Gaps Observed at the Top <strong>of</strong> the Windings.<br />

Figure 17<br />

The core dimensions were measured after the windings were removed and it was reported that there was no<br />

detectable movement in the core limbs.<br />

REPAIRS<br />

The objective <strong>of</strong> the repairs from the perspective <strong>of</strong> the utility was to return the transformer to a new condition. The<br />

following list notes the major repairs made to the transformer:<br />

<br />

<br />

<br />

Replacement <strong>of</strong> top core yoke laminations that were damaged. There was damage due to shifting <strong>of</strong> the<br />

yoke steel that caused buckling and permanent deformation <strong>of</strong> some laminations. A loose or shifted block<br />

near the core came in contact with the steel and caused damage. Handling <strong>of</strong> the laminations also created<br />

some damage, especially at the miter joints.<br />

The main blocks between the clamping rings and the core clamping frames were twisted and several<br />

showed separation at the glue lines between the pieces making up the blocks. Typically, high density<br />

laminated wood material used in transformers has a shiny platen surface which prevents adhesives from<br />

bonding properly to the surface. To help with adhesion, the blocks were separated and scuffed to remove<br />

the shiny surfaces to allow proper bonding. Two (2) wooden dowel pins were added to each block through<br />

all layers to prevent the pieces <strong>of</strong> the blocks from shifting and pivoting. The blocks were aligned properly<br />

as they were reassembled between the frames and clamping rings.<br />

The top coil blocks were realigned and glued in place. The blocks at the top <strong>of</strong> individual coils were placed<br />

back on their radial spacer columns, aligned properly and glued in place.<br />