GEZE RWA systems<br />

Legal basis<br />

Building law<br />

Requirements of the MBO and LBOs regarding smoke dissipation and<br />

ventilation<br />

– Continued –<br />

GEZE RWA<br />

Federal<br />

state<br />

Hamburg<br />

Regulations<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

Dated<br />

11 May<br />

2010<br />

<strong>Smoke</strong> dissipation<br />

where?<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

<strong>Smoke</strong><br />

dissipation<br />

where?<br />

At the highest<br />

point<br />

<strong>Smoke</strong><br />

dissipation -<br />

how large?<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Operating<br />

points where?<br />

Ground floor and<br />

top landing<br />

Ventilation<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

<strong>Smoke</strong> and heat<br />

extraction systems<br />

(RWA)<br />

Hesse<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

15 December<br />

2009<br />

For necessary internal stairways<br />

Class 5 buildings<br />

At the highest<br />

point<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Mecklenburg-West<br />

Pomerania<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

18 April<br />

2006<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Lower<br />

Saxony<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

28 October<br />

2009<br />

No statement regarding<br />

smoke dissipation / smoke<br />

extraction<br />

Stairways must be able to be ventilated<br />

North Rhine-<br />

Westphalia<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

17 December<br />

2009<br />

Building with more than<br />

5 storeys above the ground<br />

and in case of necessary<br />

internal stairways<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

5% of the floor<br />

area; however, at<br />

least 1m²<br />

Ground floor<br />

and top landing.<br />

Further operating<br />

points can be<br />

approved.<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Rhineland-<br />

Palatinate<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

27 October<br />

2009<br />

Buildings with more than<br />

5 storeys above the ground<br />

and for necessary internal<br />

stairways, not located at<br />

the external wall<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

5% of the floor<br />

area; however,<br />

at least 1m²<br />

Ground floor<br />

and top landing.<br />

Further operating<br />

points can be<br />

approved.<br />

Stairways must be able to be ventilated<br />

On each above-ground storey of necessary<br />

stairways located at the external<br />

wall in building classes 4 + 5, must<br />

have windows leading directly to the<br />

outside with minimum size 0.6m x 0.9m<br />

(width x height), which can be opened<br />

and have a sill height not greater than<br />

1.20m<br />

Saarland<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

21 November<br />

2007<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Saxony<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

13 August<br />

2009<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Saxony-<br />

Anhalt<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

20 December<br />

2005<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Schleswig-<br />

Holstein<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

9 March<br />

2010<br />

For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

Thuringia<br />

LBO<br />

(state<br />

building<br />

regulations)<br />

8 July 2009 For necessary internal<br />

stairways and necessary<br />

stairways in buildings more<br />

than 13m high<br />

At the highest<br />

point of the<br />

stairwell<br />

With a free crosssection<br />

of at least<br />

1m²<br />

Ground floor and<br />

top landing<br />

Necessary stairwells: On each aboveground<br />

storey, windows leading<br />

directly to the outside with a free crosssectional<br />

area of at least 0.5m², which<br />

can be opened<br />

GEZE RWA systems<br />

113