T24-V42(-V02)...+T24-MP<br />
Application Description<br />
Application No. 30 - Cool with 1-stage electric reheat<br />
- VAV single duct application<br />
I<br />
The room temperature aims as the demand related<br />
control value of the connected VAV units. The variable<br />
volumetric air flow range V’min...V’max:<br />
T24-MP<br />
-V’min - to the hygienic change or minimum fresh air<br />
-V’max - to the maximum cooling demand<br />
VAV Compact Control Module<br />
*Max for 2 VAV box<br />
connected together<br />
Functional diagram<br />
%<br />
BACnet / LonWorks<br />
Options<br />
At heating conditions the electric reheat gets<br />
controlled via the digital output - DO1<br />
100<br />
El. 1<br />
Cooling<br />
Vmax<br />
- AI External temp. sensor, NTC 10k@25°C sensor<br />
- DI Remote setpoint shift, e.g. Occupancy sensor (NO)<br />
Open - Normal mode, Close - Economy mode<br />
1K<br />
#30:<br />
Cool + 1-stage El. reheat<br />
DB<br />
W<br />
Vmin<br />
T [ 0 C]<br />
Heating mode<br />
reheat<br />
Econ mode<br />
<strong>Operation</strong>s - MMI<br />
- T24-MP with user interface, LCD display<br />
- TG-R10000 without user interface, No display<br />
Application No. 40 - Cool with 2-stages electric reheat<br />
- VAV single duct application<br />
I, II<br />
The room temperature aims as the demand related<br />
control value of the connected VAV units. The variable<br />
volumetric air flow range V’min...V’max:<br />
T24-MP<br />
-V’min - to the hygienic change or minimum fresh air<br />
-V’max - to the maximum cooling demand<br />
VAV Compact Control Module<br />
*Max for 2 VAV box<br />
connected together<br />
BACnet / LonWorks<br />
At heating conditions the 2-steps electric reheat<br />
gets controlled via two digital outputs - DO1 & DO2<br />
Functional diagram<br />
%<br />
Options<br />
100<br />
El. 2<br />
Cooling<br />
Vmax<br />
- AI External temp. sensor, NTC 10k@25°C sensor<br />
El. 1<br />
- DI Remote setpoint shift, e.g. Occupancy sensor (NO)<br />
Open - Normal mode, Close - Economy mode<br />
1K 1K<br />
#40:<br />
Cool + 2-stages El. reheat<br />
DB<br />
W<br />
Vmin<br />
T [ 0 C]<br />
Heating mode<br />
reheat<br />
Econ mode<br />
<strong>Operation</strong>s - MMI<br />
- T24-MP with user interface, LCD display<br />
- TG-R10000 without user interface, No display<br />
22