MODEL SLV-6<br />

FORMED STATIONARY LOUVER<br />

SIGHTPROOF<br />

Standard Construction:<br />

6"<br />

(152 mm)<br />

Frame:<br />

Blades:<br />

6” (152 mm) x 20 ga. galvanized steel.<br />

20 ga. galvanized steel,<br />

approximately 5-3/4” (146 mm) on centers.<br />

Blade Angle: 60°<br />

Screen: Bird screen - 1/2” x 1/2” (12.7 mm x 12.7 mm) x 19 ga.<br />

galvanized steel, in a removable frame on interior of <strong>louver</strong>.<br />

Finish: Mill galvanized.<br />

Minimum Size: 8”w x 12”h (203 mm x 304 mm)<br />

Options:<br />

Screens:<br />

Finish:<br />

Sill Extensions:<br />

Flange:<br />

Material:<br />

Notes:<br />

Insect screen - 18 x 16 mesh aluminum.<br />

Other: __________________________<br />

Prime coat<br />

Baked Enamel<br />

Kynar 500 Enamel<br />

Other: __________________________<br />

1-1/2” (38 mm) (front or rear)<br />

Various materials and gauges<br />

Louvers fabricated 1/4” (6.4 mm) under<br />

opening size unless otherwise noted.<br />

5-3/4"<br />

(146 mm)<br />

SLV-6 - 02-07<br />

Channel Frame<br />

Jamb<br />

Visible<br />

Mullion<br />

Blade<br />

Brace<br />

Sill<br />

Extension<br />

1-1/2” (38 mm)<br />

Flange<br />

Frame<br />

Specifications are correct at time of printing. However, as part of our ‘continuous improvement program,’ we reserve the right to make further improvements without notice.<br />

© February, 2007 <strong>NCA</strong> <strong>Manufacturing</strong><br />

Project:<br />

Location:<br />

Architect:<br />

Engineer:<br />

Contractor:<br />

Address:<br />

P.O. Number:<br />

Date:<br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL SLV-6<br />

FORMED STATIONARY LOUVER<br />

SIGHTPROOF<br />

© February, 2007 <strong>NCA</strong> <strong>Manufacturing</strong><br />

Furnish and install where shown <strong>model</strong> SLV-6 Louver, manufactured by <strong>NCA</strong> <strong>Manufacturing</strong>. Louver shall be the<br />

<strong>stationary</strong> <strong>sightproof</strong>, chevron blade type with a frame depth of 6” (152 mm). Frame and blades shall be 20 gauge<br />

galvanized steel. Blades shall be located on a 60 degree blade angle. Screen shall consist of 1/2” (12.7 mm) mesh, 19<br />

gauge galvanized, with an extruded frame, mounted to the <strong>louver</strong>s interior and be removable for cleaning. Louvers shall<br />

be finished with Polyurethane Acrylic Enamel, Kynar 500, or another finish selected by the architect from <strong>NCA</strong> Standard<br />

Color Chart.<br />

SLV-6 FREE AREA IN SQ. FT.<br />

Height - Inches<br />

Width - Inches<br />

8 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96<br />

12 0.11 0.19 0.31 0.42 0.53 0.65 0.76 0.88 0.99 1.11 1.22 1.33 1.45 1.56 1.68 1.79<br />

18 0.21 0.35 0.57 0.78 0.99 1.20 1.41 1.63 1.84 2.05 2.26 2.48 2.69 2.90 3.11 3.32<br />

24 0.31 0.52 0.83 1.14 1.45 1.76 2.07 2.38 2.69 3.00 3.31 3.62 3.93 4.24 4.55 4.86<br />

30 0.41 0.68 1.09 1.49 1.90 2.31 2.72 3.13 3.53 3.94 4.35 4.76 5.16 5.57 5.98 6.39<br />

36 0.58 0.96 1.53 2.11 2.68 3.26 3.83 4.41 4.98 5.56 6.13 6.71 7.28 7.86 8.43 9.01<br />

42 0.68 1.13 1.81 2.49 3.16 3.84 4.52 5.20 5.88 6.55 7.23 7.91 8.59 9.27 9.94 10.62<br />

48 0.68 1.14 1.82 2.51 3.19 3.88 4.56 5.25 5.93 6.61 7.30 7.98 8.67 9.35 10.04 10.72<br />

54 0.79 1.32 2.11 2.90 3.69 4.48 5.27 6.06 6.85 7.64 8.43 9.22 10.01 10.80 11.59 12.38<br />

60 0.90 1.50 2.40 3.29 4.19 5.09 5.99 6.89 7.79 8.69 9.58 10.48 11.38 12.28 13.18 14.08<br />

66 1.01 1.68 2.68 3.69 4.70 5.70 6.71 7.72 8.72 9.73 10.74 11.74 12.75 13.76 14.76 15.77<br />

72 1.11 1.86 2.97 4.09 5.20 6.32 7.43 8.55 9.66 10.78 11.89 13.01 14.12 15.24 16.35 17.47<br />

78 1.22 2.04 3.26 4.48 5.71 6.93 8.15 9.38 10.60 11.82 13.04 14.27 15.49 16.71 17.94 19.16<br />

84 1.33 2.22 3.55 4.88 6.21 7.54 8.87 10.21 11.54 12.87 14.20 15.53 16.86 18.19 19.52 20.85<br />

90 1.44 2.40 3.84 5.28 6.72 8.16 9.60 11.03 12.47 13.91 15.35 16.79 18.23 19.67 21.11 22.55<br />

96 1.55 2.58 4.13 5.67 7.22 8.77 10.32 11.86 13.41 14.96 16.51 18.05 19.60 21.15 22.70 24.24<br />

0.30<br />

0.28<br />

SLV-6 - 02-07<br />

PRESSURE DROP - INCHES OF WATER (In. W.C.)<br />

3.0<br />

2.0<br />

1.0<br />

.9<br />

.8<br />

.7<br />

.6<br />

.5<br />

.4<br />

.3<br />

.2<br />

.09 .1<br />

.08<br />

.07<br />

.06<br />

.05<br />

.04<br />

.03<br />

.02<br />

.01<br />

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 100<br />

VELOCITY THROUGH FREE AREA<br />

FPM X 100<br />

WATER PENETRATION OZ. PER SQ.FT. OF FREE AREA<br />

(15 MINUTE DURATION)<br />

0.26<br />

0.24<br />

0.22<br />

0.20<br />

0.18<br />

0.16<br />

0.14<br />

0.12<br />

0.10<br />

0.08<br />

0.06<br />

0.04<br />

0.02<br />

0.00<br />

600 700 800 900<br />

VELOCITY THROUGH FREE AREA FPM<br />

PRESSURE DROP<br />

INTAKE / EXHAUST<br />

Pressure Drop Data applies to test unit size 48" x 48" only.<br />

Performance Data does not include the effects of birdscreen.<br />

Water Penetration<br />

Water Penetration Data applies to test unit size 48" x 48" only.<br />

Beginning of Water Penetration is 743 FPM Free Area Velocity.<br />

© February, 2007 <strong>NCA</strong> <strong>Manufacturing</strong><br />