ANSI Z49.1:1999<br />

10.8.1.9 Damaged Cyl<strong>in</strong>ders. Cyl<strong>in</strong>ders evidenc<strong>in</strong>g<br />

severe damage, corrosion, or fire exposure shall not<br />

be used.<br />

10.8.2 Cyl<strong>in</strong>der Storage<br />

10.8.2.1 Protection. Cyl<strong>in</strong>ders shall be stored where<br />

they will not be exposed to physical damage, tamper<strong>in</strong>g,<br />

or subject to temperatures which would raise the contents<br />

above the limits of 10.8.1.8.<br />

Cyl<strong>in</strong>ders shall be stored away from elevators, stairs,<br />

or gangways <strong>in</strong> assigned places where cyl<strong>in</strong>ders will not<br />

be knocked over or damaged by pass<strong>in</strong>g or fall<strong>in</strong>g objects.<br />

Cyl<strong>in</strong>ders shall be secured <strong>in</strong> storage to prevent<br />

fall<strong>in</strong>g.<br />

10.8.2.2 Cyl<strong>in</strong>ders Separated from Combustibles.<br />

Cyl<strong>in</strong>ders <strong>in</strong> storage shall be separated from flammable<br />

<strong>and</strong> combustible liquids <strong>and</strong> from easily ignited materials<br />

such as wood, paper, packag<strong>in</strong>g materials, oil, <strong>and</strong> grease<br />

by at least 20 feet (6.1 meters), or by a noncombustible<br />

barrier at least 5 feet (1.6 meters) high hav<strong>in</strong>g a fire resistance<br />

of at least one-half hour.<br />

10.8.2.3 Oxygen Separated from Fuel Gas. Oxygen<br />

cyl<strong>in</strong>ders <strong>in</strong> storage shall additionally be separated<br />

from fuel gas cyl<strong>in</strong>ders, or from reserve stocks of calcium<br />

carbide, by a distance or barrier as described <strong>in</strong> 10.8.2.2.<br />

10.8.2.4 Oxygen <strong>in</strong> Acetylene Generator Build<strong>in</strong>gs.<br />

Oxygen cyl<strong>in</strong>ders stored <strong>in</strong> outside acetylene generator<br />

houses shall be separated from the generator or carbide<br />

storage rooms by a noncombustible partition hav<strong>in</strong>g<br />

a fire resistance of at least one hour. This partition shall be<br />

without open<strong>in</strong>gs <strong>and</strong> shall be gas-tight.<br />

Oxygen shall not be stored <strong>in</strong>side acetylene generator<br />

rooms.<br />

10.8.2.5 Fuel Gas Cyl<strong>in</strong>ders Upright. Acetylene<br />

<strong>and</strong> liquefied gas cyl<strong>in</strong>ders shall be used valve end up.<br />

10.8.2.6 Fuel Gas Storage Limits. Fuel gas<br />

storage limits shall be <strong>in</strong> accordance with ANSI/NFPA<br />

51, St<strong>and</strong>ard for the Design <strong>and</strong> Installation of Oxygen-<br />

Fuel Gas Systems for Weld<strong>in</strong>g, Cutt<strong>in</strong>g, <strong>and</strong> <strong>Allied</strong><br />

<strong>Processes</strong>.<br />

10.8.3 Cyl<strong>in</strong>der H<strong>and</strong>l<strong>in</strong>g<br />

10.8.3.1 Rough H<strong>and</strong>l<strong>in</strong>g. Cyl<strong>in</strong>ders shall not be<br />

dropped, struck, or permitted to strike objects violently <strong>in</strong><br />

a manner which may damage the cyl<strong>in</strong>der, valve, or safety<br />

device.<br />

10.8.3.2 Pry Bars. Bars shall not be used under<br />

valves or valve protection caps to pry cyl<strong>in</strong>ders loose when<br />

frozen to the ground or otherwise fixed.<br />

10.8.3.3 Rollers or Supports. Cyl<strong>in</strong>ders shall never<br />

be used as rollers or supports, whether full or empty.<br />

E10.8.2.1 Check for overhead combustibles such as<br />

overhead l<strong>in</strong>es <strong>and</strong> pip<strong>in</strong>g, suspended ceil<strong>in</strong>g materials,<br />

etc., when consider<strong>in</strong>g storage location.<br />

E10.8.2.5 This prevents liquid flow <strong>in</strong>to hoses <strong>and</strong><br />

regulators.<br />

E10.8.3.2 The use of warm (not boil<strong>in</strong>g) water is<br />

recommended.<br />

27

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!