Mounting, installation<br />

5.3 Connecting<br />

Before closing the terminal box, check that<br />

• the air clearances for explosion-proof machines (with the exception of machines<br />

for Zone 22) between non-insulated parts are maintained: ≥ 10 mm to 690 V.<br />

• the creepage distance for explosion-proof machines (with the exception of<br />

machines for Zone 22) between non-insulated parts are maintained: ≥ 12 mm to<br />

690 V.<br />

5.3.2 Tightening torques<br />

5.3.2.1 General notes<br />

CAUTION<br />

It must be ensured that there are no foreign bodies, dirt or moisture in the terminal box.<br />

Cable glands in the terminal box (see DIN 42925) and other open entries with dummy plugs<br />

are to be sealed with an O ring or a suitable flat gasket so that dust and water cannot enter,<br />

whereas the terminal box itself is to be sealed against dust and water with the original seal.<br />

Comply with the specified tightening torques for cable glands and other screw-type<br />

connections.<br />

Secure featherkey for trial operation without transmission elements.<br />

5.3.2.2 Electrical connections - Termincal board connections<br />

Table 5- 5<br />

Tightening torques for electrical connections on the terminal board<br />

Thread ∅ M 4 M 5 M 6 M 8 M 10 M 12 M 16<br />

Nm<br />

min 0,8 1,8 2,7 5,5 9 14 27<br />

max 1,2 2,5 4 8 13 20 40<br />

1LA5/6/7/9, 1LP7/9, 1PP6/7/9, 1MA6/7, 1MF6/7, 1MJ6, 1LE1<br />

44 Operating Instructions, 10/2008, 5 610 00000 02 000