Description<br />

3.5 nstallation<br />

Other possible fields of application for explosion-proof machines<br />

The type of construction of the machine is stated on the nameplate.<br />

DANGER<br />

In the case of explosion-proof machines where the shaft extensions point downwards<br />

(types of construction IM V5, IM V1 or IM V18 ) a protective top cover is mandatory. A<br />

protective top cover is automatically installed at the factory for explosion-proof motors with<br />

IM V5, IM V1 or IM V18 types of construction. For types of construction with shaft extension<br />

pointing upwards, a suitable cover must be implemented to prevent small parts from falling<br />

into the fan cover (see the standard IEC/EN 60079-0). The cover must not block the cooling<br />

air flow.<br />

Table 3- 7<br />

Construction type with protective top cover<br />

Conditions of installation<br />

Graphics-Based Representation<br />

IM V5 (IM 1011)<br />

IM V1 (IM 3011)<br />

IM V18 (IM 3611)<br />

3.5.7 Degree of protection<br />

The machines have degree of protection IP 55 (see rating plate). They can be installed in<br />

dusty or humid environments.<br />

NOTICE<br />

Condensation holes<br />

In order to comply with the degree of protection, any existing condensation holes are to be<br />

sealed!<br />

If the machines are used or are stored outdoors, we recommend that they be kept under<br />

some sort of additional cover so that they are not subjected to direct intensive solar radiation,<br />

rain, snow, ice or dust over a long period of time.<br />

In such cases, technical consultation may be appropriate.<br />

The machines are suitable for use in the tropics.<br />

Guide value of 60% relative humidity at a coolant temperature (CT) of 40° C.<br />

Ambient temperature: -20° C to +40° C<br />

Installation altitude: ≤ 1000 m<br />

1LA5/6/7/9, 1LP7/9, 1PP6/7/9, 1MA6/7, 1MF6/7, 1MJ6, 1LE1<br />

Operating Instructions, 10/2008, 5 610 00000 02 000 21