TAC<br />

1354 Clifford Avenue<br />

P. O. Box 2940<br />

Loves Park, IL 61132-2940<br />

www.tac.com<br />

<strong>TA157</strong> Series<br />

TB157 Series<br />

3-<strong>Wire</strong> <strong>Floating</strong><strong>Thermostat</strong>/Controller<br />

Installation Instructions<br />

MOUNTING AND WIRING<br />

Caution: Disconnect power supply and ensure that all<br />

wiring complies with applicable codes and ordinances.<br />

1. The T157 Series thermostats install with two furnished<br />

mounting screws to a standard 4-11/16" x 2-1/8" square<br />

device box with a 2" x 4" adapter ring.<br />

2. For wall installations, mount the thermostat on an inside<br />

wall approximately 5 ft. above the floor. The location<br />

should provide circulation at average room temeprature.<br />

Avoid direct sunlight or sources of hot or cold air in the<br />

room or wall.<br />

3. To remove cover, first set knob to mid span and remove.<br />

Mount thermostat base assembly to the outlet box using<br />

the screws provided. Tighten the screws evenly but do<br />

not over tighten. Connect wires as shown in the<br />

appropriate wiring diagram for your thermostat style.<br />

4. To use a remote sensor on units with local sensing<br />

capability, remove jumper JP-1 to disable local sensing.<br />

Failure to remove JP-1 will cause improper operation of<br />

the thermostat.<br />

5. On units with cycling fan option, connect terminal 1<br />

(SWITCHED POWER) to 6 (FAN SUPPLY) for<br />

continuous fan operation, see Figure-1.<br />

6. Reinstall the cover assembly. Install cover locking screw<br />

if provided (see Figure-2). Reinstall the knob to complete<br />

installation.<br />

7. Checkout: After wiring and installation are complete,<br />

energize the system and check the operation. Adjust the<br />

thermostat as necessary to complete at least one cycle.<br />

Be sure the thermostat and all other equipment are<br />

functioning correctly.<br />

Operation<br />

<strong>TA157</strong> Models: Heating/Cooling thermostats requiring a<br />

switch for manual selection of HEAT-OFF-COOL. Some<br />

models have an integral Fan Switch for manual selection of<br />

fan speeds.<br />

TB157 Models: Auto-Change Over Heating, Cooling<br />

thermostat. Heat on to Cool on dead band is 5 F° nominal.<br />

Some models have an integral system switch for selection of<br />

fan speeds.<br />

Models with SYSTEM Switches<br />

<strong>TA157</strong> Models: In the OFF position, all outputs are OFF<br />

except with the Cycling Fan Option, the FAN output is<br />

dependent on external connections.<br />

HEAT POSITION: The thermostat controls the heat output.<br />

COOL POSITION: The thermostat controls the cool output.<br />

TB157 Models: Manual selection of ON and OFF. In the OFF<br />

position, all outputs are OFF except with the Cycling Fan<br />

Option, the FAN output is dependent on external<br />

connections. In the ON position the thermostat controls either<br />

the HEAT or COOL output w/o manual selection.<br />

Models with FAN Speed Switches<br />

Manual selection of HIGH, MEDIUM, or LOW fan speeds. In<br />

units with the Cycling Fan Option, the Fan operation<br />

(CYCLING vs CONTINUOUS) is determined by application<br />

connections.<br />

Printed in U.S.A. 1/07 © Copyright 2007 TAC All Rights Reserved. F-66048-1


Note: Specific models may vary in the number of connections<br />

available. Terminal designations remain consistant between<br />

models.<br />

Copyright 2007, TAC<br />

All brand names, trademarks and registered<br />

trademarks are the property of their respective<br />

owners. Information contained within this<br />

document is subject to change without notice.<br />

TAC<br />

1354 Clifford Avenue<br />

P.O. Box 2940<br />

Loves Park, IL 61132-2940<br />

F-66048-1<br />

www.tac.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!