GEZE RWA exhaust systems<br />

geze electrically operated chain drives<br />

RWA chain drive E 740 on skylight<br />

Calculation of the area of application depending on casement weight and casement dimensions<br />

Permissible wind loads must be taken into consideration!<br />

GEZE RWA<br />

Equation for calculating opening and closing force:<br />

F = P x 0.68<br />

Key<br />

F<br />

P<br />

Drive force required for opening (N)<br />

Casement weight (kg)<br />

<strong>Smoke</strong> and heat<br />

extraction systems<br />

(RWA)<br />

Example for E 740 in individual operation:<br />

P = 25 kg = approx. 250 N<br />

F = 250 x 0.68 F = 170 N<br />

Horizontal windows and light domes<br />

Example for two drives E 740 Syncro:<br />

P = 60 kg = approx. 600 N<br />

F = 600 x 0.68 F = 408 N<br />

F<br />

P<br />

F max. = 250 N (individual operation)<br />

F max. = 500 N (synchronous operation)<br />

Minimum casement dimensions<br />

Bracket<br />

AW RM/FM<br />

Stroke 100 mm<br />

250 mm<br />

Min. casement<br />

height<br />

Stroke 200 mm<br />

Stroke 300 mm<br />

450 mm<br />

600 mm<br />

Stroke 400 mm<br />

750 mm<br />

Min. casement<br />

width<br />

Individual<br />

operation<br />

Synchronous<br />

operation<br />

450 mm<br />

1000 mm<br />

Projection range<br />

0-20 mm<br />

Min. space<br />

requirement<br />

on the frame<br />

on the casement<br />

60 mm<br />

42 mm<br />

Min. casement heights depending on projection<br />

j<br />

j<br />

Min. casement height depends on projection and increases as projection increases<br />

Guideline values: Installation can vary depending on the type of window<br />

Casement height up to centre of hinge (mm)<br />

Max. stroke 100 mm<br />

Max. stroke 200 mm<br />

Max. stroke 300 mm<br />

Max. stroke 400 mm<br />

Projection (mm)<br />

Space required<br />

for casement<br />

Space required<br />

for frame<br />

40<br />

60<br />

GEZE RWA systems<br />

19