model sto/r (single thermostat operator release) - NCA Manufacturing
model sto/r (single thermostat operator release) - NCA Manufacturing
model sto/r (single thermostat operator release) - NCA Manufacturing
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
MODEL STO/R<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
In today’s life safety products markets, many building codes require fire dampers, smoke dampers<br />
and combination fire and smoke dampers to be inspected for proper operation. Many of these codes<br />
require that the damper be inspected and cycled every 12 months to 4 years depending on the local<br />
authority and the type of system in which it is installed. Usually fire dampers and combination fire and<br />
smoke dampers are supplied with a fusible link. The fusible link is a one time device and is generally<br />
limited to 165°F or 212°F. Once the link has experienced these elevated temperatures, it can no<br />
longer be used and must be replaced with an indentical link. Locating and acquiring the indentical<br />
fusible link can be troublesome and time consuming. <strong>NCA</strong> <strong>Manufacturing</strong>’s STO/R option provides<br />
the ease of operating and resetting the damper in a matter of seconds without replacing the link. The<br />
EFL is used in lieu of a conventional fusible link. It is a reusable/resettable heat responsive device that can only be reset after a visual inspection<br />
of the damper. Dampers which allow remote resetting of the heat response device from a remote location are dangerous. A remotely<br />
reset damper may not be fully functional and should be visually inspected. The STO/R is reset from the outside of the damper sleeve, therefore<br />
requiring a visual inspection of the damper. By depressing a button on the outside of the sleeve and inspector can verify if the damper is fully<br />
operational. The ELF is a multi-use heat responsive device. It is wired in series with the GND actuator therefore it is user friendly in most<br />
applications. When the smoke detector interrupts the current to the damper, the ELF will not hinder the closing of the damper. The STO/R<br />
package includes blade indicator switches which allow for remote notification of damper blade position, as a standard feature.<br />
The STO/R option is available on all <strong>NCA</strong> <strong>Manufacturing</strong> FSD Model Combination Fire/Smoke Dampers and Motorized Multi-Blade Fire Dampers,<br />
refer to pages 3 and 4 for the Siemens GND Series actuator. The below details do not apply to the GND Series.<br />
Devices to Left of dashed line are located<br />
Devices to right of dashed line are factory<br />
remotely from damper - furnished by others.<br />
mounted on damper.<br />
Field wiring terminates at splice points<br />
indicated by " "<br />
120 or 24 volt ac damper actuator power<br />
L1<br />
L2<br />
LISTING<br />
STATE OF CALIFORNIA<br />
STATE<br />
FIRE<br />
S E R V<br />
M A R S H A L L<br />
IC E<br />
LISTED AND LABELLED BY:<br />
DESIGNED AND TESTED IN ACCORDANCE WITH<br />
UL-555 AND ULC-S112. MEETS ALL NFPA-90A<br />
REQUIREMENTS FOR FIRE DAMPERS.<br />
Electric damper actuator (power on opens<br />
damper, power off closes damper).<br />
X<br />
Blue<br />
STO/R - 05-08 (STOR)<br />
L1<br />
CLOSED<br />
Normal (DAMPER OPEN)<br />
Open/closed auto switching<br />
Any supply voltage<br />
compatible with<br />
lights & switches<br />
L2<br />
Damper open<br />
indicator light<br />
Damper closed<br />
indicator light<br />
Orange<br />
Smoke Detector<br />
(If Used)<br />
ELF Temperature sensing device<br />
(Opens when temperature exceeds<br />
closure rating)<br />
Smoke Detector may be field or factory supplied.<br />
Yellow<br />
Yellow<br />
Red<br />
Red<br />
Position indicator switch<br />
(closes when damper is open)<br />
FSD DAMPER STO/R OPERATION<br />
Switch is in Normal (Damper Open) Position: Damper motor is energized until<br />
<strong>thermostat</strong> senses temperature above initial closure rating. Above temperature<br />
closure rating, the damper motor is de-energized and damper closes.<br />
Smoke Detector (if used) wired in series with temperature sensitive device.<br />
Switch in Closed Position damper motor is de-energized and damper is closed.<br />
Detailed wiring diagrams including terminal designation and/or wire color coding<br />
furnished with each shipment.<br />
Position indicator switch<br />
(closes when damper is closed)<br />
Indicator Switch Electrical Limitations<br />
• 10 Amperes, 1/4 HP, 120 or 240 Volts A.C.<br />
• .5 Ampere, 125 Volts D.C.<br />
• .25 Ampere, 250 Volts D.C.<br />
• 5 Amperes, 120 Volts (Lamp Load)<br />
• 15 Amperes, 24 Volts D.C.<br />
Manufacturer’s Recommendations<br />
All moving parts of the damper must be inspected and cycled at intervals not greater than every six months and in accordance with<br />
the latest edition of NFPA 90A, 92A, local codes and the actuator manufacturer. In addition, fuse links shall be removed and inspected<br />
for corrosion. Dry lubricants are recommended.<br />
Page 1 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
MODEL STO/R<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
Dampers with Siemens GND Actuators, See page 3 and 4 of this document.<br />
STO/R Wiring Details<br />
L1<br />
Blk.<br />
Remote<br />
Command<br />
Station<br />
Switch Package<br />
Wiring<br />
Compartment<br />
L2<br />
Wht.<br />
Blk.<br />
Control<br />
Panel<br />
Org.<br />
Org.<br />
L<br />
Wire Nut<br />
Blue<br />
Blk.<br />
Motor<br />
Actuator<br />
M1<br />
Wht.<br />
L3<br />
Blk.<br />
Closed<br />
Blk.<br />
Smoke Detector<br />
If Used<br />
TS1<br />
Red<br />
S1<br />
Red<br />
L4<br />
Red Light<br />
Open<br />
Blk.<br />
Blk.<br />
Yellow<br />
Yellow<br />
Green Light<br />
S2<br />
L3, L4 is a Supply Voltage Compatible with Lights and Switches. Standard Voltage is<br />
Same as Actuator Ordered.<br />
STO/R - 02-06 (STOR)<br />
Red<br />
Red<br />
FS Primary<br />
Heat Sensor<br />
Manual Reset<br />
S1<br />
TS1<br />
S2<br />
Yellow<br />
Yellow<br />
Orange<br />
Blue<br />
Page 2 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
MODEL STO/R w/Siemens GND Series Actuator<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
STO/R - 02-06 (STOR)<br />
The Thermostat is wired to the actuator<br />
via a low voltage (24 vac) connection. In<br />
most cases codes does not require this<br />
wiring to be incased. Check with your<br />
local codes to see if low voltage wires<br />
requires conduit.<br />
Supply (X)<br />
Neutral (Y)<br />
Ground<br />
24 vac/vdc 120 vac 230 vac<br />
Red White Brown<br />
Black Black Blue<br />
Green Green Green<br />
Auxiliary Switches<br />
Switch Wire<br />
Makes Color Note: Both sets of auxiliary switch<br />
contacts are open when actuator<br />
Closed 85° Yellow<br />
Ratings:<br />
250 vac - 10 amps<br />
Motor Load - 3 amps<br />
o o<br />
Max. Temperature - 350 F (177 C)<br />
Page 3 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
MODEL STO/R w/Siemens GND Series Actuator<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
STO/R - 02-06 (STOR)<br />
Page 4 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
MODEL STO/R<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
L1<br />
Remote<br />
Command<br />
Station<br />
Control<br />
Panel<br />
Smoke Detector<br />
If Used<br />
L<br />
Blue<br />
Switch Package<br />
Wiring/Piping<br />
Compartment<br />
E-P Switch<br />
L2<br />
TS1<br />
Pneumatic<br />
Actuator<br />
25 Psi<br />
L3<br />
Blk.<br />
Closed<br />
Blk.<br />
Red<br />
S1<br />
Red<br />
P1<br />
L4<br />
Red Light<br />
Open<br />
Blk. Blk.<br />
Yellow<br />
Yellow<br />
Green Light<br />
S2<br />
STO/R - 02-06 (STOR)<br />
L1, L2 is the E-P Switch Supply Voltage<br />
desired (120vac or 24vac). L3, L4 is a<br />
Supply Voltage Compatible with Lights and<br />
Switches. Standard Voltage is 120vac if<br />
not Specified.<br />
Red<br />
Red<br />
S1<br />
S2<br />
Yellow<br />
Yellow<br />
FS Primary<br />
Heat Sensor<br />
Manual Reset<br />
TS1<br />
Orange<br />
Blue<br />
Page 5 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747
MODEL STO/R<br />
(SINGLE THERMOSTAT OPERATOR RELEASE)<br />
FOR COMBINATION FIRE / SMOKE DAMPERS AND<br />
MOTORIZED MULTI-BLADE FIRE DAMPERS<br />
Pneumatic Actuator with a PFV Option<br />
L1<br />
Remote<br />
Command<br />
Station<br />
E-P Switch<br />
Smoke Detector<br />
If Used<br />
Switch Package<br />
Wiring/Piping<br />
Compartment<br />
L2<br />
Pneumatic<br />
Actuator<br />
25 Psi<br />
L3<br />
Blk.<br />
Closed<br />
Blk.<br />
Flow<br />
Restrictor<br />
PFV<br />
Red<br />
S1<br />
Red<br />
P1<br />
L4<br />
Red Light<br />
Open<br />
Blk.<br />
Blk.<br />
Yellow<br />
Yellow<br />
Fusible<br />
Link<br />
Sleeve<br />
Green Light<br />
Air Supply<br />
to Actuator<br />
S2<br />
L3, L4 is a Supply Voltage Compatible<br />
with Lights and Switches. Standard<br />
Voltage is 120vac if not Specified.<br />
STO/R - 02-06 (STOR)<br />
Inside<br />
Duct<br />
Outside<br />
Duct<br />
Flow Restrictor<br />
Incoming<br />
Air Supply<br />
Red<br />
S1<br />
S2<br />
Yellow<br />
Red<br />
Yellow<br />
Page 6 of 6<br />
© 2006 <strong>NCA</strong> <strong>Manufacturing</strong><br />
<strong>NCA</strong> MANUFACTURING, INC. 1036 SOUTH JUPITER ROAD GARLAND, TEXAS 75042 TEL. 972-276-5002 FAX 972-276-6747