<strong>ANSI</strong>/<strong>TIA</strong>-<strong>568</strong>-C.1<br />

Telecommunications Room (TR)<br />

The Telecommunications Room (TR) is an enclosed space for management and<br />

termination of backbone and horizontal cross connections. The TR typically<br />

provides the horizontal cabling to all of the work areas on a single floor of a<br />

building. The TR is centrally located, and isolated from EMI (electromagnetic<br />

interference), with proper grounding and lighting. The TR may also contain other<br />

active equipment, power, or security devices. Backbone cabling feeds each TR in<br />

a building from the main cross-connect (MC) in the Equipment Room (ER).<br />

Basic requirements:<br />

• Minimum (1) TR per floor<br />

• No carpet or suspended ceilings<br />

• Minimum (2) walls covered with ¾" A/C plywood<br />

• Dedicated, unswitched electrical power<br />

• (1) TR serves up to 10,000 square feet of floor space<br />

• Temperature and humidity control<br />

T e c h n i c a l I n f o r m a t i o n<br />

Equipment Room (ER)<br />

The Equipment Room (ER) is a centralized space for housing the core electronic<br />

equipment, such as computer servers, routers, switches, etc. The backbone<br />

cabling originates from the ER, which serves the entire building or campus. The<br />

ER may function as a TR, and also may contain an entrance facility. Stringent<br />

electrical and environmental requirements apply to the design of an ER to provide<br />

a suitable operating environment for active network equipment. ERs should be<br />

supplied with non-switched, conditioned power with back-up. ERs should not be<br />

located near mechanical rooms, electrical distribution panels, or wet/dirty areas.<br />

Basic requirements:<br />

• Minimum (1) ER per building<br />

• No carpet, suspended ceiling permitted<br />

• Dedicated, unswitched electrical power; back-up and surge protection<br />

• (1) ER serves up to 20,000 square feet of floor space<br />

• Temperature and humidity control<br />

• Double doors for entrance<br />

Entrance Facility (EF)<br />

The Entrance Facility (EF) is located where the access provider and interbuilding<br />

network cables enter the building. Outside plant cables, typically from<br />

underground, are terminated inside the entrance facility. This location is known<br />

as the demarcation point – the transition from access provider to customerowned<br />

cable. A combination of electrical, fire, building, municipal, and FCC<br />

codes apply to the EF. The EF may share other functions, including fire and<br />

security alarms, CCTV, CATV, PBX, etc.<br />

Basic requirements:<br />

• Dry environment<br />

• Proper back-boarding for equipment<br />

• Secure location<br />

• Access to building electrical service ground<br />

• Circuit protection<br />