MODEL STO/R<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

In today’s life safety products markets, many building codes require fire dampers, smoke dampers<br />

and combination fire and smoke dampers to be inspected for proper operation. Many of these codes<br />

require that the damper be inspected and cycled every 12 months to 4 years depending on the local<br />

authority and the type of system in which it is installed. Usually fire dampers and combination fire and<br />

smoke dampers are supplied with a fusible link. The fusible link is a one time device and is generally<br />

limited to 165°F or 212°F. Once the link has experienced these elevated temperatures, it can no<br />

longer be used and must be replaced with an indentical link. Locating and acquiring the indentical<br />

fusible link can be troublesome and time consuming. <strong>NCA</strong> <strong>Manufacturing</strong>’s STO/R option provides<br />

the ease of operating and resetting the damper in a matter of seconds without replacing the link. The<br />

EFL is used in lieu of a conventional fusible link. It is a reusable/resettable heat responsive device that can only be reset after a visual inspection<br />

of the damper. Dampers which allow remote resetting of the heat response device from a remote location are dangerous. A remotely<br />

reset damper may not be fully functional and should be visually inspected. The STO/R is reset from the outside of the damper sleeve, therefore<br />

requiring a visual inspection of the damper. By depressing a button on the outside of the sleeve and inspector can verify if the damper is fully<br />

operational. The ELF is a multi-use heat responsive device. It is wired in series with the GND actuator therefore it is user friendly in most<br />

applications. When the smoke detector interrupts the current to the damper, the ELF will not hinder the closing of the damper. The STO/R<br />

package includes blade indicator switches which allow for remote notification of damper blade position, as a standard feature.<br />

The STO/R option is available on all <strong>NCA</strong> <strong>Manufacturing</strong> FSD Model Combination Fire/Smoke Dampers and Motorized Multi-Blade Fire Dampers,<br />

refer to pages 3 and 4 for the Siemens GND Series actuator. The below details do not apply to the GND Series.<br />

Devices to Left of dashed line are located<br />

Devices to right of dashed line are factory<br />

remotely from damper - furnished by others.<br />

mounted on damper.<br />

Field wiring terminates at splice points<br />

indicated by " "<br />

120 or 24 volt ac damper actuator power<br />

L1<br />

L2<br />

LISTING<br />

STATE OF CALIFORNIA<br />

STATE<br />

FIRE<br />

S E R V<br />

M A R S H A L L<br />

IC E<br />

LISTED AND LABELLED BY:<br />

DESIGNED AND TESTED IN ACCORDANCE WITH<br />

UL-555 AND ULC-S112. MEETS ALL NFPA-90A<br />

REQUIREMENTS FOR FIRE DAMPERS.<br />

Electric damper actuator (power on opens<br />

damper, power off closes damper).<br />

X<br />

Blue<br />

STO/R - 05-08 (STOR)<br />

L1<br />

CLOSED<br />

Normal (DAMPER OPEN)<br />

Open/closed auto switching<br />

Any supply voltage<br />

compatible with<br />

lights & switches<br />

L2<br />

Damper open<br />

indicator light<br />

Damper closed<br />

indicator light<br />

Orange<br />

Smoke Detector<br />

(If Used)<br />

ELF Temperature sensing device<br />

(Opens when temperature exceeds<br />

closure rating)<br />

Smoke Detector may be field or factory supplied.<br />

Yellow<br />

Yellow<br />

Red<br />

Red<br />

Position indicator switch<br />

(closes when damper is open)<br />

FSD DAMPER STO/R OPERATION<br />

Switch is in Normal (Damper Open) Position: Damper motor is energized until<br />

<strong>thermostat</strong> senses temperature above initial closure rating. Above temperature<br />

closure rating, the damper motor is de-energized and damper closes.<br />

Smoke Detector (if used) wired in series with temperature sensitive device.<br />

Switch in Closed Position damper motor is de-energized and damper is closed.<br />

Detailed wiring diagrams including terminal designation and/or wire color coding<br />

furnished with each shipment.<br />

Position indicator switch<br />

(closes when damper is closed)<br />

Indicator Switch Electrical Limitations<br />

• 10 Amperes, 1/4 HP, 120 or 240 Volts A.C.<br />

• .5 Ampere, 125 Volts D.C.<br />

• .25 Ampere, 250 Volts D.C.<br />

• 5 Amperes, 120 Volts (Lamp Load)<br />

• 15 Amperes, 24 Volts D.C.<br />

Manufacturer’s Recommendations<br />

All moving parts of the damper must be inspected and cycled at intervals not greater than every six months and in accordance with<br />

the latest edition of NFPA 90A, 92A, local codes and the actuator manufacturer. In addition, fuse links shall be removed and inspected<br />

for corrosion. Dry lubricants are recommended.<br />

Page 1 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL STO/R<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

Dampers with Siemens GND Actuators, See page 3 and 4 of this document.<br />

STO/R Wiring Details<br />

L1<br />

Blk.<br />

Remote<br />

Command<br />

Station<br />

Switch Package<br />

Wiring<br />

Compartment<br />

L2<br />

Wht.<br />

Blk.<br />

Control<br />

Panel<br />

Org.<br />

Org.<br />

L<br />

Wire Nut<br />

Blue<br />

Blk.<br />

Motor<br />

Actuator<br />

M1<br />

Wht.<br />

L3<br />

Blk.<br />

Closed<br />

Blk.<br />

Smoke Detector<br />

If Used<br />

TS1<br />

Red<br />

S1<br />

Red<br />

L4<br />

Red Light<br />

Open<br />

Blk.<br />

Blk.<br />

Yellow<br />

Yellow<br />

Green Light<br />

S2<br />

L3, L4 is a Supply Voltage Compatible with Lights and Switches. Standard Voltage is<br />

Same as Actuator Ordered.<br />

STO/R - 02-06 (STOR)<br />

Red<br />

Red<br />

FS Primary<br />

Heat Sensor<br />

Manual Reset<br />

S1<br />

TS1<br />

S2<br />

Yellow<br />

Yellow<br />

Orange<br />

Blue<br />

Page 2 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL STO/R w/Siemens GND Series Actuator<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

STO/R - 02-06 (STOR)<br />

The Thermostat is wired to the actuator<br />

via a low voltage (24 vac) connection. In<br />

most cases codes does not require this<br />

wiring to be incased. Check with your<br />

local codes to see if low voltage wires<br />

requires conduit.<br />

Supply (X)<br />

Neutral (Y)<br />

Ground<br />

24 vac/vdc 120 vac 230 vac<br />

Red White Brown<br />

Black Black Blue<br />

Green Green Green<br />

Auxiliary Switches<br />

Switch Wire<br />

Makes Color Note: Both sets of auxiliary switch<br />

contacts are open when actuator<br />

Closed 85° Yellow<br />

Ratings:<br />

250 vac - 10 amps<br />

Motor Load - 3 amps<br />

o o<br />

Max. Temperature - 350 F (177 C)<br />

Page 3 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL STO/R w/Siemens GND Series Actuator<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

STO/R - 02-06 (STOR)<br />

Page 4 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL STO/R<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

L1<br />

Remote<br />

Command<br />

Station<br />

Control<br />

Panel<br />

Smoke Detector<br />

If Used<br />

L<br />

Blue<br />

Switch Package<br />

Wiring/Piping<br />

Compartment<br />

E-P Switch<br />

L2<br />

TS1<br />

Pneumatic<br />

Actuator<br />

25 Psi<br />

L3<br />

Blk.<br />

Closed<br />

Blk.<br />

Red<br />

S1<br />

Red<br />

P1<br />

L4<br />

Red Light<br />

Open<br />

Blk. Blk.<br />

Yellow<br />

Yellow<br />

Green Light<br />

S2<br />

STO/R - 02-06 (STOR)<br />

L1, L2 is the E-P Switch Supply Voltage<br />

desired (120vac or 24vac). L3, L4 is a<br />

Supply Voltage Compatible with Lights and<br />

Switches. Standard Voltage is 120vac if<br />

not Specified.<br />

Red<br />

Red<br />

S1<br />

S2<br />

Yellow<br />

Yellow<br />

FS Primary<br />

Heat Sensor<br />

Manual Reset<br />

TS1<br />

Orange<br />

Blue<br />

Page 5 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />

<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747


MODEL STO/R<br />

(SINGLE THERMOSTAT OPERATOR RELEASE)<br />

FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />

MOTORIZED MULTI-BLADE FIRE DAMPERS<br />

Pneumatic Actuator with a PFV Option<br />

L1<br />

Remote<br />

Command<br />

Station<br />

E-P Switch<br />

Smoke Detector<br />

If Used<br />

Switch Package<br />

Wiring/Piping<br />

Compartment<br />

L2<br />

Pneumatic<br />

Actuator<br />

25 Psi<br />

L3<br />

Blk.<br />

Closed<br />

Blk.<br />

Flow<br />

Restrictor<br />

PFV<br />

Red<br />

S1<br />

Red<br />

P1<br />

L4<br />

Red Light<br />

Open<br />

Blk.<br />

Blk.<br />

Yellow<br />

Yellow<br />

Fusible<br />

Link<br />

Sleeve<br />

Green Light<br />

Air Supply<br />

to Actuator<br />

S2<br />

L3, L4 is a Supply Voltage Compatible<br />

with Lights and Switches. Standard<br />

Voltage is 120vac if not Specified.<br />

STO/R - 02-06 (STOR)<br />

Inside<br />

Duct<br />

Outside<br />

Duct<br />

Flow Restrictor<br />

Incoming<br />

Air Supply<br />

Red<br />

S1<br />

S2<br />

Yellow<br />

Red<br />

Yellow<br />

Page 6 of 6<br />

© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />