FDA Multi Systems - Installation<br />

B<br />

A<br />

C<br />

B<br />

A<br />

C<br />

D<br />

B<br />

A<br />

E<br />

F<br />

C<br />

G<br />

D<br />

Pipe Length Limitations<br />

Height Difference (all systems)<br />

Outdoor unit above max. height difference is 30m<br />

Outdoor unit below max. height difference is 15m<br />

Difference between indoor units max. height difference is 0.5m<br />

Twin Systems 7.2kW to 14.3kW<br />

A = main piping, B = branch piping, C = branch piping<br />

A + B + C Maximum is 50 metres<br />

Difference between B & C No more than 10 metres<br />

B Maximum is 20 metres<br />

C Maximum is 20 metres<br />

Triple Systems 14.3kW<br />

A + B + C + D Maximum is 50 metres<br />

Difference between B & C or C & D No more than 10 metres<br />

B Maximum is 20 metres<br />

C Maximum is 20 metres<br />

D Maximum is 20 metres<br />

Quad Systems 14.3kW<br />

Contact 3D for details<br />

Twin Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />

Outdoor unit to furthest indoor unit Maximum is 70 metres<br />

Difference between B & C no more than 10 metres<br />

B Maximum is 30 metres<br />

C Maximum is 30 metres<br />

Triple Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />

Outdoor unit to furthest indoor unit Maximum is 70 metres<br />

Difference between B & C & D no more than 10 metres<br />

B Maximum is 30 metres<br />

C Maximum is 30 metres<br />

D Maximum is 30 metres<br />

Quad Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />

Outdoor unit to furthest indoor unit Maximum is 70 metres<br />

Difference between B & C no more than 10 metres<br />

Difference between D, E, F, G no more than 10 metres<br />

B + D Maximum is 30 metres<br />

B + E Maximum is 30 metres<br />

C + F Maximum is 30 metres<br />

C + G Maximum is 30 metres<br />

Refrigerant Pipework must be installed within limitations detailed<br />

in the table below. Each system is supplied with the appropriate<br />

branch pipe. Pipe connections to the branch kits must be brazed<br />

and it is essential to use nitrogen purge while making the<br />

connections.<br />

Outdoor Units for Multi Systems<br />

FDCA<br />

801, 1001<br />

FDCA 301<br />

Outdoor Unit Dimensions & Weights<br />

FDCA<br />

401, 501, 601<br />

mm H W D Kg<br />

FDCA301 845 880 340 75<br />

FDCA401 1050 920 340 92<br />

FDCA501 1300 970 370 112<br />

FDCA601 1300 970 370 126<br />

FDCA801 1690 1350 720 210<br />

FDCA1001 1690 1350 720 225<br />

<strong>NEW</strong><br />

Large<br />

Capacities<br />

<strong>Mitsubishi</strong> <strong>Heavy</strong> <strong>Industries</strong> has made a giant leap forward in air conditioning<br />

and heat pump technology, with the development of high performance FD<br />

Multi Systems. These systems allow twin/triple/quad indoor units to be<br />

installed and connected to one outdoor unit. This provides a saving compared to the<br />

installation cost of several standard split systems.<br />

The new FDA Multi Systems are ideal for open plan areas. It is not advisable to install<br />

the connected indoor units in different rooms. Systems are supplied with the relevant<br />

branch pipe kits, and one controller per system.<br />

7-Day Programmable Timer - now included in standard controls specification.<br />

The CoP (Coefficient of Performance) has been dramatically increased, up to<br />

3.67 on some models. This means the system can deliver 3.67kW of heating, whilst<br />

consuming only 1.0kW of electrical power. This has been achieved by combining<br />

advanced <strong>Mitsubishi</strong> technology with R410A.<br />

air conditioning


FDA Multi Systems<br />

Ideal for open plan areas from 20m 2 to 6000m 2<br />

Cost effective solution for cooling and<br />

heating applications:<br />

• Much lower cost than individual split<br />

systems<br />

• Reduced number of outdoor units<br />

• Less power supplies required<br />

• Less refrigerant pipework entering the<br />

building<br />

• Cost savings of installation<br />

• Simple wiring and control<br />

arrangements<br />

• High performance R410A<br />

systems<br />

MIX-MATCH It is possible to have cassette<br />

units matched with wall, ceiling or ducted<br />

indoor units, as required.<br />

Indoor unit capacity indexes must be as<br />

those listed on opposite page.<br />

SIMPLE CONTROL All units on one system<br />

are connected to one controller, and will<br />

all operate in the same mode, i.e. cooling<br />

/ fan only / heating.<br />

It is not advisable to have indoor units<br />

installed in separate rooms.<br />

FDA Twin, Triple & Quad<br />

System 7.2kW to 16kW<br />

FDA Twin, Triple & Quad<br />

System 20.0kW to 28.0kW<br />

All new EHPAC range of indoor units have<br />

wired controllers, and compatible for FDA<br />

Multi application.<br />

Typical applications of FDA Multi Systems<br />

are:<br />

• Retail Stores<br />

• Convenience Stores<br />

• Petrol Station Shops<br />

• Open Plan Offices<br />

• Large Restaurants<br />

• Workshop areas<br />

• Nightclubs<br />

• Conference Rooms<br />

• Fitness Gyms<br />

<strong>NEW</strong><br />

Controller<br />

includes 7-day<br />

programmable<br />

timer<br />

FDA Multi Systems - Technical Data<br />

3Ph<br />

<strong>NEW</strong><br />

Single Phase<br />

7 & 10 kW<br />

systems<br />

Wiring Arrangement and Master/Slave settings for Multi Systems<br />

Power Source<br />

L1<br />

L2<br />

L3<br />

N<br />

Power Source<br />

1Ph<br />

L<br />

N<br />

Outdoor Unit<br />

2N<br />

2N<br />

0.75mm 2 to 1.5mm 2<br />

Outdoor Unit<br />

1<br />

2N<br />

3<br />

1<br />

3<br />

1<br />

3<br />

= Power Line<br />

= Neutral<br />

= Signal<br />

Wiring to<br />

Indoor Unit<br />

same as<br />

3PH above<br />

L N 3<br />

Master<br />

X Y Z<br />

X Y Z<br />

Wired Remote<br />

Controller<br />

Mains power is to the outdoor unit first.<br />

Check the correct power supply 1ph or 3ph is available on<br />

site. Check the correct outdoor units are ordered to suit<br />

1ph or 3ph.<br />

The EHPAC series now includes 1ph outdoor units for models<br />

301 (7.2kW/7.3kW) and 401 (10.0kW/11.2kW).<br />

0.75mm 2<br />

L N 3<br />

Slave ‘a’<br />

X Y Z<br />

L N 3<br />

Slave ‘b’<br />

X Y Z<br />

Indoor unit<br />

Signal wire 3<br />

is low voltage.<br />

Isolator not<br />

required.<br />

Factory setting: Master Master unit Slave ‘a’ Slave ‘b’ Slave ‘c’<br />

Indoor board SW5-1 OFF OFF ON ON<br />

address switches SW5-2 OFF ON OFF ON<br />

FDA Multi System<br />

Combinations R410A<br />

List Prices are for complete systems:<br />

Indoor units (+ facia panels), one<br />

remote controller, branch pipe kits<br />

and one outdoor unit.<br />

Cooling Heating Power Indoor<br />

Nom. kW Nom. kW Supply Ref.<br />

7.2 7.3 1 ph<br />

Twin<br />

20A<br />

7.2 7.3 3 ph<br />

Twin<br />

15A/ph<br />

10.0 11.2 1 ph<br />

Twin<br />

40A<br />

10.0 11.2 3 ph<br />

Twin<br />

20A/ph<br />

12.5 13.6 3 ph<br />

Twin<br />

20A/ph<br />

14.3 16.2 3 ph<br />

Twin<br />

20A/ph<br />

14.3 16.2 3 ph<br />

Triple<br />

20A/ph<br />

14.3 16.2 3 ph<br />

Quad<br />

20A/ph<br />

20.0 21.2 3 ph<br />

Twin<br />

32A/ph<br />

20.0 21.2 3 ph<br />

Triple<br />

32A/ph<br />

20.0 21.2 3 ph<br />

Quad<br />

32A/ph<br />

2x151 M2-FDTA151HEN M2-FDEA151HEN<br />

FDURA Units include<br />

M2-FDKA151HEN<br />

return air filter and<br />

condensate lift pump<br />

2x151 M2-FDTA151HES M2-FDEA151HES M2-FDKA151HES<br />

2x201 M2-FDTA201HEN M2-FDEA201HEN M2-FDURA201HEN M2-FDKA201HEN<br />

2x201 M2-FDTA201HES M2-FDEA201HES M2-FDURA201HES M2-FDKA201HES<br />

2x251 M2-FDTA251HES M2-FDEA251HES M2-FDURA251HES M2-FDKA251HES<br />

2x301 M2-FDTA301HES M2-FDEA301HES M2-FDURA301HES M2-FDKA301HES<br />

3x201 M3-FDTA201HES M3-FDEA201HES M3-FDURA201HES M3-FDKA201HES<br />

4x151 M4-FDTA151HES M4-FDEA151HES M4-FDKA151HES<br />

2x401 M2-FDTA401HES M2-FDEA401HES M2-FDURA401HES<br />

3x301 M3-FDTA301HES M3-FDEA301HES M3-FDURA301HES M3-FDKA301HES<br />

4x201 M4-FDTA201HES M4-FDEA201HES M4-FDURA201HES M4-FDKA201HES<br />

25.0 28.0 3 ph<br />

Twin 2x501 M2-FDTA501HES M2-FDEA501HES M2-FDURA501HES<br />

32A/ph<br />

25.0 28.0 3 ph 2x301<br />

+ M3-FDTA301-401HES M3-FDEA301-401HES M3-FDURA301-401HES<br />

Triple 32A/ph 1x401<br />

25.0 28.0 3 ph<br />

Quad<br />

32A/ph<br />

Multi Systems have all indoor units operating<br />

in the same mode (cool or heat) at the same<br />

time. They are ideal for open plan areas, such<br />

as large offices, retail shops and stores, fitness<br />

gyms, conference halls. They are not suitable<br />

for indoor units to be installed in separate rooms.<br />

Use the new KX INVERTER Multi Systems for<br />

these applications.<br />

FDTA FDEA FDURA FDKA<br />

4-Way Cassette Ceiling Mounted Ducted Wall mounted<br />

4x251 M4-FDTA251HES M4-FDEA251HES M4-FDUR251HES M4-FDKA251HES<br />

Cooling & Heating capacities listed above are<br />

for guidance, and are based on nominal ratings.<br />

Please refer to technical data for exact cooling<br />

and heating values.<br />

Alternative Combinations are available for<br />

20kW & 25kW Triple Systems. Details available<br />

on request.<br />

Mix-Match Indoor Units it is possible to<br />

connect Cassette / Wall / Ceiling / Ducted on<br />

the same Multi System, please contact 3D for<br />

a quote.