Standard UTP <strong>Wiring</strong> Conventions<br />

Horizontal UTP Cable and Patch Cords<br />

• Solid copper 4-pair 24 AWG UTP is specified for distribution cabling. Stranded UTP<br />

is specified for patch cords for flexibility. Shielded cable is not commonly used in the<br />

U.S. Splices bridge taps are not permitted.<br />

• Cable, connectors and patch cords shall be marked with the performance category.<br />

Always match performance categories of cables and components throughout the<br />

infrastructure.<br />

• All cable, cords and connecting hardware shall meet performance requirements<br />

of <strong>ANSI</strong>/<strong>TIA</strong>-<strong>568</strong>-C.2. <strong>Hubbell</strong> assures this compliance with all products and<br />

cable partners.<br />

COLOR CODING:<br />

white-blue/blue<br />

white-orange/orange<br />

white-green/green<br />

white-brown/brown<br />

Backbone UTP Cable<br />

• Solid copper 4-pair and 25-pair UTP is specified. An overall shield is optional.<br />

• Performance category markings and compliance to <strong>ANSI</strong>/<strong>TIA</strong>-<strong>568</strong>-C.1 and <strong>568</strong>-C.2 is required.<br />

• Circuits with incompatible signals should be partitioned in separate binder groups. Prior to making shared sheath circuit<br />

assignments, consult the equipment manufacturer for signal characteristics (i.e., frequency, amplitude, voltage, etc.).<br />

• Tip conductor insulation colors are matched to the binder group. Ring conductor insulation colors correspond the pair.<br />

T e c h n i c a l I n f o r m a t i o n<br />

Recognized Connector and <strong>Wiring</strong> Configurations<br />

• 8-position modular jack/plug<br />

• 8-position modular panel/plug<br />

• T<strong>568</strong>A wiring or T<strong>568</strong>B wiring options<br />

• Cat 5e, Cat 6 or Cat 6A recommended<br />

RJ-45 <strong>ANSI</strong>/<strong>TIA</strong>-<strong>568</strong> <strong>Wiring</strong> Conventions<br />

Two wiring standards were adopted. Both configurations are based on maximum transmission performance.<br />

T<strong>568</strong>A<br />

1: Green/White<br />

2: Green<br />

3: Orange/White<br />

4: Blue<br />

5: Blue/White<br />

6: Orange<br />

7: Brown/White<br />

8: Brown<br />

• Preferred method<br />

• Directly compatible with<br />

2-pair voice and token<br />

ring systems utilizing<br />

6-position connectors<br />

T<strong>568</strong>B<br />

1: Orange/White<br />

2: Orange<br />

3: Green/White<br />

4: Blue<br />

5: Blue/White<br />

6: Green<br />

7: Brown/White<br />

8: Brown<br />

• Optional method<br />

• AT&T ® standard<br />

• Directly compatible with<br />

AT&T phone systems<br />

AT&T ® is a registered trademark of AT&T Inc.<br />