Lightning and Surge Protection<br />
PowerPro BCD (Reducing Follow-on current)<br />
PP BCD TN 25/50 /LED(/FM)<br />
-350<br />
Combined two-pole TOV resistant Lightning Current and Surge Voltage Protective Device<br />
protection class I+II+III T1 T2 T3 (BCD),<br />
Used as equipotential bonding lightning and surge protection in single phase TN-Power Net Systems<br />
• Combined 2-pole modular Lightning Current + Surge Voltage Protective SPD, fully<br />
pre-connected and leakage current free<br />
• Fully based on patented hermetically sealed gas-filled Multi-chamber spark-gaps<br />
• No blow-out vents, no distances for safety installation required<br />
• Highly resistant against danger TOV, as no MOV to phase<br />
• Protection level ≤ 1 kV<br />
• Lightning current test level 25 kA (10/350 µs) per phase,<br />
• High self-extinguishing capability without tripping fuses<br />
• High insulation resistance R isol > 10 G Ω<br />
• Serial wiring with multifunctional screw terminal<br />
• LED for direct optical function monitoring built in<br />
• Remote monitoring by built-in potential-free /FM remote signal sensor (optional)<br />
Product description:<br />
This combined two-pole SPD type PP BCD TN 25/50/LED-350 and PP BCD TN 25/50/LED/FM-350, with remote<br />
signal contacts as well as LED monitoring, offers a complete solution for the protection of single phase TN-Power<br />
Net Systems. They are usually installed in main- or sub-distribution panels or close to equipments to be<br />
protected.<br />
Thanks to the use of the patented, hermetically sealed inert-gas-filled isolating spark-gaps, this SPD allows to<br />
achieve a very high-level discharge capacity without needing blow-out vents. This saves you from keeping the<br />
safety distance to adjoining electrical components usually necessary to avoid electric arcs and fire hazardous.<br />
As there is no risk of leakage currents, this SPD can also be installed before the electric power meter (acc. to<br />
TAB2000, installation rules of the German Union of Electric Energy Suppliers).<br />
This 2-pole SPD is capable to discharge lightning current surges of 25 kA (10/350µs) per phase and totally 50 kA<br />
(10/350µs) to PE.<br />
It self-extinguishes main supply follow-on currents up to 4 kA, so that even small fuses (>35A) will not trip.<br />
Each protective spark gap is installed in an easy-to-handle compact DIN size housing with 2 fixable snap-on clips<br />
for 35 mm DIN rail mounting on each SPD-module. Multifunctional large dimensioned screw terminals for wireand<br />
bus-bar connections. Line installation can be carried out either by parallel wiring via the multifunctional screw<br />
connection terminal L, N, or by serial V-wiring via the terminals L,N to L’,N´ connected with the two-pole busbars.<br />
Optional a sealed potential-free remote signal sensor (/FM) with thermal NC safety function can be built-in. The<br />
wire connection is made via a pluggable screw terminal block.<br />
Protects People and Valuables
Technical Data:<br />
Application:<br />
Lightning current and Surge Protective Device for single phase TN-Power Net Systems protection class<br />
I+II+III T1 T2 T3 (BCD), built in LED indication for function monitoring<br />
Type<br />
PP BCD<br />
PP BCD<br />
TN 25/50/LED -350 TN25/50/LED/FM -350<br />
Article number 38 51 00 38 51 10<br />
IEC 61643-1<br />
EN 61643-11<br />
E DIN VDE 0675-6 11/98-A1<br />
SPD class I+II+III<br />
SPD type T1 + T2 + T3<br />
BCD<br />
Nominal voltage of AC net 50/60 Hz U n [V~] 230 / 400 or 240 / 415<br />
Rated voltage (max. continuous operating voltage) 50/60 Hz U c [V~] 350<br />
Insulation resistance R isol [GΩ] > 10<br />
Voltage protection level L,N-PE at lightning impulse<br />
spark over voltage (1,2/50µs, Uoc 6kV)<br />
U as [kV] ≤ 1,0<br />
Voltage protection level at I imp U p [kV] ≤ 1,0<br />
Response time t A [ns] < 50<br />
Lightning impulse current I imp (10/350µs)<br />
[kA]<br />
[As]<br />
[kJ/Ω]<br />
Follow current extinguishing capability at U c I f [kA peak ] 4,0<br />
I peak<br />
Q<br />
W/R<br />
L, N - PE:<br />
25<br />
12,5<br />
160<br />
Short-circuit withstand capability at max. pre-fuse I k [kA rms ] 50<br />
Max. permissible line or back fuse F2 at parallel wiring [A] 250 A gL/gG<br />
Max. permissible line resp. back fuse F3 at serial wiring [A] 125 A gL/gG<br />
Operating temperature range T U [°C] -40 … +85<br />
Max. cross-sectional area [mm²] solid or stranded 50 / flexible 35<br />
Min. required / Recommended cross sectional area [mm²] Solid, stranded ore flexible…….. 10 / 25<br />
Recommended connection torque [Nm] 4,5<br />
Max. cross-sectional area for remote signal contact [mm²] 1,5<br />
Max. switching capacity of remote signal contact<br />
Material of housing / colour<br />
250V/0,5A<br />
Polycarbonate (halogen free) UL 94-V0 / yellow<br />
Environment protection category IP 20 (IEC/EN 60529)<br />
Mounting on 35 mm DIN rail form C (DIN/EN 50 022)<br />
Dimensions in mm / Diagram<br />
Dimension 2x 2 DIN-modules, acc. DIN 43880<br />
Application:<br />
If line or backup fuse (F1) is ≤ 250 A gL/gG,<br />
a back up fuse (F2) is not forced.<br />
Parallel wiring<br />
for active<br />
lines<br />
two-pol. bus-bar<br />
connection<br />
Line or backup fuse (F3) ≤ 125 A gL/gG<br />
Serial wiring<br />
for active<br />
lines<br />
PP BCD TN 25/50/LED/FM -350<br />
24.04.2007_pdf<br />
© 2007 by LEUTRON <strong>GmbH</strong><br />
Subject to technical modifications and<br />
delivery possibilities<br />