<strong>iFan</strong> <strong>Twin</strong><strong>Box</strong> Section 1.1<br />

• 125mm - 400mm diameter spigot sizes<br />

• Volume flow up to 0.74m 3 /s<br />

• Static pressures up to 425 Pa<br />

• Spigots with double lip neoprene seals<br />

as standard<br />

• Forward curved impellers<br />

• Acoustically lined box<br />

• ICU display to assist in set up<br />

Sizes<br />

<strong>iFan</strong> Inline <strong>Twin</strong>fan<br />

<strong>iFan</strong> 125, 150, 200, 250, 315, 355, 400 ILT<br />

All sizes refer to circular inlet and outlet connections.<br />

Construction<br />

Casings are manufactured from pre-galvanised sheet steel and are carefully designed to provide a strong<br />

and rigid casing.<br />

<strong>iFan</strong> inline twinfan units have circular inlet and outlet spigots with a double-lip neoprene seal minimising leakage.<br />

The units are internally lined with acoustic grade rockwool with a facing to prevent the erosion of fibres.<br />

<strong>iFan</strong> inline twinfan units incorporate an internal shutter arrangement to prevent recirculation through the<br />

standby fan.<br />

<strong>iFan</strong> inline twinfan and ICU1.5 are designed for duct mounting within the building.<br />

Motors<br />

The motor is mounted within the centrifugal impeller to form a compact unit, powered by a 220-240V/50Hz/1<br />

phase motor, giving silent and virtually vibration free running, operating at temperatures of up to a maximum<br />

of 40°C. All motors are manufactured in accordance with BS5000 and incorporate thermal overload protection,<br />

they are maintenance free, with sealed for life bearings offering an expected life L10 of 40,000 hours.<br />

Electrical Supply<br />

220 - 240V / 50Hz / 1φ.<br />

Temperature Range<br />

up to 40°C.<br />

Wiring/Controls<br />

• Robust construction<br />

• Suitable for either horizontal or vertical<br />

(air up) mounting<br />

• Low sound levels<br />

• Fan operation up to 40°C<br />

• Auto-changeover facility in the event of fan failure<br />

• Integral Intelligent Control Unit<br />

• Duty sharing facility<br />

Section 1 - Demand Control Ventilation<br />

All units are speed controllable using the integral Fläkt Woods <strong>iFan</strong> Intelligent Control Unit (ICU1.5).<br />

Servicing<br />

The top panel of each unit allows easy access for inspection.<br />

The fan assembly can also be easily removed for cleaning purposes.<br />

Mounting<br />

Suitable for both horizontal and vertical (air up) mounting only.<br />

The units can be inverted if bottom access is required.<br />