1<br />

<strong>EDS3090</strong> <strong>Series</strong><br />

Portable Ground Fault Location System<br />

Ungrounded (Floating) AC/DC Systems<br />

Technical Bulletin<br />

NAE1012030 / 04.2011


EDS30…<br />

Portable Ground Fault Location System<br />

for Ungrounded AC and DC Systems<br />

Product description<br />

The EDS30… is a portable ground fault location system for ungrounded AC and DC systems.<br />

The system locates ground faults down to the load level in both energized and deenergized<br />

circuits. The EDS... may also be used for branch ground fault current measurements<br />

in grounded systems. All essential components are housed in a robust aluminum<br />

casing.<br />

EDS30…<br />

System features<br />

• Portable ground fault location system for<br />

ungrounded systems: AC 42…460 Hz<br />

0…790 V / DC 0…960 V<br />

• Works while system is online or offline<br />

• Branch ground fault current measurement<br />

in grounded systems<br />

• Use in main and control circuits<br />

• Comes standard with 0.8" and 2" clamps<br />

(4.5" clamp also available)<br />

• Robust aluminium case with handle<br />

• Test devices PGH18… with variable<br />

test current 1…25 mA<br />

Ground fauilt evaluator EDS190P<br />

• Backlit LCD display, 3 x 16 characters<br />

• Supplied by an accumulator (delivered<br />

with a power supply unit)<br />

• Response value for ground fault location<br />

test current: 2…10 mA for main circuits<br />

• Response value for ground fault location<br />

test current: 0.2…1 mA for control circuits<br />

• Additionally can measure for ground fault<br />

current, with response value 10 mA…10 A<br />

Application<br />

Standalone portable fault location system (no other devices required):<br />

• <strong>EDS3090</strong>PG<br />

For main circuits: AC 20…575 V (42…460 Hz), DC 20…504 V<br />

With voltage coupler AGE185: AC 500…790 V, DC 400…960 V<br />

• EDS3091PG<br />

For control circuits: AC 20…265 V (42…460 Hz), DC 20…308 V<br />

Portable fault location system used in conjunction with installed units:<br />

(Requires IRDH575 ground fault monitor to be installed - see datasheet for more)<br />

• <strong>EDS3090</strong><br />

For main circuits<br />

• EDS3091<br />

For control circuits<br />

Function<br />

Ground fault signal generator PGH18…<br />

For online systems: The PGH18… generates a defined test current signal. The test current<br />

generated in this manner depends on the value of the present insulation fault and the system<br />

voltage.<br />

• Depending on the switch position of the PGH185 or PGH186, the test current is limited<br />

to a maximum of 25 mA or 10 mA.<br />

• The PGH183 limits the test current to a maximum of 2.5 mA or 1 mA depending on the<br />

switch position.<br />

For offline systems or systems < 50 V, the PGH186 drives a test current generated by an<br />

integrated voltage source (DC 50 V). For systems > 50 V, the system voltage itself drives<br />

the test current.<br />

Ground fault evaluator EDS190P<br />

The ground fault evaluator EDS190P provides the following measuring functions:<br />

• Ground fault location. The EDS190P locates ground faults down to the load level by locating<br />

<br />

the test current signal generated by the PGH18… device.<br />

• Ground fault current measurements in grounded AC circuits.<br />

The response range for ground fault current is 10 mA…10 A.<br />

Displays<br />

The full-featured LCD display includes many different indications, including the detection of<br />

the ground fault test pulse (in ungrounded systems), the measured ground fault current (in<br />

grounded systems), the accumulator capacity, alarm memory indication, and the set nominal<br />

frequency. A buzzer also activates when the alarm occurs.


PGH18x<br />

Application example:<br />

Using the portable fault location system (<strong>EDS3090</strong>/3091PG) in a three-phase ungrounded system in a completely portable<br />

application (no installed units)<br />

Application example: Using the portable fault location system (<strong>EDS3090</strong>/3091) in an ungrounded system with a complete installed fault<br />

location system (IRDH575 and EDS460/490)


Portable AC/DC Ground Fault Location System EDS30...<br />

Application example: Using the portable fault location system (EDS3096PG) in an offline ungrounded system<br />

Application example: Using the EDS309… system for ground fault current measurements in a grounded three-phase system


Operating Elements: PGH18… Test Generator<br />

1 - ON/OFF switch to activate the test current<br />

2 - Selector switch for maximum test current 25/10 mA or 2.5 / 1 mA<br />

3 - Not visible: Magnetic adhesive strip at the back of the enclosure<br />

for affixing to metal parts (e.g. switchboard cabinet)<br />

4 - 3 sockets for system coupling<br />

5 - Socket for ground connection<br />

6 - LED indicators:<br />

Power ON LED<br />

Indication of the positive test cycle of the test current<br />

Indication of the negative test cycle of the test current<br />

7 - Microfuse, 100 mA<br />

8 - Panel plug for supply voltage<br />

8<br />

7<br />

6<br />

1<br />

2<br />

3<br />

5<br />

4<br />

Display and operating elements: EDS190P Evaluator<br />

1 - Connection for external power supply charger (DC 6 V)<br />

2 - BNC connection for measuring clamp<br />

3 - LCD display, backlit<br />

3 lines x 16 characters<br />

4 - Alarm LED<br />

5 - Button for selecting operating mode<br />

I ΔS<br />

= Ground fault location (ungrounded system)<br />

I Δn<br />

= Ground fault current measurement (grounded system)<br />

6 - Button for selecting the type of clamp being used<br />

for I Tmax<br />

= 50 mA : for I Tmax<br />

= 5 mA:<br />

P20 = PSA3020 = PSA3320<br />

P52 = PSA3052 = PSA3352<br />

P165 = PSA3165 ---------------<br />

W/WR = W… / WR… = W…-8000<br />

WS = WS… = W…-8000<br />

7 - INFO key: Displays relevant device/system information<br />

- Device type<br />

- Software version<br />

– Current response values I ΔS<br />

and I Δn<br />

– Setup status<br />

ESC key:<br />

Exits the menu without changing parameters<br />

10<br />

11<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

12<br />

9


Portable AC/DC Ground Fault Location System EDS30...<br />

Technical Data: EDS309…system<br />

The technical data listed in this chapter apply to the components:<br />

PGH18…, EDS190P, AGH185.<br />

Environment / EMC<br />

EMC IEC 61326<br />

Operating temperature - 10 °C…+ 55 °C<br />

Classification of climatic conditions acc. to IEC 60721:<br />

Stationary use (IEC 60721-3-3) <br />

3K5 (except condensation and formation of ice)<br />

Transport (IEC 60721-3-2) <br />

2K3 (except condensation and formation of ice)<br />

Storage (IEC 60721-3-1) <br />

1K4 (except condensation and formation of ice)<br />

Classification of mechanical conditions acc. to IEC 60721<br />

Stationary use (IEC 60721-3-3)<br />

3M4<br />

Transport (IEC 60721-3-2) 2M2<br />

Long-time storage (IEC 60721-3-1) 1M3<br />

General data<br />

Operating mode continuous operation<br />

Position of normal use<br />

any<br />

Weight approx. 7000 g (8500 g including PSA3165)<br />

Technical Data: PGH18...<br />

Insulation coordination acc. to IEC 60664-1 / IEC 60664-3<br />

Rated insulation voltage<br />

AC 500 V<br />

Rated impulse voltage/pollution degree 4 kV/3<br />

Nominal system voltage U n<br />

PGH185<br />

3AC/AC 42…460 Hz 20…575 V, DC 20…504 V<br />

PGH183 AC 42…460 Hz 20…265 V, DC 20…308 V<br />

PGH186<br />

3AC/AC 42…460 Hz 0…575 V, DC 0…504 V<br />

Supply voltage<br />

Supply voltage U S<br />

<br />

AC 50…60 Hz 230 V<br />

Operating range of U S<br />

<br />

0.85…1.15 x U S<br />

Supply voltage U S<br />

version -13<br />

AC 50…60 Hz 90…132 V<br />

Power consumption ≤ 3 VA<br />

Test current<br />

PGH185/186<br />

Max. test current, selectable<br />

PGH183<br />

Max. test current, selectable<br />

PGH183/185/186<br />

Test cycle<br />

Idle time <br />

Test voltage<br />

PGH186<br />

General data<br />

Degree of protection, internal components DIN EN 60529 (VDE 0470-1)<br />

Enclosure material<br />

Flammability class<br />

Weight<br />

10 / 25 mA<br />

1 / 2.5 mA<br />

2 s<br />

4 s<br />

DC 50 V<br />

IP40<br />

ABS plastic<br />

UL94V-0<br />

< 700 g<br />

Technical Data: EDS190P<br />

Insulation coordination acc. to IEC 60664-1 / IEC 60664-3<br />

Rated insulation voltage<br />

Rated impulse voltage/pollution degree<br />

50 V<br />

0.8 kV / III<br />

Supply voltage<br />

Supply voltage U S<br />

<br />

DC 6 V +/- 10 %, external power supply unit<br />

Batteries<br />

3 x LR6 AA – 1.5 V<br />

Accumulators 3 x NiMh ≥ 2000 mAh<br />

Size AA R6<br />

Power consumption<br />

≤ 0.5 W<br />

Hours of operation (without display illumination) ≥ 60 h<br />

Measuring circuit insulation fault location<br />

Nominal system voltage when the conductors are uninsulated,<br />

<br />

including measuring clamp up to 600 V<br />

Rated frequency DC, 42…2000 Hz<br />

Main circuit (I Tmax<br />

= 50 mA):<br />

Measuring clamps<br />

PSA3020, PSA3052, PSA3165<br />

Response value I Δs<br />

adjustable<br />

2…10 mA (5 mA)*<br />

Max. percentage operating uncertainty ± 30 % / ± 2 mA of the reference value<br />

Control circuit: (I Tmax<br />

= 5 mA)<br />

Measuring clamps<br />

PSA3320, PSA3352<br />

Response value I Δs<br />

adjustable 200… 1 000 μA (500 μA)*<br />

Percentage operating uncertainty ± 30 % / ± 0.1 mA of the reference value<br />

Measuring circuit residual current<br />

with measuring clamps<br />

PSA3020, PSA3052, PSA3165<br />

Measuring range 5 mA … 10 A (crest factor up to 3)<br />

Response value I Δn<br />

adjustable<br />

10 mA…10 A (100 mA)*<br />

Measuring clamps<br />

PSA3320, PSA3352<br />

Measuring range 2 mA … 2 A (crest factor up to 3)<br />

Response value I Δn<br />

adjustable 5 mA … 1 A (100 mA)*<br />

Frequency range <br />

42…2000 Hz<br />

Relative percentage uncertainty of the response value<br />

0…-35%<br />

Display accuracy ± 17,5 %<br />

Hysteresis 20 %<br />

Harmonics, adjustable<br />

2.-9. harmonic component<br />

Inputs<br />

Type of connection measuring clamp<br />

Power supply unit<br />

BNC plug<br />

DC 6 V<br />

Displays<br />

LCD 3 x 16 characters, selectable illumination<br />

LED Alarm<br />

General data<br />

Degree of protection, internal components DIN EN 60529 (VDE 0470-1)<br />

IP40<br />

Protection class acc. to IEC 60947-1, DIN EN 60947-1 (VDE 0660-100)<br />

Class III<br />

Enclosure material<br />

ABS plastic<br />

Flammability class<br />

UL94V-0<br />

Operating manual<br />

TGH1420<br />

Weight<br />

< 400 g<br />

Software version D316 V1.0<br />

Dimensions W x H x D 84 x 197 x 30 mm<br />

( )* = Factory settings


Technical Data: Measuring Clamps<br />

Electrical safety<br />

Standard IEC 61010-2-030:2004-05-01<br />

Pollution degree 2<br />

Category<br />

III<br />

Operating voltage<br />

600 V<br />

Nominal insulation voltage<br />

AC 600 V CAT III bzw. AC 300 V CAT IV<br />

General data<br />

Degree of protection, internal components IEC 60529 IP40<br />

Protection class acc. to IEC 60947-1 Class III<br />

Test port <br />

BNC plug<br />

Dimensions PSA3052 / 3352 216 x 111 x 45 mm<br />

Dimensions PSA3020 / 3320<br />

135 x 65 x 30 mm<br />

Dimensions PSA3165 <br />

285 x 179 x 45 mm<br />

permissible cable diameter PSA3052 / 3352 52 mm<br />

permissible cable diameter PSA3052 / 3320 20 mm<br />

permissible cable diameter PSA3165 <br />

115 mm<br />

Weigth PSA3052 / 3352 approx. 700 g<br />

Weight PSA3020 / 3320 approx. 300 g<br />

Weight PSA3165 <br />

approx. 1300 g<br />

Technical Data: AGE185 coupler<br />

Insulation coordination acc. to IEC 60664-1<br />

Rated insulation voltage<br />

AC 1000 V<br />

Rated impulse voltage/pollution degree<br />

4 kV / III<br />

Nominal system voltage U n<br />

<br />

3AC/AC 42…460 Hz, 500…790 V, DC 400…960 V<br />

General data<br />

Degree of protection, internal components IEC 60529 IP30<br />

Type of connection/cable: Safety plug with green-yellow connecting wire 1 mm²<br />

Weight<br />

< 200 g<br />

Dimensions W x H x D 88,5 x 42 x 21 mm<br />

Ordering information<br />

Type Included in delivery Supply voltage Nominal voltage Art. No.<br />

Ground fault<br />

Measuring clamps Measuring clamps<br />

Tracer generator<br />

evaluator<br />

20 mm<br />

52 mm<br />

<strong>EDS3090</strong> EDS190P PSA3020 PSA3052 AC 42…460 Hz, 20…575 V und DC 20…504 V B91082026<br />

<strong>EDS3090</strong>PG EDS190P PGH185 PSA3020 PSA3052 AC 50…60 Hz, 230 V AC 42…460 Hz, 20…575 V und DC 20…504 V B91082021<br />

<strong>EDS3090</strong>PG-13 EDS190P PGH185-13 PSA3020 PSA3052 AC 50…60 Hz, 90…132 V AC 42…460 Hz, 20…575 V und DC 20…504 V B91082022<br />

EDS3096PG EDS190P PGH186 PSA3020 PSA3052 AC 50…60 Hz, 230 V AC 42…460 Hz, 0…575 V und DC 0…504 V B91082025<br />

EDS3096PG-13 EDS190P PGH186-13 PSA3020 PSA3052 AC 50…60 Hz, 90…132 V AC 42…460 Hz, 0…575 V und DC 0…504 V B91082029<br />

EDS3091 EDS190P PSA3320 PSA3352 AC 42…460 Hz, 20…265 V und DC 20…308 V B91082027<br />

EDS3091PG EDS190P PGH183 PSA3320 PSA3352 AC 50…60 Hz, 230 V AC 42…460 Hz, 20…265 V und DC 20…308 V B91082023<br />

EDS3091PG-13 EDS190P PGH183-13 PSA3320 PSA3352 AC 50…60 Hz, 90…132 V AC 42…460 Hz, 20…265 V und DC 20…308 V B91082024<br />

Optional accessories<br />

PSA3165 Measuring clamp 115 mm for <strong>EDS3090</strong>… and EDS3096… B980852<br />

AGE185 Coupling device to extend the voltage range of the PGH185/186 AC 42…460 Hz 500…790 V, DC 400…960 V B980305<br />

EDS165-SET Accessories for fault location in diode-decoupled systems B91082007


Portable AC/DC Ground Fault Location System EDS30...<br />

Build a complete ground fault location system<br />

Step 1: Choose an installed ground fault monitor<br />

IRDH575 Ground fault monitor<br />

I R D H 5 7 5 B 1 - 4 3 5<br />

1<br />

2<br />

Part Number 1: Nominal (line) voltage 2: Supply (control) voltage System type<br />

IRDH575B1-435 3AC / AC 20…575 V - DC 20…504 V AC 88…264 V - DC 77…286 V Main circuits<br />

IRDH575B1-427 3AC / AC 20…575 V - DC 20…504 V DC 19.2…72 V Main circuits<br />

IRDH575B1-4227 3AC / AC 20…150 V - DC 20…150 V DC 19.2…72 V Small systems<br />

IRDH575B1-4235 3AC / AC 20…150 V - DC 20…150 V AC 88…264 V - DC 77…286 V Small systems<br />

IRDH575B2-435 3AC / AC 340…760 V - DC 340…575 V AC 88…264 V - DC 77…286 V Small systems<br />

Step 2: Choose an installed ground fault location device<br />

EDS4... Ground Fault Location Device<br />

E D S 4 6 0 D - 2<br />

1<br />

2<br />

Part Number 1: Number of output contacts 2: Supply (control) voltage System type<br />

EDS460-D-1 One common DPDT contact AC 16…72 V - DC 16…94 V Main circuits<br />

EDS460-D-2 One common DPDT contact AC / DC 70…276 V Main circuits<br />

EDS490-D-1 One common DPDT / 12 SPST contacts AC 16…72 V - DC 16…94 V Main circuits<br />

EDS490-D-2 One common DPDT / 12 SPST contacts AC / DC 70…276 V Main circuits<br />

EDS461-D-1 One common DPDT contact AC 16…72 V - DC 16…94 V Small systems<br />

EDS461-D-2 One common DPDT contact AC / DC 70…276 V Small systems<br />

Step 3: Choose a portable ground fault location system<br />

EDS309... Portable Ground Fault Location System<br />

E D S 3 0 9 0<br />

Part Number Included evaluator Included clamps 1: System type<br />

<strong>EDS3090</strong> EDS190P PSA3020 (20 mm), PSA3052 (52 mm) Main circuits<br />

EDS3091 EDS190P PSA3320 (20 mm), PSA3352 (52 mm) Small systems<br />

1


Selection guide: Portable-only fault location system<br />

Application Main circuits Small systems<br />

Online circuits Offline circuits Online circuits<br />

Function<br />

Insulation fault test device PGH<br />

Nominal system voltage U n<br />

<br />

3AC / AC 20…575 V<br />

DC 20…504 V<br />

3AC / AC 0…575 V<br />

DC 0…504 V<br />

AC 20…265 V DC 20…308 V<br />

U S<br />

AC 230 V PGH185 PGH186 PGH183<br />

U S<br />

AC 90…132 V PGH185-13 PGH186-13 PGH183-13<br />

Test current 10 / 25 mA 10 / 25 mA 1 / 2.5 mA<br />

Type<br />

Hand-held ground fault evaluator<br />

EDS190P<br />

LC display<br />

Test current max.<br />

Response value<br />

3 x 16 characters<br />

1 … 50 mA<br />

0.2 … 1 / 2…10 mA selectable<br />

Measuring clamps<br />

Type PSA3020 PSA3052 PSA3165 (optional) PSA3320 PSA3352<br />

20 mm × ×<br />

52 mm × ×<br />

115 mm ×<br />

Complete system<br />

Type <strong>EDS3090</strong>PG (-13) EDS3096PG (-13) EDS3091PG (-13)<br />

Comprising <br />

<strong>EDS3090</strong>PG for U S<br />

=<br />

AC50…60 Hz 230 V<br />

<strong>EDS3090</strong>-13 for U S<br />

=<br />

AC 50…60 Hz 90…132 V<br />

Aluminium case, PGH185,<br />

EDS190, PSA3020, PSA3052,<br />

power supply unit, cable set<br />

EDS3096PG for U S<br />

=<br />

AC 50…60 Hz 230 V<br />

EDS3096PG-13 for U S<br />

=<br />

AC 50…60 Hz 90…132 V<br />

Aluminium case, PGH186,<br />

EDS190, PSA3020, PSA3052,<br />

power supply unit, cable set<br />

EDS3091PG for U S<br />

=AC 50…60 Hz 230 V<br />

EDS3091PG-13 for U S<br />

=AC 50…60 Hz 90…132V<br />

Aluminium case, PGH183, EDS190, PSA3320,<br />

PSA3352, power supply unit, cable set<br />

Type<br />

Accessories<br />

AGE185<br />

Extension<br />

Nominal voltage range<br />

AC45…400 Hz, 500…790 V<br />

DC400…960 V


Dimensions: Aluminum Case<br />

North American Headquarters • Coatesville, PA<br />

Toll-Free: 800.356.4266 • Fax: 610.383.7100<br />

Canada • Brampton, ON<br />

Toll-Free: 800-243-2438 • Fax: 905-799-3051<br />

Document NAE1012030 / 04.2011 / © <strong>Bender</strong> Inc.<br />

www.bender.org • E-mail: info@bender.org

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!