MODEL <strong>ACD</strong>-<strong>56</strong><br />
AIRFOIL PARALLEL OR OPPOSED BLADE DAMPER<br />
LOW LEAKAGE: TESTED TO AMCA 500<br />
<strong>ACD</strong>-<strong>56</strong> - 02-05<br />
Standard Construction:<br />
Frame: Extruded aluminum hat section, 5"w x 1"h<br />
Blades:<br />
Bearings:<br />
Axles:<br />
Linkage:<br />
Extended Shaft:<br />
Blade Seals:<br />
Jamb Seals:<br />
Finish:<br />
Jackshaft:<br />
Minimum Damper Size:<br />
Maximum Damper Size:<br />
Options:<br />
Operators:<br />
Finish:<br />
Face & Bypass:<br />
Jackshaft:<br />
Bearings:<br />
(127 mm x 25 mm) heavy gauge 6063-T5.<br />
Extruded aluminum 6" (152 mm) wide<br />
airfoil profile, heavy gauge 6063-T5<br />
extrusion.<br />
Nylon, press fit into frame.<br />
Square plated steel.<br />
Galvanized steel linkage bar,<br />
concealed in frame.<br />
Removable, 6" long x 1/2” dia.<br />
(152 mm x 12.7 mm) plated steel<br />
coupled to square axle.<br />
Inflatable, pressure sensitive.<br />
Flexible metal, pressure sensitive.<br />
Mill.<br />
1/2" (12.7 mm) diameter standard on<br />
multi sections up to 96"h x 72”w (2438 mm x 1829 mm).<br />
Single Blade 6"w x 5"h (152 mm x 127 mm).<br />
Single Section: 60"w x 72"h (1524 mm x 1829 mm),<br />
Multi Section: Unlimited.<br />
5"<br />
(127 mm)<br />
Motor mounting - Factory furnished<br />
or by others.<br />
Manual quadrant or Chain operator<br />
Painted Finishes<br />
Clear Anodize - 204-R1 & 215-R1<br />
Integral Color Anodize<br />
Right angle and straight line face<br />
and bypass<br />
3/4" (19 mm) Jackshaft reinforcement<br />
Bronze oilite bearings.<br />
Notes: • Dampers fabricated 1/4"<br />
(6.4 mm) under opening size<br />
unless otherwise noted<br />
• All dimensions in ( ) indicate millimeters<br />
• Specify parallel or opposed blade action.<br />
5-3/4"<br />
(146 mm)<br />
Suggested Specification<br />
Opposed<br />
Blade<br />
6"<br />
(152 mm)<br />
3-7/8"<br />
(98 mm)<br />
6"<br />
(152 mm)<br />
Parallel<br />
Blade<br />
Features<br />
The <strong>ACD</strong>-<strong>56</strong> series<br />
Control dampers have<br />
been designed and tested<br />
to provide the ultimate in<br />
performance features for<br />
sophisticated HVAC<br />
systems. Streamlined<br />
("airfoil") blades provide<br />
reduced turbulence and<br />
noise. Inflatable blade<br />
edge and jamb seals<br />
allow extremely tight<br />
seating without unduly<br />
increasing torque<br />
requirements.<br />
5"<br />
(127 mm)<br />
Low Profile<br />
(Damper 16" High or Less)<br />
(406 mm)<br />
Low leakage Control dampers shall be Model: <strong>ACD</strong>-<strong>56</strong> by <strong>NCA</strong> <strong>Manufacturing</strong>. Damper blades shall be of aluminum streamline<br />
("airfoil") construction for minimum pressure drop. Both blade edge and jamb seals shall be of the pressure sensitive type<br />
for low leakage. Dampers shall be rated for leakage and pressure drop to AMCA Standard 500. Leakage through a 48" x 48"<br />
(1219 mm x 1219 mm) shall not exceed 2 cfm/sq/ ft. at 4.0" static pressure.<br />
Specifications are correct at time of printing. However, as part of our ‘continuous improvement program,’ we reserve the right to make further improvements without notice.<br />
© 1999 <strong>NCA</strong> <strong>Manufacturing</strong><br />
Project:<br />
Location:<br />
Architect:<br />
Engineer:<br />
Contractor:<br />
Address:<br />
P.O. Number:<br />
Date:<br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
Pressure Drop – Damper Open 24" x 24" (610 mm x 610 mm)<br />
1.0 (25.4)<br />
0.9 (22.9)<br />
0.8 (20.3)<br />
0.7 (17.8)<br />
0.6 (15.2)<br />
MODEL <strong>ACD</strong>-<strong>56</strong><br />
AIRFOIL PARALLEL OR OPPOSED BLADE DAMPER<br />
LOW LEAKAGE: TESTED TO AMCA 500<br />
Performance Data Graphs<br />
Air Leakage – Damper Closed 48" x 48" (1219 mm x 1219 mm)<br />
8.0 (203.2)<br />
7.0 (177.8)<br />
6.0 (152.4)<br />
0.5 (12.7)<br />
5.0 (127)<br />
0.4 (10.2)<br />
4.0 (127)<br />
Static Pressure Drop In Inches<br />
and (Millimeters) of Water<br />
0.3 (7.6)<br />
0.2 (5.1)<br />
0.15 (3.8)<br />
0.1 (2.5)<br />
Static Pressure In Inches<br />
and (Millimeters) of Water<br />
3.5 (88.9)<br />
3.0 (76.2)<br />
2.5 (63.5)<br />
2.0 (50.8)<br />
.08 (2.03)<br />
1.0 (25.4)<br />
.06 (1.5)<br />
.05 (1.3)<br />
.04 (1.0)<br />
0.9 (22.9)<br />
0.8 (20.3)<br />
0.7 (17.8)<br />
0.6 (15.2)<br />
<strong>ACD</strong>-<strong>56</strong> - 02-05<br />
1000 1500 2000 3000 4000 5000 6000<br />
(5.1) (7.6) (10.2) (15.2) (20.3) (25.4) (30.5)<br />
Velocity<br />
Tested as per AMCA Std. 500, Fig. 5.3 – Air velocity<br />
shown in feet per minute and in ( ) meters per second.<br />
1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0<br />
Leakage<br />
Tested as per AMCA Std. 500, Fig. 5.5 – leakage in CFM per sq. ft.<br />
Typical Model<br />
<strong>ACD</strong>-<strong>56</strong> Installation<br />
The <strong>ACD</strong>-<strong>56</strong> series is not recommended<br />
for vertical blades installation. Always<br />
connect motors to power blade and on<br />
linkage side.<br />
The <strong>ACD</strong>-<strong>56</strong> is suitable for applications<br />
with total pressures up to 4.0" w.g. It may be used<br />
in applications exceeding 4.0" w.g. by reducing<br />
the damper width. For correct damper sizing<br />
consult the factory when exceeding standard<br />
design limit of 4.0" w.g.<br />
The <strong>NCA</strong> frame is designed for easy<br />
installation into duct. Simply put sheet<br />
metal screws through the duct into the<br />
1/2" (12.7 mm) wide mounting flanges<br />
approximately 18" (457 mm) on center.<br />
<strong>NCA</strong> dampers are designed to be self<br />
supporting only in largest single section<br />
size. Larger size may require external<br />
bracing. Reco mmended bracing minimum<br />
of 8' (2438 mm). The amount and size<br />
will depend on unit size and system<br />
pressure.<br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747