GEZE RWA exhaust systems<br />

geze electrically operated chain drives<br />

RWA electrically operated chain drive E 860 – minimum casement heights<br />

Depending on the type of installation and the drive fittings and brackets to be used, the following minimum casement heights can be achieved<br />

(depending on the projection (Ü))<br />

GEZE RWA<br />

Drive fitting type 1 Drive fitting type 2<br />

Drive fitting type 2<br />

Drive fitting type 3<br />

Bracket set FM<br />

A<br />

Dimension x =<br />

35 mm<br />

B<br />

Dimension x =<br />

51 mm<br />

B<br />

+ bracket type C<br />

C<br />

Stroke Projection (mm) Projection (mm) Projection (mm) Projection (mm) Projection (mm)<br />

(mm) 0 8 16 21 0 8 16 21 0 8 16 21 0 8 16 21 0 10 21<br />

1250 900 900 1000 1000 500 550 550 650 200 200 200 250 350 350 400 400 500 350 375<br />

1400 1600 1600 1700 1700 1000 1150 1200 1300 400 400 450 500 700 700 800 800 800 500 600<br />

1500 2100 2100 2200 2200 1100 1300 1300 1350 500 500 600 600 900 900 1000 1000 1000 650 750<br />

1600 2500 2500 s s 1250 1500 1600 1700 600 650 700 750 1200 1200 1300 1300 1200 800 900<br />

1800 s s s s 1700 2100 2200 2350 800 850 950 1000 1600 1600 1700 1700 1600 1050 1200<br />

1000 s s s s 2150 2600 2800 3000 1000 1050 1150 1200 2000 2000 2100 2100 2000 1300 1500<br />

<strong>Smoke</strong> and heat<br />

extraction systems<br />

(RWA)<br />

s = no<br />

The minimum casement height for top hung windows that open outwards is 400 mm (drive fitting type 2) or 800 mm (drive fitting type 1).<br />

Minimum casement heights are applicable for bottom, top and side hung windows. On horizontally and vertically pivot hung windows,<br />

FH corresponds to the distance from the main closing edge to the hinge axis. For the assignment of A, B and C see the following fitting<br />

dimensions.<br />

Fitting dimensions drive fitting type1 with bracket type A<br />

A<br />

min. 30<br />

24<br />

43<br />

80<br />

Space<br />

required for<br />

casement<br />

11<br />

55<br />

(67)<br />

15<br />

13<br />

14<br />

37 30<br />

51 16<br />

10 22<br />

LE<br />

198<br />

22 10<br />

42<br />

Centre of window<br />

42<br />

Space required<br />

for frame<br />

Fitting dimensions drive fitting type 2 with bracket type A<br />

80<br />

Space required<br />

for casement<br />

24<br />

43<br />

B<br />

11<br />

(88)<br />

x<br />

(x–16)<br />

72 16<br />

55<br />

37<br />

13<br />

22<br />

10 22<br />

42<br />

LE<br />

198<br />

Centre of window<br />

22 10<br />

42<br />

Space required<br />

for frame<br />

GEZE RWA systems<br />

41