UK / IRL - Mennekes Electric Ltd
UK / IRL - Mennekes Electric Ltd
UK / IRL - Mennekes Electric Ltd
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Switch disconnectors made of AMELAN ®<br />
Disconnecting property in acc. with EN 60947 (up to 690V). Finger protection in acc. with DIN 57106 / VDE 0106 T.100.<br />
Combination units Plugs and connectors Sockets<br />
Service<br />
Image<br />
Characteristics switch disconnector<br />
Title / description<br />
Switch disconnector<br />
rigid enclosures, ample space<br />
for wiring, padlocking facilities,<br />
excellent switching capacity,<br />
open terminals and captive<br />
terminal screws<br />
IP 67<br />
Std. Pack. Qty: 1<br />
without<br />
aux. contact<br />
Rated Current<br />
Ampere<br />
Poles<br />
Auxiliary<br />
contact<br />
BS Motor<br />
rating<br />
AC3/440V<br />
kilowatt<br />
Part numbers<br />
25 3 7.5 52241 MEG<br />
25 3 7.5 52242 MEG<br />
40 3 18.5 52243 MEG<br />
40 3 18.5 52244 MEG<br />
80 3 30.0 52245 MEG<br />
80 3 30.0 52246 MEG<br />
Products with additional aux. contact (1 x NO and 1 x NC).<br />
with<br />
aux. contact<br />
without<br />
aux. contact<br />
with<br />
aux. contact<br />
without<br />
aux. contact<br />
with<br />
aux. contact<br />
Part numbers<br />
52241 MEG 52242 MEG 52243 MEG 52244 MEG 52245 MEG 52246 MEG<br />
Rated operational voltage U e<br />
IEC / EN / VDE / SEV 690V 690V 690V<br />
Main switch: Isol. voltage up to 690V 690V 690V<br />
Rated continuous current l u<br />
IEC / EN / VDE 25A 40A 80A<br />
Rated operational current l e<br />
IEC / EN 25A 40A 80A<br />
Rated operational current at 50 up to 60 Hz<br />
AC-23A IEC / EN / VDE<br />
3 phase 220-240V 5.5 kW 11.0 kW 18.5 kW<br />
3 pole 380-440V 11.0 kW 22.0 kW 18.5 kW<br />
600-690V 11.0 kW 18.5 kW 30.0 kW<br />
AC-3 IEC / EN / VDE<br />
3 phase 220-240V 4.0 kW 7.5 kW 15.0 kW<br />
3 pole 380-440V 7.5 kW 18.5 kW 30.0 kW<br />
600-690V 7.5 kW 15.0 kW 30.0 kW<br />
Rated breaking capacity<br />
AC-23A / AC-3 motor switch 220-240V 220A 350A 550A<br />
380-440V 220A 350A 550A<br />
600-690V 135A 190A 285A<br />
Maximum fuse size (gL) 35A 63A 80A<br />
Terminal cross section<br />
Single / multiple wire min. 1.0 mm 2 4.0 mm 2 6.0 mm 2<br />
max. 6.0 mm 2 16.0 mm 2 35.0 mm 2<br />
Fine-strand wire with sleeve min. 0.75 mm 2 2.5 mm 2 6.0 mm 2<br />
max. 4.0 mm 2 10.0 mm 2 25.0 mm 2<br />
Characteristics auxiliary contacts<br />
Special plugs and sockets,<br />
accessories<br />
Part numbers 52242 MEG 52244 MEG 52246 MEG<br />
Auxiliary module 500V 690V 690V<br />
Rated operational voltage U e<br />
Rated continuous current l u<br />
16A 16A 16A<br />
Rated operational current l e<br />
220-240V<br />
AC-15A IEC / EN 380-440V 2.5A/1.5A 6A/3A 6A/4A<br />
Terminal cross section<br />
Single / multiple wire min. 1.0 mm 2 1.0 mm 2 1.0 mm 2<br />
Fine-strand wire with sleeve max. 1.5 mm 2 2.5 mm 2 2.5 mm 2<br />
84