The Figure 4 shows the variati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> voltage unbalance<br />
factor (VUF) at different substati<strong>on</strong>s over a 24-hour<br />
period using load flow analysis that synthesises the<br />
actual network operati<strong>on</strong>. This was d<strong>on</strong>e by applying<br />
loads (c<strong>on</strong>stant power) that are similar to what exists,<br />
however applied as balanced loads. It is clear that the<br />
asymmetry <str<strong>on</strong>g>of</str<strong>on</strong>g> the network (due to untransposed lines)<br />
itself produces excessive levels <str<strong>on</strong>g>of</str<strong>on</strong>g> voltage unbalance at<br />
G, H and I load buses and c<strong>on</strong>siderable levels at D and<br />
F as shown in Table 1. The VUF levels caused <strong>on</strong>ly by<br />
system asymmetry at G, H and I down stream load buses<br />
are out <str<strong>on</strong>g>of</str<strong>on</strong>g> the the code requirements, and the situati<strong>on</strong><br />
will be aggravated when the load unbalance comes into<br />
account, as depicted by the measured VUF values given<br />
in Table 1.<br />
Figure 5 illustrates the variati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> VUF (at receiving<br />
end) with respect to line current (as a percentage to<br />
line’s rated current) for individual lines under balanced<br />
supply (<str<strong>on</strong>g>66kV</str<strong>on</strong>g>) and loading (c<strong>on</strong>stant power loads with<br />
0.9 power factor) c<strong>on</strong>diti<strong>on</strong>s. It is evident from Figure 5<br />
that some lines (F-C, H-I, A-F, A-D and E-D) behave<br />
adversely in relati<strong>on</strong> to voltage unbalance when they are<br />
heavily loaded. Am<strong>on</strong>g these F-C, A-F, A-D and E-D are<br />
significantly loaded under operating c<strong>on</strong>diti<strong>on</strong>s and thus<br />
can have a significant impact <strong>on</strong> the problem (Table 2).<br />
Figure 5: Variati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> VUF (%) with line current (%)<br />
Table 2: Maximum loading level and respective<br />
VUF (at recieving end) for individual lines<br />
Line Maximum loading VUF (%)<br />
level (%)<br />
F-C 26 1<br />
A-F 30.5 0.6<br />
A-D 39 0.5<br />
E-D 56 0.75<br />
6. CONCLUSIONS AND FUTURE DIREC-<br />
TIONS<br />
<str<strong>on</strong>g>of</str<strong>on</strong>g> the code requirements during peak demand periods,<br />
even when the loads are completely balanced. Analysis <str<strong>on</strong>g>of</str<strong>on</strong>g><br />
individual line behaviour enabled identificati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> critical<br />
<str<strong>on</strong>g>transmissi<strong>on</strong></str<strong>on</strong>g> lines, which make significant c<strong>on</strong>tributi<strong>on</strong><br />
to the problem. Hence, untransposed lines even at lower<br />
<str<strong>on</strong>g>transmissi<strong>on</strong></str<strong>on</strong>g> voltage levels such as <str<strong>on</strong>g>66kV</str<strong>on</strong>g>, are investigated<br />
as a primary cause <str<strong>on</strong>g>of</str<strong>on</strong>g> voltage unbalance.<br />
In relati<strong>on</strong> to unbalanced load flow analysis it is crucial<br />
that advanced load modelling be undertaken. This is<br />
due to that fact that loads such as inducti<strong>on</strong> machines<br />
behave differently when subjected to unbalanced supply<br />
voltages. This is in c<strong>on</strong>trary to the behaviour exhibited<br />
by static loads such as resistive loads.<br />
REFERENCES<br />
[1] System Standards, Nati<strong>on</strong>al Electicity Code<br />
Australia, Versi<strong>on</strong> 1.0 - Amendment 9.0,<br />
S5.1a.7, October 2004.<br />
[2] Electricity Distributi<strong>on</strong> Code, Victoria, January<br />
2002.<br />
[3] W. Xu, H. W. Dommel and J. R. Marti, ‘A<br />
Generalised Three-phase Power Flow Method<br />
for the Initialisati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> EMTP Simulati<strong>on</strong>s’, Int.<br />
C<strong>on</strong>f. <strong>on</strong> Power System Technology, POWER-<br />
CON ’98, Vol. 2, pp. 875-879, 18-21 Aug. 1998.<br />
[4] Xiao-Ping Zhang and Heng Chen, ‘Sequence-<br />
Decoupled Newt<strong>on</strong>-Raphs<strong>on</strong> Three-phase Load<br />
Flow’, Proc. IEEE Regi<strong>on</strong> 10 C<strong>on</strong>f. <strong>on</strong> Computer,<br />
Communicati<strong>on</strong>, C<strong>on</strong>trol and Power Engineering,<br />
TENCON ’93, Vol. 5, Issue 0,<br />
Part 50000, pp. 394 - 397, 19-21 Oct. 1993.<br />
[5] M. A. Laught<strong>on</strong>, ‘Analysis <str<strong>on</strong>g>of</str<strong>on</strong>g> Unbalanced<br />
Poly-phase Networks by the Method <str<strong>on</strong>g>of</str<strong>on</strong>g> Phase<br />
Co-ordinates’, IEE Proc., Vol. 115, No. 8,<br />
Aug. 1968.<br />
[6] M. Abdel-Akher, K. M. Nor and<br />
A. H. A. Rashid, ‘Improved Three-phase Power<br />
Flow Methods using Sequence Comp<strong>on</strong>ents’,<br />
IEEE Trans. <strong>on</strong> Power Systems, Vol. 20,<br />
Issue 3, pp. 1389 - 1397, Aug. 2005.<br />
[7] W. Xu, J. R. Marti and H. W. Dommel, ‘A<br />
Multiphase Harm<strong>on</strong>ic Load Flow Soluti<strong>on</strong> Technique’,<br />
IEEE Trans. <strong>on</strong> Power Systems, Vol. 6,<br />
Issue 1, pp. 174 - 182, Feb. 1991.<br />
[8] Prabha Kundur, ‘Power System Stability and<br />
C<strong>on</strong>trol’, McGraw-Hill, Inc., pp. 271-274, 1993.<br />
[9] Paul M. Anders<strong>on</strong>, ‘Analysis <str<strong>on</strong>g>of</str<strong>on</strong>g> Faulted Power<br />
Systems’, A John Wiley & S<strong>on</strong>s, Inc., pp. 71-<br />
83, 1995.<br />
Investigati<strong>on</strong>s were carried out to examine the impact <str<strong>on</strong>g>of</str<strong>on</strong>g><br />
<str<strong>on</strong>g>66kV</str<strong>on</strong>g> untransposed <str<strong>on</strong>g>transmissi<strong>on</strong></str<strong>on</strong>g> lines <strong>on</strong> voltage unbalance.<br />
An Interc<strong>on</strong>nected <str<strong>on</strong>g>66kV</str<strong>on</strong>g> sub-<str<strong>on</strong>g>transmissi<strong>on</strong></str<strong>on</strong>g> network<br />
and its individual lines were analysed under balanced<br />
loading c<strong>on</strong>diti<strong>on</strong>s, employing a three-phase power flow<br />
program. It is seen that the level <str<strong>on</strong>g>of</str<strong>on</strong>g> voltage unbalance at<br />
some load substati<strong>on</strong>s <str<strong>on</strong>g>of</str<strong>on</strong>g> the interc<strong>on</strong>nected system is out