FDA Multi Systems - Installation<br />
B<br />
A<br />
C<br />
B<br />
A<br />
C<br />
D<br />
B<br />
A<br />
E<br />
F<br />
C<br />
G<br />
D<br />
Pipe Length Limitations<br />
Height Difference (all systems)<br />
Outdoor unit above max. height difference is 30m<br />
Outdoor unit below max. height difference is 15m<br />
Difference between indoor units max. height difference is 0.5m<br />
Twin Systems 7.2kW to 14.3kW<br />
A = main piping, B = branch piping, C = branch piping<br />
A + B + C Maximum is 50 metres<br />
Difference between B & C No more than 10 metres<br />
B Maximum is 20 metres<br />
C Maximum is 20 metres<br />
Triple Systems 14.3kW<br />
A + B + C + D Maximum is 50 metres<br />
Difference between B & C or C & D No more than 10 metres<br />
B Maximum is 20 metres<br />
C Maximum is 20 metres<br />
D Maximum is 20 metres<br />
Quad Systems 14.3kW<br />
Contact 3D for details<br />
Twin Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />
Outdoor unit to furthest indoor unit Maximum is 70 metres<br />
Difference between B & C no more than 10 metres<br />
B Maximum is 30 metres<br />
C Maximum is 30 metres<br />
Triple Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />
Outdoor unit to furthest indoor unit Maximum is 70 metres<br />
Difference between B & C & D no more than 10 metres<br />
B Maximum is 30 metres<br />
C Maximum is 30 metres<br />
D Maximum is 30 metres<br />
Quad Systems 20.0 & 25.0 kW – FDCA801 & 1001<br />
Outdoor unit to furthest indoor unit Maximum is 70 metres<br />
Difference between B & C no more than 10 metres<br />
Difference between D, E, F, G no more than 10 metres<br />
B + D Maximum is 30 metres<br />
B + E Maximum is 30 metres<br />
C + F Maximum is 30 metres<br />
C + G Maximum is 30 metres<br />
Refrigerant Pipework must be installed within limitations detailed<br />
in the table below. Each system is supplied with the appropriate<br />
branch pipe. Pipe connections to the branch kits must be brazed<br />
and it is essential to use nitrogen purge while making the<br />
connections.<br />
Outdoor Units for Multi Systems<br />
FDCA<br />
801, 1001<br />
FDCA 301<br />
Outdoor Unit Dimensions & Weights<br />
FDCA<br />
401, 501, 601<br />
mm H W D Kg<br />
FDCA301 845 880 340 75<br />
FDCA401 1050 920 340 92<br />
FDCA501 1300 970 370 112<br />
FDCA601 1300 970 370 126<br />
FDCA801 1690 1350 720 210<br />
FDCA1001 1690 1350 720 225<br />
<strong>NEW</strong><br />
Large<br />
Capacities<br />
<strong>Mitsubishi</strong> <strong>Heavy</strong> <strong>Industries</strong> has made a giant leap forward in air conditioning<br />
and heat pump technology, with the development of high performance FD<br />
Multi Systems. These systems allow twin/triple/quad indoor units to be<br />
installed and connected to one outdoor unit. This provides a saving compared to the<br />
installation cost of several standard split systems.<br />
The new FDA Multi Systems are ideal for open plan areas. It is not advisable to install<br />
the connected indoor units in different rooms. Systems are supplied with the relevant<br />
branch pipe kits, and one controller per system.<br />
7-Day Programmable Timer - now included in standard controls specification.<br />
The CoP (Coefficient of Performance) has been dramatically increased, up to<br />
3.67 on some models. This means the system can deliver 3.67kW of heating, whilst<br />
consuming only 1.0kW of electrical power. This has been achieved by combining<br />
advanced <strong>Mitsubishi</strong> technology with R410A.<br />
air conditioning
FDA Multi Systems<br />
Ideal for open plan areas from 20m 2 to 6000m 2<br />
Cost effective solution for cooling and<br />
heating applications:<br />
• Much lower cost than individual split<br />
systems<br />
• Reduced number of outdoor units<br />
• Less power supplies required<br />
• Less refrigerant pipework entering the<br />
building<br />
• Cost savings of installation<br />
• Simple wiring and control<br />
arrangements<br />
• High performance R410A<br />
systems<br />
MIX-MATCH It is possible to have cassette<br />
units matched with wall, ceiling or ducted<br />
indoor units, as required.<br />
Indoor unit capacity indexes must be as<br />
those listed on opposite page.<br />
SIMPLE CONTROL All units on one system<br />
are connected to one controller, and will<br />
all operate in the same mode, i.e. cooling<br />
/ fan only / heating.<br />
It is not advisable to have indoor units<br />
installed in separate rooms.<br />
FDA Twin, Triple & Quad<br />
System 7.2kW to 16kW<br />
FDA Twin, Triple & Quad<br />
System 20.0kW to 28.0kW<br />
All new EHPAC range of indoor units have<br />
wired controllers, and compatible for FDA<br />
Multi application.<br />
Typical applications of FDA Multi Systems<br />
are:<br />
• Retail Stores<br />
• Convenience Stores<br />
• Petrol Station Shops<br />
• Open Plan Offices<br />
• Large Restaurants<br />
• Workshop areas<br />
• Nightclubs<br />
• Conference Rooms<br />
• Fitness Gyms<br />
<strong>NEW</strong><br />
Controller<br />
includes 7-day<br />
programmable<br />
timer<br />
FDA Multi Systems - Technical Data<br />
3Ph<br />
<strong>NEW</strong><br />
Single Phase<br />
7 & 10 kW<br />
systems<br />
Wiring Arrangement and Master/Slave settings for Multi Systems<br />
Power Source<br />
L1<br />
L2<br />
L3<br />
N<br />
Power Source<br />
1Ph<br />
L<br />
N<br />
Outdoor Unit<br />
2N<br />
2N<br />
0.75mm 2 to 1.5mm 2<br />
Outdoor Unit<br />
1<br />
2N<br />
3<br />
1<br />
3<br />
1<br />
3<br />
= Power Line<br />
= Neutral<br />
= Signal<br />
Wiring to<br />
Indoor Unit<br />
same as<br />
3PH above<br />
L N 3<br />
Master<br />
X Y Z<br />
X Y Z<br />
Wired Remote<br />
Controller<br />
Mains power is to the outdoor unit first.<br />
Check the correct power supply 1ph or 3ph is available on<br />
site. Check the correct outdoor units are ordered to suit<br />
1ph or 3ph.<br />
The EHPAC series now includes 1ph outdoor units for models<br />
301 (7.2kW/7.3kW) and 401 (10.0kW/11.2kW).<br />
0.75mm 2<br />
L N 3<br />
Slave ‘a’<br />
X Y Z<br />
L N 3<br />
Slave ‘b’<br />
X Y Z<br />
Indoor unit<br />
Signal wire 3<br />
is low voltage.<br />
Isolator not<br />
required.<br />
Factory setting: Master Master unit Slave ‘a’ Slave ‘b’ Slave ‘c’<br />
Indoor board SW5-1 OFF OFF ON ON<br />
address switches SW5-2 OFF ON OFF ON<br />
FDA Multi System<br />
Combinations R410A<br />
List Prices are for complete systems:<br />
Indoor units (+ facia panels), one<br />
remote controller, branch pipe kits<br />
and one outdoor unit.<br />
Cooling Heating Power Indoor<br />
Nom. kW Nom. kW Supply Ref.<br />
7.2 7.3 1 ph<br />
Twin<br />
20A<br />
7.2 7.3 3 ph<br />
Twin<br />
15A/ph<br />
10.0 11.2 1 ph<br />
Twin<br />
40A<br />
10.0 11.2 3 ph<br />
Twin<br />
20A/ph<br />
12.5 13.6 3 ph<br />
Twin<br />
20A/ph<br />
14.3 16.2 3 ph<br />
Twin<br />
20A/ph<br />
14.3 16.2 3 ph<br />
Triple<br />
20A/ph<br />
14.3 16.2 3 ph<br />
Quad<br />
20A/ph<br />
20.0 21.2 3 ph<br />
Twin<br />
32A/ph<br />
20.0 21.2 3 ph<br />
Triple<br />
32A/ph<br />
20.0 21.2 3 ph<br />
Quad<br />
32A/ph<br />
2x151 M2-FDTA151HEN M2-FDEA151HEN<br />
FDURA Units include<br />
M2-FDKA151HEN<br />
return air filter and<br />
condensate lift pump<br />
2x151 M2-FDTA151HES M2-FDEA151HES M2-FDKA151HES<br />
2x201 M2-FDTA201HEN M2-FDEA201HEN M2-FDURA201HEN M2-FDKA201HEN<br />
2x201 M2-FDTA201HES M2-FDEA201HES M2-FDURA201HES M2-FDKA201HES<br />
2x251 M2-FDTA251HES M2-FDEA251HES M2-FDURA251HES M2-FDKA251HES<br />
2x301 M2-FDTA301HES M2-FDEA301HES M2-FDURA301HES M2-FDKA301HES<br />
3x201 M3-FDTA201HES M3-FDEA201HES M3-FDURA201HES M3-FDKA201HES<br />
4x151 M4-FDTA151HES M4-FDEA151HES M4-FDKA151HES<br />
2x401 M2-FDTA401HES M2-FDEA401HES M2-FDURA401HES<br />
3x301 M3-FDTA301HES M3-FDEA301HES M3-FDURA301HES M3-FDKA301HES<br />
4x201 M4-FDTA201HES M4-FDEA201HES M4-FDURA201HES M4-FDKA201HES<br />
25.0 28.0 3 ph<br />
Twin 2x501 M2-FDTA501HES M2-FDEA501HES M2-FDURA501HES<br />
32A/ph<br />
25.0 28.0 3 ph 2x301<br />
+ M3-FDTA301-401HES M3-FDEA301-401HES M3-FDURA301-401HES<br />
Triple 32A/ph 1x401<br />
25.0 28.0 3 ph<br />
Quad<br />
32A/ph<br />
Multi Systems have all indoor units operating<br />
in the same mode (cool or heat) at the same<br />
time. They are ideal for open plan areas, such<br />
as large offices, retail shops and stores, fitness<br />
gyms, conference halls. They are not suitable<br />
for indoor units to be installed in separate rooms.<br />
Use the new KX INVERTER Multi Systems for<br />
these applications.<br />
FDTA FDEA FDURA FDKA<br />
4-Way Cassette Ceiling Mounted Ducted Wall mounted<br />
4x251 M4-FDTA251HES M4-FDEA251HES M4-FDUR251HES M4-FDKA251HES<br />
Cooling & Heating capacities listed above are<br />
for guidance, and are based on nominal ratings.<br />
Please refer to technical data for exact cooling<br />
and heating values.<br />
Alternative Combinations are available for<br />
20kW & 25kW Triple Systems. Details available<br />
on request.<br />
Mix-Match Indoor Units it is possible to<br />
connect Cassette / Wall / Ceiling / Ducted on<br />
the same Multi System, please contact 3D for<br />
a quote.