GEZE RWA exhaust systems<br />

geze electrically operated chain drives<br />

Combination of brackets/type of installation<br />

Bracket for<br />

bottom hung window<br />

inward-opening<br />

Frame-Installation<br />

bottom hung window<br />

Outward-opening<br />

Frame-Installation<br />

bottom hung window<br />

inward-opening<br />

Casement Installation<br />

Top hung window<br />

inward-opening<br />

Frame-Installation<br />

Top hung window<br />

Outward-opening<br />

Frame-Installation<br />

Top hung window<br />

inward-opening<br />

Casement Installation<br />

Side hung window<br />

inward-opening<br />

Frame-Installation<br />

Side hung window<br />

Outward-opening<br />

Frame-Installation<br />

Side hung window<br />

inward-opening<br />

Casement Installation<br />

Drive fitting type A s d type A d type A s d type A d type A s d type A d type A<br />

Drive fitting type B d type B s s s s s s s s<br />

without drive fitting d type B s s d type B s s d type B s s<br />

GEZE RWA<br />

<strong>Smoke</strong> and heat<br />

extraction systems<br />

(RWA)<br />

Where there are several alternatives available, selection depends on the window size, structural circumstances and chain stroke chosen.<br />

d = yes<br />

s = no<br />

RWA chain drive E 820 on bottom hung and top hung windows that open inwards and outwards<br />

Calculation of the area of application depending on casement weight and casement dimensions<br />

Permissible wind loads must be taken into consideration!<br />

Equation for calculating opening and closing force:<br />

F =<br />

p x stroke x 0.54<br />

b<br />

Example for E 820 in individual operation:<br />

P = 25 kg = approx. 250 N<br />

Stroke = 400 mm<br />

b = 1000 mm<br />

250 x 400 x 0.54<br />

F =<br />

1000<br />

F max. = 250 N per drive<br />

F = 54 N<br />

Key<br />

F Opening and closing force required (N)<br />

P Casement weight (kg)<br />

Stroke Casement path/drive stroke (mm)<br />

b Casement height (mm)<br />

Top hung windows<br />

Bottom hung window<br />

Stroke<br />

F<br />

Example for two drives E 820 Syncro:<br />

P = 95 kg = approx. 950 N<br />

Stroke = 400 mm<br />

b = 800 mm<br />

950 x 400 x 0.54<br />

F =<br />

800<br />

F = 257 N<br />

b<br />

F<br />

P<br />

Stroke<br />

P<br />

b<br />

Casement panel weight:<br />

max. 30 kg/m 2 (drive cannot be swivelled)<br />

max. 40 kg/m 2 (drive can be swivelled)<br />

Max. pushing and pulling force depends on the drive stroke<br />

(see force-path diagram). This must be considered in the<br />

calculation<br />

Force-path diagram<br />

Force F (N)<br />

Pull<br />

Pressure<br />

(shaded area)<br />

Stroke (mm)<br />