TAC<br />
1354 Clifford Avenue<br />
P. O. Box 2940<br />
Loves Park, IL 61132-2940<br />
www.tac.com<br />
<strong>TA157</strong> Series<br />
TB157 Series<br />
3-<strong>Wire</strong> <strong>Floating</strong><strong>Thermostat</strong>/Controller<br />
Installation Instructions<br />
MOUNTING AND WIRING<br />
Caution: Disconnect power supply and ensure that all<br />
wiring complies with applicable codes and ordinances.<br />
1. The T157 Series thermostats install with two furnished<br />
mounting screws to a standard 4-11/16" x 2-1/8" square<br />
device box with a 2" x 4" adapter ring.<br />
2. For wall installations, mount the thermostat on an inside<br />
wall approximately 5 ft. above the floor. The location<br />
should provide circulation at average room temeprature.<br />
Avoid direct sunlight or sources of hot or cold air in the<br />
room or wall.<br />
3. To remove cover, first set knob to mid span and remove.<br />
Mount thermostat base assembly to the outlet box using<br />
the screws provided. Tighten the screws evenly but do<br />
not over tighten. Connect wires as shown in the<br />
appropriate wiring diagram for your thermostat style.<br />
4. To use a remote sensor on units with local sensing<br />
capability, remove jumper JP-1 to disable local sensing.<br />
Failure to remove JP-1 will cause improper operation of<br />
the thermostat.<br />
5. On units with cycling fan option, connect terminal 1<br />
(SWITCHED POWER) to 6 (FAN SUPPLY) for<br />
continuous fan operation, see Figure-1.<br />
6. Reinstall the cover assembly. Install cover locking screw<br />
if provided (see Figure-2). Reinstall the knob to complete<br />
installation.<br />
7. Checkout: After wiring and installation are complete,<br />
energize the system and check the operation. Adjust the<br />
thermostat as necessary to complete at least one cycle.<br />
Be sure the thermostat and all other equipment are<br />
functioning correctly.<br />
Operation<br />
<strong>TA157</strong> Models: Heating/Cooling thermostats requiring a<br />
switch for manual selection of HEAT-OFF-COOL. Some<br />
models have an integral Fan Switch for manual selection of<br />
fan speeds.<br />
TB157 Models: Auto-Change Over Heating, Cooling<br />
thermostat. Heat on to Cool on dead band is 5 F° nominal.<br />
Some models have an integral system switch for selection of<br />
fan speeds.<br />
Models with SYSTEM Switches<br />
<strong>TA157</strong> Models: In the OFF position, all outputs are OFF<br />
except with the Cycling Fan Option, the FAN output is<br />
dependent on external connections.<br />
HEAT POSITION: The thermostat controls the heat output.<br />
COOL POSITION: The thermostat controls the cool output.<br />
TB157 Models: Manual selection of ON and OFF. In the OFF<br />
position, all outputs are OFF except with the Cycling Fan<br />
Option, the FAN output is dependent on external<br />
connections. In the ON position the thermostat controls either<br />
the HEAT or COOL output w/o manual selection.<br />
Models with FAN Speed Switches<br />
Manual selection of HIGH, MEDIUM, or LOW fan speeds. In<br />
units with the Cycling Fan Option, the Fan operation<br />
(CYCLING vs CONTINUOUS) is determined by application<br />
connections.<br />
Printed in U.S.A. 1/07 © Copyright 2007 TAC All Rights Reserved. F-66048-1
Note: Specific models may vary in the number of connections<br />
available. Terminal designations remain consistant between<br />
models.<br />
Copyright 2007, TAC<br />
All brand names, trademarks and registered<br />
trademarks are the property of their respective<br />
owners. Information contained within this<br />
document is subject to change without notice.<br />
TAC<br />
1354 Clifford Avenue<br />
P.O. Box 2940<br />
Loves Park, IL 61132-2940<br />
F-66048-1<br />
www.tac.com