EDS30…<br />
Portable Ground Fault Location System<br />
for Ungrounded AC and DC Systems<br />
Product description<br />
The EDS30… is a portable ground fault location system for ungrounded AC and DC systems.<br />
The system locates ground faults down to the load level in both energized and deenergized<br />
circuits. The EDS... may also be used for branch ground fault current measurements<br />
in grounded systems. All essential components are housed in a robust aluminum<br />
casing.<br />
EDS30…<br />
System features<br />
• Portable ground fault location system for<br />
ungrounded systems: AC 42…460 Hz<br />
0…790 V / DC 0…960 V<br />
• Works while system is online or offline<br />
• Branch ground fault current measurement<br />
in grounded systems<br />
• Use in main and control circuits<br />
• Comes standard with 0.8" and 2" clamps<br />
(4.5" clamp also available)<br />
• Robust aluminium case with handle<br />
• Test devices PGH18… with variable<br />
test current 1…25 mA<br />
Ground fauilt evaluator EDS190P<br />
• Backlit LCD display, 3 x 16 characters<br />
• Supplied by an accumulator (delivered<br />
with a power supply unit)<br />
• Response value for ground fault location<br />
test current: 2…10 mA for main circuits<br />
• Response value for ground fault location<br />
test current: 0.2…1 mA for control circuits<br />
• Additionally can measure for ground fault<br />
current, with response value 10 mA…10 A<br />
Application<br />
Standalone portable fault location system (no other devices required):<br />
• <strong>EDS3090</strong>PG<br />
For main circuits: AC 20…575 V (42…460 Hz), DC 20…504 V<br />
With voltage coupler AGE185: AC 500…790 V, DC 400…960 V<br />
• EDS3091PG<br />
For control circuits: AC 20…265 V (42…460 Hz), DC 20…308 V<br />
Portable fault location system used in conjunction with installed units:<br />
(Requires IRDH575 ground fault monitor to be installed - see datasheet for more)<br />
• <strong>EDS3090</strong><br />
For main circuits<br />
• EDS3091<br />
For control circuits<br />
Function<br />
Ground fault signal generator PGH18…<br />
For online systems: The PGH18… generates a defined test current signal. The test current<br />
generated in this manner depends on the value of the present insulation fault and the system<br />
voltage.<br />
• Depending on the switch position of the PGH185 or PGH186, the test current is limited<br />
to a maximum of 25 mA or 10 mA.<br />
• The PGH183 limits the test current to a maximum of 2.5 mA or 1 mA depending on the<br />
switch position.<br />
For offline systems or systems < 50 V, the PGH186 drives a test current generated by an<br />
integrated voltage source (DC 50 V). For systems > 50 V, the system voltage itself drives<br />
the test current.<br />
Ground fault evaluator EDS190P<br />
The ground fault evaluator EDS190P provides the following measuring functions:<br />
• Ground fault location. The EDS190P locates ground faults down to the load level by locating<br />
<br />
the test current signal generated by the PGH18… device.<br />
• Ground fault current measurements in grounded AC circuits.<br />
The response range for ground fault current is 10 mA…10 A.<br />
Displays<br />
The full-featured LCD display includes many different indications, including the detection of<br />
the ground fault test pulse (in ungrounded systems), the measured ground fault current (in<br />
grounded systems), the accumulator capacity, alarm memory indication, and the set nominal<br />
frequency. A buzzer also activates when the alarm occurs.