Standard Signal<br />
Measuring Contact<br />
<strong>AD</strong>-<strong>MK</strong> <strong>330</strong> <strong>GS</strong><br />
Description<br />
The measuring contact <strong>AD</strong>-<strong>MK</strong> <strong>330</strong> <strong>GS</strong> compares the measuring<br />
value applied at the input with the measuring value set at the pushbutton<br />
encoder switch. If the measuring signal exceeds or falls<br />
below the set value, the appropriate output relay reacts to pre-set<br />
function.<br />
As analogue input value all three standard signals (0-20mA, 4-<br />
20mA, 0-10V) are possible without additional commutation. The<br />
critical values are to be set at 0-99% at the front via encoder switch.<br />
The output function 2 max, 2 min or 1 max/min as well as the rest or<br />
working principle of the output relay is also adjustable at the front.<br />
Input, output and the supply voltage are galvanically separated<br />
from each other.<br />
A highly efficient, integrated electronic power pack enables operation<br />
with 20-253 V AC/DC. There is no possibility of cross polarity of<br />
the connection voltage. A high packing density is achieved due to its<br />
narrow build.<br />
Application<br />
Monitoring and signalling of critical values of analogue measuring<br />
signals, as for instance flow, level, temperature, dry operating protection.<br />
Specification<br />
Construction type:<br />
Power supply:<br />
1-channel switchboard housing<br />
ALLPOWER 20-253V AC/DC<br />
power consumption: ca. 2,3VA resp. 1,5W<br />
Input: selectable 0-20mA, 4-20mA, 0-10V<br />
Input-resistance:<br />
Output:<br />
Breaking voltage:<br />
r.m.s. current:<br />
Breaking capacity:<br />
Selectable function:<br />
Precision:<br />
with 0/4-20mA: 50 Ohm<br />
with 0-10V: 400kOhm<br />
2 relays (changer), selectable in<br />
rest- or working principle<br />
max. 250V, 50Hz<br />
max 2A<br />
max. 100VA<br />
2 max, 2 min, 1 max/min<br />
1% resp. 1 digit<br />
EMC-certification: CE-conform IEC 801-5 SURGE class 3<br />
IEC 801-4 BURST class 3<br />
Radio shielding<br />
Protective systems:<br />
Ambient temperature:<br />
EN 55011, limit-graph B<br />
input/power supply: against over<br />
voltage, confusing the poles, over<br />
current, over temperature<br />
0° - 50° C<br />
Connections and dimensions: <strong>AD</strong>-<strong>MK</strong> <strong>330</strong> <strong>GS</strong><br />
4<br />
5<br />
6<br />
Switches on the<br />
front side:<br />
1 2 3<br />
Relay B<br />
attract relay A<br />
drop out relay A<br />
Relay A<br />
attract relay B<br />
drop out relay B<br />
7 8<br />
9<br />
2 x contact (A+B)<br />
1 x Hysteresis<br />
10 11 12<br />
7 8 9<br />
ground ( - )<br />
0-10 V (+)<br />
0-20 mA (+)<br />
4-20 mA (+)<br />
manner of fastening:<br />
attachment rail NS 35 / 7,5<br />
protection: IP 20<br />
weight: ca. 200 g<br />
103<br />
10<br />
11<br />
12<br />
Power supply<br />
20-253 VDC resp.<br />
30-253 VAC (50-60Hz)<br />
connection data:<br />
finewire: 2,5 mm²<br />
singlewire 4,0 mm²<br />
max. voltage 250 V AC<br />
23<br />
78<br />
39<br />
Printed 01/2009. We reserve the right for technical changes<br />
<strong>AD</strong>AMCZEWSKI<br />
Elektronische <strong>Messtechnik</strong> <strong>GmbH</strong><br />
Felix-Wankel-Str. 13<br />
Tel. +49 (0)7046-875<br />
vertrieb@ad-messtechnik.de<br />
74374 Zaberfeld<br />
Fax +49 (0)7046-7678<br />
www.adamczewski.com
Supply Measuring Contact<br />
<strong>AD</strong>-S<strong>MK</strong> <strong>330</strong> <strong>GS</strong><br />
Description<br />
The supply-measuring-contact <strong>AD</strong>-S<strong>MK</strong> <strong>330</strong> <strong>GS</strong> supplies a 2 or 3<br />
wire transmitter with a DC voltage of 24 V DC, registers and compares<br />
the measuring value of 4-20 mA at the input with the values<br />
set at the touch code switches. If the measuring signal is higher or<br />
lower than the set value, the appertaining output relay reacts to<br />
pres-set function.<br />
The limiting values are set at the front via touch code switches 0 -<br />
99%. The output functions 2 max., 2 min. or 1 max/min as well as<br />
the rest or working principle of the output relay can also be set at the<br />
front side. Input feed voltage, outputs and the supply voltage are<br />
separated from each other galvanically.<br />
Application<br />
Potential free supply of a 2 or 3 wire transmitter with monitor and<br />
signalling of limiting values of analogue measuring signals such as<br />
flow-through, height levels, temperatures, dry run protection,<br />
amongst others.<br />
Specification<br />
Construction type:<br />
Power supply:<br />
Power consumption:<br />
Input:<br />
Transmitter supply:<br />
Input-resistance:<br />
Output:<br />
Breaking voltage:<br />
Switching current:<br />
Breaking capacity:<br />
Selectable function:<br />
Precision:<br />
EMC-verification<br />
Noise suppression<br />
Protective systems:<br />
1-channel switchboard housing<br />
ca. 2,3VA resp.1,8 W<br />
4-20mA from 2- or 3-wire transmitter<br />
24V DC internal limited to 30 mA<br />
50 Ohm with 4-20 mA<br />
2 relays (change over contact),<br />
selectable in rest- or working principle<br />
max. 250V, 50Hz<br />
max 2A<br />
max. 100VA<br />
ambient temperature: 0- 50°C<br />
ALLPOWER 20-253 V AC/DC<br />
internal galvanical separate<br />
2 max, 2 min, 1 max/min<br />
1% resp. 1 digit<br />
CE conform<br />
IEC 801-5 SURGE, class 3<br />
IEC 801-4 BURST, class 3<br />
EN 55011, marginal testing graph "B"<br />
input/power supply: against overvoltage,<br />
confusing the poles, overcurrent<br />
and over-temperature<br />
4 5 6<br />
1 2 3<br />
7 8 9<br />
10 11 12<br />
relay B<br />
relay A<br />
( ) ground<br />
(only 3-wire)<br />
( ) input 0-10 V<br />
( )<br />
transmitter supply<br />
24 V DC<br />
( ) input<br />
4-20 mA<br />
( ~= ) power-supply<br />
Connections and dimensions: <strong>AD</strong>-S<strong>MK</strong> <strong>330</strong> <strong>GS</strong> weight: ca. 200 g<br />
protection: IP 20<br />
manner of fastening:<br />
DIN rail: NS35/7,5<br />
7 8 9<br />
10 11 12<br />
23<br />
103<br />
78<br />
39<br />
pull-in<br />
relay A<br />
pull-in<br />
relay B<br />
2x<br />
contact (A/B)<br />
connection data:<br />
fine-wire: 2,5 mm²<br />
single-wire: 4,0 mm²<br />
max. voltage: 250 V~<br />
switches on the front-side<br />
release<br />
relay A<br />
release<br />
relay B<br />
1x<br />
hysteresis<br />
connecting 2-wire-transmitter<br />
24 V DC<br />
( )<br />
( )<br />
9<br />
10<br />
connecting 3-wire-transmitter (current)<br />
24 V DC<br />
input<br />
ground<br />
( )<br />
( )<br />
( )<br />
9<br />
10<br />
7<br />
connecting 3-wire-transmitter (voltage)<br />
24 V DC<br />
input<br />
ground<br />
( )<br />
( )<br />
( )<br />
9<br />
8<br />
7<br />
Printed 01/2009. We reserve the right for technical changes<br />
<strong>AD</strong>AMCZEWSKI<br />
Elektronische <strong>Messtechnik</strong> <strong>GmbH</strong><br />
Felix-Wankel-Str. 13<br />
Tel. +49 (0)7046-875<br />
vertrieb@ad-messtechnik.de<br />
74374 Zaberfeld<br />
Fax +49 (0)7046-7678<br />
www.adamczewski.com