br />

BLADE)<br />

TENANT ELEVATION REAR WALL<br />

SOUTH TENANT STORE SECTION OVERALL<br />

TENANT SECTION FRONT COUNTER<br />

Grease Waste<br />

<br />

<br />

common grease interceptor.<br />

Fire Protection / Sprinkler System<br />

Tenants must use the mall’s required sprinkler<br />

contractor.<br />

Submittal & Approval Requirements<br />

-<br />

PLETE submittal has been received, including any<br />

additional information necessary or helpful to make<br />

an evaluation of the design.<br />

Make all submittals to the Landlord’s Tenant Coordinator.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

III. In-Line Food<br />

29


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS<br />

Tenant signs are vital to the successful functioning<br />

of the Shopping Center. Uncontrolled signs<br />

<br />

communicate effectively. The ultimate goal is to<br />

produce a colorful collage of signs that tastefully<br />

inform, delight and stimulate the Shopper.<br />

<br />

design theme, enhancing the storefront and evoking<br />

a positive retail image. Due to the variety of<br />

-<br />

<br />

considered in relationship to its particular location.<br />

What may be appropriate in one location may<br />

<br />

<br />

<br />

Shopping Center.<br />

The Landlord reserves the right to disapprove any<br />

<br />

and the aesthetics of the Shopping Center. Excep-<br />

<br />

must be approved in advance by the Landlord. As<br />

<br />

Mall depends on the positive contribution of all<br />

participants.<br />

This criterion is intended to assist you, the Tenant,<br />

during the design and construction phases of your<br />

sign. It is provided by the Landlord in the interest<br />

of maintaining a high level of design excellence<br />

throughout the Center.<br />

<br />

leasing documents. It is the responsibility of the<br />

<br />

architect, contractor and various consultants.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

Landlord reserves the rights to, from time to time,<br />

make additions, deletions, revisions, etc., as may<br />

<br />

attachments referenced or contained herein. No<br />

<br />

<br />

Company.<br />

General Requirements For Primary Sign Design<br />

<br />

1. Imaginative signs utilizing a variety of materials<br />

are encouraged. Adaptation of current sign<br />

practices may be necessary in order to comply<br />

<br />

2. <br />

graphics visible from the common area are to<br />

<br />

prior to fabrication/installation.<br />

3. <br />

<br />

merchandise sold or services rendered, regardless<br />

of the Tenant’s legal name. Corporate<br />

crests, logos or insignia may be acceptable<br />

pending the Landlord’s approval and provided<br />

they are part of the Tenant’s name.<br />

4. One sign is permitted per store frontage. Tenants<br />

occupying corner spaces may utilize one<br />

<br />

signs, or one sign on a diagonal corner.<br />

5. Signs shall be designed as an integral part of<br />

portional<br />

to the overall storefront design, and in<br />

<br />

6. -<br />

tions.<br />

7. <br />

A.F.F. 9’-0” minimum.<br />

8. Letter size: proportional letters required; 18”<br />

-<br />

<br />

16” maximum.<br />

9. Letter dimensions of greater proportions may<br />

be considered if, in the Landlord’s opinion, the<br />

sign design is of exceptional merit and architectural<br />

quality.<br />

10. Signs are to remain on during shopping center<br />

business hours. Signs are to be controlled by<br />

a time clock and must be on a separate circuit<br />

from other lighting.<br />

11. Advertising placards, banners, pennants,<br />

names, insignia, trade-marks and other<br />

descriptive material may not be attached to the<br />

storefront or glazing.<br />

12. <br />

ness<br />

may not exceed one hundred foot-Lamberts.<br />

13. Premium quality fabrications are required.<br />

ted.<br />

Attachment devices, bolts, clips, threaded<br />

<br />

other mechanisms are to be concealed from<br />

<br />

14. <br />

15. High quality fabrications are required. Hums,<br />

<br />

Attachment devices, bolts, clips, threaded rods,<br />

IV. Signage and Graphics<br />

30


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS (Cont’d.)<br />

<br />

mechanisms are to be concealed. All labels<br />

<br />

16. tions,<br />

must bear the U.L. label, and must have<br />

current sign permits.<br />

17. Storefront signs are to state the store name<br />

and/or logo as stated on the Lease, and may<br />

not advertise or list items sold.<br />

18. Tenant may use Landlord bulkhead for lateral<br />

bracing only.<br />

19. Threaded rods or anchor bolts shall be used to<br />

mount sign letters spaced out from background<br />

<br />

not be permitted. All bolts, fastenings, and<br />

clips shall be of hot-dipped galvanized iron,<br />

stainless steel, aluminum, brass or bronze,<br />

and no black iron materials of any type shall be<br />

permitted.<br />

20. All signage shall not exceed a maximum brightness<br />

of one hundred (100) foot-candles<br />

Primary Signage Design<br />

The zone for Tenant’s primary signage is located<br />

directly above the entry portal. Optional locations<br />

<br />

<br />

that are encouraged:<br />

1. Reverse channel (halo letters) minimum of 3”<br />

ground.<br />

tive<br />

architectural shape.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

Exposed neon recessed in open metal channel<br />

letters. Letters should not be more than 4” in<br />

depth.<br />

<br />

Backs of exposed neon tubes are to be<br />

blacked out.<br />

<br />

<br />

<br />

at all fascia penetrations and must compliment.<br />

-<br />

<br />

letters routed out and formed letters protruding<br />

beyond the routed out letter.<br />

<br />

light source)<br />

<br />

surface<br />

Gold leaf on glass or stone<br />

Silk-screened glass or metal panels<br />

Indirect illumination on non-internally illuminated<br />

signs (artisan type panel signs).<br />

ALTERNATE SIGNAGE<br />

Storefront Window Signs<br />

<br />

identity, it is to be located at the pedestrian level on<br />

the inside face of the storefront glass.<br />

1. <br />

<br />

2. Glazing signs are to be translucent (similar to<br />

frosted glass), reverse-reading and applied<br />

directly to the interior of the glass surface.<br />

3. Tenant graphics on storefront glass shall be<br />

<br />

logos)<br />

4. <br />

<br />

5. mum<br />

of three (3”) inches in height.<br />

Threshold Signs<br />

In addition to storefront signs, Tenants are encour-<br />

<br />

<br />

individual basis.<br />

1. Threshold signs are to be graphics comprised<br />

of logos, crests and accent.<br />

2. <br />

<br />

3. <br />

metal and terrazzo inlays.<br />

4. Not to extend beyond their lease line into the<br />

Center.<br />

IV. Signage and Graphics<br />

31


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS (Cont’d.)<br />

Awning Signage<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

9.<br />

<br />

or metal are the preferred materials of choice<br />

<br />

<br />

tion<br />

of the Landlord.<br />

Additional signage in addition to the Tenant’s<br />

<br />

sole discretion of the Landlord.<br />

Signage may occur on the valence of the<br />

<br />

a contrasting color.<br />

<br />

only.<br />

Logos are highly encouraged. Symbols<br />

<br />

<br />

and interest to the storefront design. Logos<br />

<br />

<br />

<br />

<br />

<br />

be a minimum of eight feet (8’-0”) above the<br />

<br />

cable<br />

codes.<br />

<br />

vinyl materials shall not be permitted.<br />

<br />

good condition at the sole expense of the<br />

Tenant’s.<br />

Blade Sign<br />

<br />

1.<br />

2.<br />

<br />

of the store (if in the opinion of the Landlord<br />

additional signage is merited due to the visibility<br />

or location of the storefront sign.)<br />

<br />

special circumstances.<br />

Prohibited Signs/materials<br />

1. Internally illuminated plexi-faced channel letters.<br />

2. <br />

signs.<br />

3. minated<br />

translucent backgrounds and silhouetted<br />

letters.<br />

4. Exposed skeleton neon applied directly to<br />

fascia element.<br />

5. front.<br />

6. Freestanding tripod signs.<br />

7. Flashing, scintillating, moving, sequencing,<br />

audible or odor producing signs.<br />

8. Paper, cardboard and Styrofoam signs.<br />

9. Credit card and advertising placards, decals,<br />

stickers or trademarks.<br />

10. Manufacturer labels.<br />

11.<br />

12.<br />

Carpet or rubber entry mat signs.<br />

<br />

13. Other signs deemed unsuitable by the Landlord.<br />

14. Signs employing unedged or uncapped plastic<br />

<br />

fastenings.<br />

15. <br />

ing<br />

permitted.<br />

Sign Area Calculations<br />

Sign area calculations shall be made by circumscribing<br />

a “box” around the main body of the sign.<br />

ments:<br />

1. Area of the sign shall be calculated by;<br />

2.<br />

tiplied<br />

by 2/3 equals the MAXIMUM sign<br />

area in square feet.<br />

Width of the sign shall be calculated by;<br />

Dividing the overall sign area, by the maximum<br />

letter height.<br />

Sample Sign Area Calculation:<br />

1. <br />

square feet of sign area.<br />

2. If the maximum letter height of 1’-6” is desired,<br />

<br />

<br />

height.<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

IV. Signage and Graphics<br />

32


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS (Cont’d.)<br />

PLAN SUBMITTAL GUIDELINES<br />

Drawing Preparation<br />

Prior to Tenant preparing calculations, designs,<br />

rial<br />

submittals (collectively referred to as Tenant’s<br />

<br />

architect, contractor and engineers shall thoroughly<br />

<br />

<br />

Tenant’s Architect and Sign Contractor shall make a<br />

physical on-site inspection of the premises to verify<br />

the “as-built” location, the applicable “zone condition”<br />

and physical dimensions of the premises. Failure<br />

to do so shall be at the risk and sole expense of<br />

the Tenant.<br />

<br />

<br />

fully detailed and dimensioned scaled preliminary<br />

<br />

Tenant’s preliminary plans shall be prepared in full<br />

<br />

state and national ordinances, rules and regulations.<br />

The preliminary design submittal is intended<br />

<br />

Tenant’s basic design intentions for the tenant’s<br />

<br />

-<br />

-<br />

<br />

selection, its method of application, or its detail of<br />

<br />

contained in the Design Manual for the Mall.<br />

Review Process<br />

<br />

approve Tenant’s plans for conformance to the<br />

Center’s design criteria. Landlord’s approval shall<br />

not be deemed to certify that Tenant’s plans comply<br />

<br />

-<br />

ances<br />

and property lines.<br />

Landlord’s Tenant Coordinator shall notify Ten-<br />

<br />

<br />

<br />

after receipt of any such notice from the Landlord’s<br />

Tenant Coordinator, Tenant’s Contractor/Architect<br />

<br />

as required to obtain Tenant Coordinator’s approval<br />

ings<br />

to Landlord for preliminary approval.<br />

Incomplete Submittals<br />

<br />

<br />

<br />

NOTE:<br />

DRAWINGS PREPARED BY A CONTRACTOR<br />

WHO IS NOT LICENSED FOR THE DISCIPLINE<br />

IN QUESTION WILL NOT BE ACCEPTED;<br />

DRAWINGS RECEIVED VIA FACSIMILE WILL<br />

NOT BE REVIEWED. THIS IS DUE TO THE<br />

POOR IMAGE QUALITY OF THE TRANSMITTED<br />

DOCUMENTS.<br />

Drawing Requirements<br />

Tenant’s licensed sign contractor shall submit<br />

, directly to<br />

Landlord’s Tenant Coordinator, as instructed, for<br />

<br />

must be fully detailed and dimensioned, and shall<br />

tion:<br />

1. Elevation of the storefront including signage<br />

<br />

features, etc., and fully detailed/dimensioned<br />

sections and details through the storefront.<br />

2. <br />

<br />

Storefront Plan, Elevation and Sectional<br />

<br />

Details of the Signage at 1/2 inch scale or<br />

larger.<br />

Storefront Signage at 1/2 inch scale.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

<br />

<br />

signage.<br />

<br />

<br />

output voltage of transformers. PK housing, (or<br />

other U.L. approved insulating sleeve approved<br />

by Landlord and local building codes), is<br />

<br />

<br />

<br />

<br />

and transformers. NONE of these items shall<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

IV. Signage and Graphics<br />

33


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS (Cont’d.)<br />

8.<br />

9.<br />

10.<br />

be visible to the public from any portion of the<br />

Mall.<br />

<br />

dimension (in mm) of tubes to be used.<br />

Type of lamps.<br />

<br />

Sign Construction / Installation<br />

1. The Tenant is responsible for all signs, permits,<br />

<br />

2. ings,<br />

conduit, boxes, electrode boxes and other<br />

<br />

3. <br />

are not permitted.<br />

4. Metal sign materials, fastenings and clips of<br />

all types, shall be hot dipped galvanized iron,<br />

stainless steel or brass. Black iron materials of<br />

any type are not permitted.<br />

5. Labels on exposed sign surfaces are not<br />

permitted, except those required by local ordinances.<br />

Any required labels must be inconspicuous.<br />

6. All electrical sign components must be U.L.<br />

labeled.<br />

7. cation).<br />

Insurance Requirements<br />

Please contact Tenant Coordination for Insurance<br />

Information.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

Exterior Sign Criteria<br />

<br />

<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

Wording of the signage shall be limited to the<br />

Tenant’s trade name and shall not include<br />

<br />

rendered, regardless of Tenant “legal name.”<br />

Logos may be permitted at the discretion of the<br />

Landlord.<br />

<br />

<br />

be a minimum of 6” in depth, and must be<br />

<br />

spacers.<br />

<br />

<br />

<br />

letters. Letters should not be more than 9” in<br />

<br />

on an individual mall basis. Trim caps are to<br />

match letter color.<br />

-<br />

tion<br />

current of 20 milli-amperes.<br />

<br />

<br />

determined by the lineal footage of the Tenants<br />

leaseline.<br />

<br />

<br />

determined on an individual mall basis. Trim<br />

caps are to match letter color.<br />

<br />

conductors, transformers, etc. shall be permitted.<br />

8. PK housing (or other U.L. approved insulating<br />

sleeve approved by Landlord and local building<br />

tions<br />

and must be indicated on the sign shop<br />

<br />

9. <br />

conductors, transformers, etc. shall be permitted.<br />

10. All signage and sign components shall be UL<br />

listed.<br />

11. All signs, bolts, fastenings, and clips shall be<br />

of hot-dipped galvanized iron, stainless steel,<br />

aluminum, brass or bronze, and no black iron<br />

materials of any type shall be permitted.<br />

12. All exterior signage components (logos and<br />

all individual letters) shall stand off the face<br />

<br />

This shall be accomplished by the use of nylon<br />

<br />

and the back of the logo or letter.<br />

13. Tenant is responsible for the operation of the<br />

Tenant’s sign contractor.<br />

14. Electrical service to the Tenant’s sign shall be<br />

installed by the Tenant and not be part of the<br />

Landlord’s operating costs. The sign shall be<br />

controlled by a time clock.<br />

Construction Requirements For Exterior Signage<br />

1. All metal letters shall be fabricated using full-<br />

<br />

IV. Signage and Graphics<br />

34


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

SIGNAGE AND GRAPHICS (Cont’d.)<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

9.<br />

<br />

the Landlord shall indicate location of all openings<br />

for conduit sleeves and supports in sign<br />

<br />

<br />

<br />

Tenant’s sign contractor shall repair any<br />

<br />

Tenant shall be fully responsible for the operations<br />

of Tenant’s sign contractors.<br />

<br />

<br />

Tenant and/or his subcontractors.<br />

If Tenant has a non-customer door for receiving<br />

merchandise, Tenant may place its name and<br />

address on said door in a location approved in<br />

<br />

<br />

than one (1) Tenant uses the same door, each<br />

name and address may be applied. Landlord’s<br />

Tenant Coordinator shall also specify the size,<br />

type and color of numbers.<br />

Tenant may install on its Mall storefront, if<br />

required by the US Postal Service, only the<br />

numbers of Tenant’s street address and only in<br />

such location as Landlord shall specify. Landlord’s<br />

Tenant Coordinator shall also specify<br />

size, type and color of numbers.<br />

Floor signs consisting of inlaid logos or name<br />

<br />

<br />

<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

Height of Exterior Signs/Logos<br />

1. Logos cannot exceed 30” square depending<br />

upon the application.<br />

2. Uppercase letters shall not exceed 24” in<br />

height.<br />

3. <br />

height<br />

4. <br />

<br />

on an individual mall basis. Trim caps are to<br />

match individual letter color.<br />

Again this criterion is intended to assist you, the<br />

Tenant, during the design and construction of your<br />

sign. If you should have any questions prior to and<br />

during the submittal process please contact your<br />

Tenant Coordinator.<br />

IV. Signage and Graphics<br />

35


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

MECHANICAL/PLUMBING SUMMARY<br />

Restaurant Tenants<br />

Landlord Provided:<br />

<br />

Landlord to provide and install grease interceptors sized per the City of <strong>Scottsdale</strong><br />

interpretation of the IPC 2006 code, in a predetermined location, one<br />

per Restaurant. Tenant to reimburse the cost for equipment and installation to<br />

Landlord.<br />

<br />

<br />

Gas service to a central distribution point.<br />

<br />

Kitchen exhaust<br />

Designated structurally enhanced roof area for Tenant’s designated HVAC and<br />

Kitchen exhaust rooftop equipment<br />

<br />

Tenant Provided:<br />

<br />

<br />

only.<br />

Tenant to connect to common toilet exhaust duct<br />

Gas distribution from central point to Tenant’s space by Tenant. Gas meter<br />

and installation by Tenant at Tenant’s cost<br />

All Kitchen Equipment by Tenant<br />

HVAC – complete system provided by Tenant at Tenant’s expense.<br />

<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

designated roof location.<br />

2. Kitchen exhaust, all by Tenant, to be located in Landlord desig<br />

nated roof location<br />

3. All roof mounted fans and equipment to be located in Landlord<br />

designated roof location<br />

4. Make-up air duct system<br />

Sprinkler System: Tenant to modify heads to accommodate their space<br />

layout<br />

Inline Tenants<br />

Landlord Provided:<br />

<br />

<br />

<br />

<br />

HVAC: Minimum of 1 ton per 250 sf<br />

Tenant Provided:<br />

<br />

locations<br />

Tenant to connect to common toilet exhaust duct<br />

<br />

Landlord to provide requirements for VAV box by Tenant.<br />

Sprinkler System: Tenant to modify heads to accommodate their space<br />

layout<br />

V. Technical Criteria<br />

36


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ELECTRICAL/PLUMBING SUMMARY<br />

In Line and Restaurant Tenants<br />

Landlord Provided:<br />

<br />

<br />

<br />

2” empty electrical conduit per location-277/480 volt, 3 phase service<br />

1” empty telephone conduit per location<br />

3/4” Fire Alarm conduit, and 1” EMS conduit<br />

Tenant Provided:<br />

Final connection to Landlord’s service by Landlord’s designated contractor at<br />

Tenant’s cost.<br />

Final connection to Landlord’s distribution panel by Landlord’s designaged<br />

contractor at Tenant’s cost.<br />

Final connection to Landlord’s Fire Alarm Panel by Landlord’s designated contractor<br />

at Tenant’s cost and expense.<br />

Final connection to Landlord’s Energy Management System using Landlord’s<br />

designated contractor at Tenant’s cost and expense.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

37


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

HVAC SYSTEMS<br />

<br />

Tenant shall install a heating, cooling and ventilating system as designed by<br />

<br />

Landlord interface requirements, NFPA recommended practice, and this criterion.<br />

<br />

design load calculations, prepared and sealed by a State of Arizona Registered<br />

<br />

1.<br />

2.<br />

3.<br />

<br />

Completed Load Submission Form.<br />

<br />

Codes and Standards<br />

1. International Mechanical Code<br />

2. International Building Code<br />

3. NFPA 90A<br />

4. NFPA 101<br />

HVAC Design Temperatures<br />

Design Conditions Indoor Outdoor<br />

<br />

<br />

* Cooling is only provided during normal operating hours<br />

<br />

Winter No heat provided<br />

GENERAL<br />

1. Tenant shall not cause, for any reason, the delivery of air quantities in excess<br />

of that approved by the Landlord’s engineer.<br />

2. Each tenant shall be responsible for providing ducted return air openings,<br />

<br />

the return air system.<br />

3. <br />

than 40 square feet for return air.<br />

4. lord<br />

provided variable air volume (VAV) air handling unit (AHU). Tenant<br />

shall be responsible for tapping the Landlord’s trunk duct and provid-<br />

<br />

install a VAV box or boxes as required by Tenant’s HVAC design. Each<br />

<br />

be connected to the Landlord’s direct digital control (DDC) Building<br />

Automation System (BAS). A return air grill shall be located above each<br />

<br />

5. <br />

6. <br />

<br />

toilet room, the Tenant is responsible for providing a toilet exhaust fan,<br />

<br />

<br />

<br />

operational during normally occupied hours.<br />

7. -<br />

<br />

-<br />

-<br />

<br />

<br />

8. <br />

9. <br />

diffusers or registers install as required to achieve good air distribution<br />

<br />

shall have integral volume control devices.<br />

10. Duct penetrations at Landlord’s main trunk duct shall not exceed the<br />

size of the inlet at the VAV box by more than one nominal size.<br />

11. <br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

38


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

HVAC SYSTEMS (Cont’d.)<br />

prior to the inlet of the VAV box.<br />

12. <br />

<br />

13. <br />

<br />

column.<br />

14. Service corridors are not conditioned.<br />

15. <br />

dampers and install same.<br />

16. Special cooling and heating systems, such as required for refrigeration display<br />

<br />

equipment, shall be provided by the “Tenant. Location of equipment serving<br />

special cooling and heating equipment shall be designated and/or approved by<br />

the Landlord.<br />

17. At the completion of Tenant’s installation, the mechanical systems shall be<br />

<br />

<br />

<br />

performed under the direct supervision of a State of Arizona registered Professional<br />

Engineer.<br />

18. <br />

<br />

air back the equipment via an opening at the top of the bulkhead. These areas<br />

<br />

stores only.)<br />

19. <br />

is above any hard ceiling areas. Equipment above the hard ceiling shall have<br />

<br />

access the equipment for servicing.<br />

20. All pet stores, Hair and Nail Salons, and similar odor producing tenants shall<br />

<br />

21. The smoke control system serves only the mall common areas, it does not<br />

serve the tenant spaces.<br />

RESTAURANT EXHAUST REQUIREMENTS<br />

1. Exhaust for food service tenants shall be through the roof in a manner<br />

<br />

exhaust duct, fan and make-up air provisions supplied by the Tenant.<br />

<br />

<br />

<br />

air supply in addition to Tenant’s make-up intake.<br />

2. <br />

<br />

<br />

3. Discharge of all exhaust fans shall be kept at a minimum of 20 feet from<br />

all mall air intakes.<br />

4. Rooftop mounted grease exhaust fans shall be located over a spill containment<br />

device in order to protect the roof surface.<br />

5. -<br />

<br />

Landlord upon completion.<br />

6. <br />

and installed at the Tenant’s expense.<br />

ODOR CONTROL EXHAUST REQUIREMENTS<br />

1. mum,<br />

shall be maintained during all hours that the tenant is operating<br />

it’s business in the leased premises.<br />

2. <br />

supply air to offset the quantity of air exhausted.<br />

3. A commercial roof mounted exhaust fan and curb shall be used. Roof<br />

<br />

requirements.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

39


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

HVAC SYSTEMS (Cont’d.)<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

9.<br />

<br />

The exhaust fan shall be ducted to ceiling grilles located approximately in<br />

the center and rear of the leased premises. The system shall be designed<br />

to cause the exhaust air to gravitate from the mall common area to the odor<br />

producing area and then to the exhaust system.<br />

tomer<br />

service area.<br />

<br />

<br />

<br />

and approval.<br />

Discharge of all exhaust fans shall be kept at a minimum of 20 feet from all<br />

mall air intakes.<br />

<br />

be in operation during all hours that the tenant is operating its business in the<br />

<br />

VAV BOXES<br />

1. All VAV boxes shall use a thermostat/controller provide by the Landlord’s BAS<br />

contractor at Tenant’s expense.<br />

2. <br />

3. <br />

be purchased and connected through the Landlord’s BAS contractor Integrated<br />

Controls Systems at Tenant’s expense.<br />

Integrated Controls Systems<br />

<br />

602-454-6310<br />

<br />

4. Any BAS controls that must be relocated shall be done by the Landlord’s BAS<br />

contractor at Tenant’s expense.<br />

5. VAV boxes must be manufactured by Envirotec, Titus or Trane. Note that VAV<br />

<br />

lead time for ordering VAV boxes in their critical path construction<br />

schedule.<br />

Contact - Dave Mure’<br />

Phone: 480-483-9622<br />

6. -<br />

<br />

controls contractor, Envirotec.<br />

7. <br />

-<br />

<br />

each VAV box for service.<br />

8. The Tenant’s electrical contractor is responsible for rough in of a single<br />

<br />

-<br />

<br />

ROOFING<br />

1. <br />

<br />

roof penetrations required by Tenant and approved by the Landlord shall<br />

<br />

<br />

2. <br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

40


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ELECTRICAL CRITERIA<br />

General Design/Construction Coordination<br />

mitted<br />

at this location.<br />

The electrical criteria is provided for the purpose<br />

of designing the Tenant’s electrical system. This<br />

criteria is provided as a guideline for Tenant’s<br />

Engineer. It is the Tenant’s responsibility to verify<br />

<br />

codes and standards.<br />

1. <br />

<br />

<br />

<br />

or conduit above.<br />

2. Tenant’s equipment in the mall electric room<br />

<br />

and space number.<br />

3. <br />

locations and at smoke detectors above the<br />

ceiling.<br />

4. <br />

<br />

devices, hanger supports and other items<br />

required for a complete distribution must be<br />

furnished and installed by Tenant.<br />

5. <br />

<br />

<br />

cutting and patching must be provided by<br />

Tenant.<br />

<br />

<br />

mance<br />

to basic mall requirements. The Landlord<br />

<br />

the Landlord accept responsibility for the Tenant’s<br />

adherence to governing codes.<br />

<br />

<br />

1.<br />

2.<br />

3.<br />

-<br />

<br />

line riser Diagram. Documents must be signed<br />

and sealed by a Licensed Engineer in the state<br />

<br />

<br />

calculations and meter information.<br />

<br />

<br />

steel structure.<br />

Power Source<br />

Landlord has provided facilities for the delivery<br />

<br />

<br />

distribution electrical rooms at each building .<br />

Main Switch & Conduits<br />

For Retail Tenants, the Landlord has provided a<br />

main electrical Tenant distribution panelboard for<br />

-<br />

<br />

<br />

<br />

ant’s<br />

space. The conduit to the Tenant space has<br />

<br />

<br />

panleboard to the Tenant space shall be a 2” race-<br />

<br />

has also provided a 1” telephone service conduit<br />

<br />

size and location of the previously mentioned distribution<br />

equipment, conduits and electrical room.<br />

<br />

<br />

<br />

distribution panelboards shall be performed by the<br />

Landlord’s approved Electrical Contractor, at the<br />

Tenant’s expense. Each Retail Tenant (10,000sf or<br />

larger), Food Court Tenant, or restaurant Tenant is<br />

<br />

the Landlord electrical room that serves the applicable<br />

Tenant. Coordinate location and all installa-<br />

<br />

1.<br />

2.<br />

3.<br />

4.<br />

All tenant panelboards and associated distribution<br />

equipment shall be provided by the tenant.<br />

Note that transformation for any voltage other<br />

than 277/480 shall be furnished by the tenant<br />

<br />

<br />

<br />

<br />

the space.<br />

<br />

at each VAV box and fan coil unit for service.<br />

Each fan coil units must have a combination<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

41


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ELECTRICAL CRITERIA (Cont’d.)<br />

5.<br />

6.<br />

7.<br />

8.<br />

9.<br />

<br />

All fan coils must be 480 volt, 3-phase and be<br />

ant’s<br />

space. Tenant is responsible for providing<br />

branch circuit (s) to 480 volt, 3 phase fan coil<br />

<br />

The Tenant’s electrical contractor must provide<br />

-<br />

<br />

Tenant’s space. This breaker must have a lock<br />

ing.<br />

Restroom toilet exhaust fans must be tied to<br />

<br />

An electrical load calculation form can be found<br />

in the appendix of this handbook. The form<br />

must be complete and submitted to Landlord<br />

<br />

<br />

<br />

sections (s). The service utility is Salt River<br />

<br />

source available in the tenant spaces. The<br />

<br />

isolated, and does not have “transient voltage<br />

surge suppression” equipment.<br />

Maximum Loads<br />

Loads in general shall be governed by the local<br />

Energy Codes, and per City, State, IBC/IEC and<br />

<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

-<br />

<br />

<br />

is available from the Landlord via the utility or the<br />

Tenant distribution panelboard. Landlord shall<br />

provide such service upgrades at cost (including<br />

engineering and related overhead expenses) to be<br />

reimbursed by the Tenant.<br />

Telephone Service<br />

Tenant shall make application to the serving tele-<br />

<br />

their requirments.<br />

<br />

demised premises to Landlord’s main telephone<br />

lord<br />

using Landlord’s designated contractor. Tenant<br />

shall extend conduit to the Landlord’s backboard<br />

<br />

Lighting<br />

(See Lighting Requirements outlined in Section II<br />

Architectural design Criteria.)<br />

Tenant is responsible for lighting system control,<br />

including connection to the Building Management<br />

system and connection to the Fire Alarm system.<br />

All emergency lighting, exit signs, horns and<br />

strobes must be provided by Tenant as required by<br />

code.<br />

Wire and Disconnect Sizing<br />

ment<br />

or the Tenant distribution panelboard shall<br />

be sized to meet the calculated demand load<br />

requirements of the Tenant space and minimum<br />

overcurrent protection rating of the circuit breaker<br />

<br />

equipment or Tenant distribution panel. Current<br />

limiting circuit breakers are not permitted. The<br />

circuit breaker shall be purchased and installed<br />

by a Landlord’s approved Electrical Coordinator at<br />

the Tenant’s expense. The circuit breaker may not<br />

<br />

breaker device for applicable Tenant distribution<br />

panelboard or utility service entrance equipment.<br />

<br />

as required to accommodate any voltage drop<br />

<br />

<br />

approved Electrical Contractor to complete feeder<br />

termination at panelboard. The Tenant shall provide<br />

<br />

the distribution to Tenant loads. This can be in the<br />

<br />

the main Tenant panel. Tenant General Contrac-<br />

<br />

approved electrician to supply and install circuit<br />

breaker and complete feeder termination at <strong>Scottsdale</strong><br />

<strong>Fashion</strong> <strong>Square</strong> panel board.<br />

Due to the high available interrupting currents (AIC)<br />

present at the Landlord’s I-Line (type) Tenant dis-<br />

<br />

<br />

<br />

V. Technical Criteria<br />

42


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ELECTRICAL CRITERIA (Cont’d.)<br />

can choose to:<br />

1.<br />

2.<br />

Have the landlord provide at the Tenant’s<br />

expense a circuit breaker in the Tenant distribu-<br />

<br />

<br />

Provide an overcurrent protection device at the<br />

Tenant main disconnecting means that is U.L.<br />

<br />

the upstream circuit breaker provided in the<br />

Landlord’s <strong>Square</strong> D I-Line Tenant distribution<br />

panelboard. All circuit breakers in the Tenant<br />

distribution panelboards are <strong>Square</strong> D Type<br />

EG, FG, KH, LH, EJ, FC, FJ, KC, LC, or LX (or<br />

equal by G.E.) as applicable per the required<br />

Tenant circuit breaker size and available short<br />

circuit current at each Tenant distribution<br />

panelboard. Tenant may use a <strong>Square</strong> D type<br />

EDB or EGB circuit breaker to achieve a series<br />

cal<br />

Engineer, <strong>Square</strong> D, or G.E. as appropriate.<br />

-<br />

<br />

<br />

Materials<br />

Materials, products and equipment including all<br />

<br />

<br />

<br />

<br />

Code and other applicable codes; and shall be<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

<br />

<br />

exterior elements or required by codes shall be<br />

-<br />

<br />

Conduit<br />

<br />

or electrical metallic tubing.<br />

Conductors/Wiring<br />

-<br />

<br />

<br />

BX, Romex MC or any other armored or metal clad<br />

-<br />

<br />

60 degrees Celsius shall be THW or THWM of high<br />

<br />

coded insulation per code.<br />

<br />

<br />

recommendations.<br />

Panelboards<br />

<br />

<br />

Circuit breakers shall be thermal magnetic type and<br />

<br />

of the common pull type. Distribution panelboards,<br />

<br />

utilizing automatic circuit breakers.<br />

Cabinets shall be constructed of code gauge<br />

sheet steel door and trim. All panelboards shall<br />

<br />

door enclosure single piece assembly. Panelboard<br />

bussing shall be cooper tin-plated aluminum. All<br />

<br />

<br />

Tenant Space (including Kiosks) unless permitted<br />

<br />

Transformers<br />

<br />

level Class H.<br />

Devices<br />

<br />

<br />

Floor Boxes<br />

<br />

<br />

lord<br />

or the Landlord’s Structural Engineer.<br />

Grounding<br />

Tenant’s electrical system shall be grounded to<br />

<br />

<br />

<br />

V. Technical Criteria<br />

43


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

ELECTRICAL CRITERIA (Cont’d.)<br />

Telephone Service<br />

Tenant provide and install their complete telephone<br />

system. Tenant shall make application to the serving<br />

telephone company for service and shall comply<br />

<br />

Security System<br />

If so required or desired, Tenant shall provide<br />

<br />

<br />

<br />

<br />

permitted.<br />

Fire Alarm & Detection System<br />

<br />

via the systems’ vendor. Tenant shall be respon-<br />

<br />

<br />

be performed by a Landlord approved Contractor.<br />

<br />

<br />

Miscellaneous Equipment<br />

All equipment not described herein such as (but not<br />

limited to) clocks, signage, or music systems shall<br />

be provided by Tenant.<br />

Tenant must furnish and install a main electrical<br />

disconnect inside Tenant’s space.<br />

<br />

<br />

<br />

<br />

system. At a minimum for Restaurant Tenants, Ten-<br />

<br />

<br />

monitoring purposes. Landlord has provided indication<br />

and annunciation circuitry at the service corri-<br />

<br />

into Tenant space for expansion.<br />

<br />

detection system, the system shall be compatible to<br />

<br />

<br />

shall annunciate back to the Landlord’s addressable<br />

<br />

Tenant shall be responsible at all times for coordi-<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

44


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

PLUMBING CRITERIA<br />

Tenant shall install a plumbing system as designed<br />

<br />

plumbing codes, Landlord interface requirements<br />

and criteria. Tenant shall submit, for Landlord’s<br />

<br />

load calculations prepared and sealed by a State of<br />

Arizona Registered Professional Engineer. Submit-<br />

<br />

1.<br />

2.<br />

3.<br />

4.<br />

Completed Plumbing Equipment Submission<br />

form<br />

Floor plan<br />

Riser Diagrams<br />

<br />

for the demised premises<br />

Codes and Standards<br />

1.<br />

2.<br />

3.<br />

4.<br />

International Plumbing Code<br />

International Building Code<br />

International Mechanical Code<br />

NFPA 101<br />

<br />

1.<br />

2.<br />

<br />

premises. This stub out shall be located either<br />

<br />

service corridor. 2” line for Restaurant Tenants<br />

1” line for In-line Tenants<br />

<br />

6” line for Restaurants<br />

4” line for In-line Tenants<br />

3.<br />

Vent piping located either in the tenant<br />

<br />

corridor.<br />

lord’s<br />

domestic valve or Main:<br />

1.<br />

2.<br />

<br />

out. If the Tenant requirements exceed<br />

the capacity of the stub out provided, the<br />

Tenant shall notify the Landlord and obtain<br />

<br />

<br />

<br />

<br />

<br />

<br />

and vent piping to Landlord furnished stub<br />

outs.<br />

General Requirements<br />

1.<br />

2.<br />

In the event that the Tenant requires<br />

<br />

<br />

<br />

-<br />

<br />

<br />

<br />

core drilled.<br />

<br />

the Tenant’s space shall be the Tenant’s<br />

<br />

the Landlord at Tenant’s expense.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

-<br />

-<br />

<br />

<br />

<br />

<br />

Tenant shall install a full port, ball type<br />

<br />

<br />

space. This valve shall be clearly labeled<br />

“Water Shut Off Valve”.<br />

Water meter shall be installed to record all<br />

<br />

hair salons, nail salon, and pet stores at<br />

Tenant’s expense. The meter shall be<br />

installed at eye level or have a remote<br />

<br />

shall read in gallons.<br />

<br />

<br />

<br />

<br />

<br />

extended by the Tenant from the valved<br />

connection as indicated on the Tenant’s<br />

<br />

<br />

<br />

95-5 solder. Tenant shall install air chambers<br />

or shock absorbers in piping systems<br />

<br />

hammer. Branch piping shall have accessible<br />

service valves. Provide shut off valves<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

45


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

PLUMBING CRITERIA (Cont’d.)<br />

8. <br />

<br />

installed by the Tenant at Tenant’s expense.<br />

Heaters shall be of storage or instantaneous<br />

type and shall be UL listed. The relief valve<br />

shall be piped to an open drain. Storage type<br />

<br />

sheet metal pan piped to a visible drain.<br />

9. Tenants requiring supplementary plumbing<br />

<br />

in the immediate vicinity of plumbing rough-in<br />

provided by the Landlord. Tenant is advised<br />

<br />

provided in the rear of the demised premises.<br />

<br />

location of service.<br />

10. Fixtures shall be as manufactured by American<br />

<br />

<br />

<br />

Tenants shall use pressure assisted, tank type<br />

toilets.<br />

11. <br />

lected<br />

and discharges into a Landlord provided<br />

grease interceptor.<br />

12. All in-line food service tenants and any tenant<br />

discharging grease or oil into the sanitary<br />

system, shall furnish and install, at Tenant’s<br />

expense, a grease interceptor of slab-on-grade<br />

<br />

local codes. Tenant shall inspect and clean<br />

grease interceptor as required to prevent the<br />

<br />

<br />

related to the correction of such discharge.<br />

Tenant shall maintain an adequate record<br />

of the regularly scheduled maintenance<br />

required to prevent blockage of the grease<br />

<br />

lord’s<br />

request.<br />

GAS SERVICE CRITERIA<br />

Food Service Tenants<br />

1.<br />

2.<br />

3.<br />

Natural gas service may be available for<br />

food service tenants if approved by the<br />

Landlord and local utility service provider.<br />

When available, natural gas service shall<br />

be used for food preparation purposes only<br />

<br />

<br />

<br />

be permitted.<br />

<br />

<br />

<br />

<br />

Distribution piping from the discharge side<br />

of the gas meter, regulators, and related<br />

miscellaneous equipment required for a<br />

complete approved system shall be the sole<br />

responsibility of the Tenant. Tenant shall<br />

<br />

<br />

utility company fees, permits and inspection<br />

fees related to the installation.<br />

The Tenant shall be responsible for obtaining<br />

all necessary approval prior to the instal-<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

lation of any gas piping, including approval<br />

of the utility company and Landlord for<br />

routing.<br />

The gas piping installation shall be installed<br />

<br />

<br />

rules and regulations of the utility company<br />

and any local and state agency involved in<br />

the regulation of this type of installation.<br />

Piping and installation shall be in accor-<br />

<br />

an alternate, the piping may be furnished<br />

and installed by the Landlord at the Tenant’s<br />

expense.<br />

Natural gas delivery pressure at the meter<br />

ing<br />

greater pressure, if it is available, for the<br />

operation of their food preparation equip-<br />

<br />

by the utility company to provide such special<br />

service demands, including any costs<br />

<br />

a result of the Tenant’s requirements.<br />

<br />

<br />

involvement. Each Tenant shall be individually<br />

metered by the utility company.<br />

Tenant shall prime and paint all gas lines<br />

<br />

<br />

ROOFING<br />

1.<br />

There shall be no penetrations of the roof<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

46


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

PLUMBING CRITERIA (Cont’d.)<br />

2.<br />

3.<br />

-<br />

<br />

such roof penetrations required by Tenant and<br />

approved by the Landlord shall be engineered<br />

-<br />

<br />

<br />

<br />

performed under this section shall be per-<br />

<br />

Tenant’s expense.<br />

All Tenant roof top equipment must be placed<br />

on a roof curb and installed by the landlord’s<br />

<br />

FIRE PROTECTION<br />

<br />

by the Landlord’s required contractor at the Tenant’s<br />

expense<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

47


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

FIRE ALARM<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

-<br />

<br />

and True Alarm Addressable Class “B” initiating circuits.<br />

-<br />

-<br />

<br />

Simplex Seriers 4903 combination speaker strobes<br />

Simplex Series 4098 photoelectric smoke detectors for initiation of Mall/<br />

Tenant smoke control system<br />

Simplex Series 4098 photoelectric duct mounted smoke detectors for all<br />

fan coil unit supply ducts<br />

<br />

<br />

Tenant shall be responsible for system programming and testing. Further information<br />

regarding programming, testing, scheduling, etc., can be obtained from<br />

Simplex (see required subcontractor’s list).<br />

<br />

<br />

<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

48


<strong>Scottsdale</strong> <strong>Fashion</strong> <strong>Square</strong><br />

Phase 10-Barney’s Expansion 7014 E. Camelback Road, <strong>Scottsdale</strong>, AZ 85251<br />

STRUCTURAL CRITERIA<br />

<br />

<br />

criteria is provided as a guideline for Tenant’s Engineer.<br />

It is the Tenant’s responsibility to verify exist-<br />

<br />

and standards.<br />

<br />

<br />

mance<br />

to basic mall requirements. The Landlord<br />

<br />

accept responsibility for the Tenant’s adherence to<br />

governing codes.<br />

<br />

<br />

<br />

<br />

<br />

Center is located.<br />

General Requirements<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

8.<br />

9.<br />

The Tenant’s storefront must be structurally<br />

self-supported. Tenant may not support the<br />

storefront from the bulkhead or fascia. Structural<br />

support for Tenant storefronts must be<br />

<br />

architect and engineer of record are responsible<br />

for this design<br />

Fixtures and equipment may not be attached to<br />

<br />

<br />

that require support from the steel structure or<br />

for all roof top equipment. Tenant’s architect<br />

and engineer of record are responsible for this<br />

design.<br />

Joist reinforcing is required for roof top equip-<br />

ings.<br />

<br />

<br />

<br />

lbs. or more.<br />

<br />

<br />

<br />

<br />

<br />

Landlord.<br />

<br />

the expense of the Tenant, all structural items<br />

listed in these requirements.<br />

Structural and physical support of all sus-<br />

pended equipment in the Tenant space shall be<br />

the responsibility of the Tenant’s architect and<br />

engineer of record.<br />

Tenant Design Criteria<br />

Updated: September, 2008<br />

V. Technical Criteria<br />

49