T24-V42(-V02)...+T24-MP<br />
Application Description<br />
Application No. 42 - Cool with 2-stages electric reheat & series fan<br />
- VAV single duct application<br />
I, II<br />
The room temperature aims as the demand related<br />
control value of the connected VAV units. The variable<br />
volumetric air flow range V’min...V’max:<br />
-V’min - to the hygienic change or minimum fresh air<br />
T24-MP<br />
-V’max - to the maximum cooling demand<br />
VAV Compact Control Module<br />
*Max for 2 VAV box<br />
connected together<br />
Functional diagram<br />
BACnet / LonWorks<br />
Under heating conditions the 2-steps electric reheat<br />
& series fan gets controlled via three digital outputs -<br />
DO1, DO2 & DO3<br />
* During the normal operation, the series fan will<br />
always on.<br />
%<br />
Options<br />
100<br />
El. 2<br />
Cooling<br />
Vmax<br />
- AI External temp. sensor, NTC 10k@25°C sensor<br />
El. 1<br />
- DI Remote setpoint shift, e.g. Occupancy sensor (NO)<br />
Open - Normal mode, Close - Economy mode<br />
1K 1K<br />
#42:<br />
Cool + 2-stages El. reheat<br />
DB<br />
W<br />
Vmin<br />
T [ 0 C]<br />
Heating mode<br />
reheat<br />
Econ mode<br />
<strong>Operation</strong>s - MMI<br />
- T24-MP with user interface, LCD display<br />
- TG-R10000 without user interface, No display<br />
Application No. 52 - Cool with 3-point reheat & series fan<br />
- VAV single duct application<br />
The room temperature aims as the demand related<br />
control value of the connected VAV units. The variable<br />
volumetric air flow range V’min...V’max:<br />
-V’min - to the hygienic change or minimum fresh air<br />
T24-MP<br />
-V’max - to the maximum cooling demand<br />
VAV Compact Control Module<br />
*Max for 2 VAV box<br />
connected together<br />
Functional diagram<br />
BACnet / LonWorks<br />
Under heating conditions the 3 point reheat valve &<br />
series fan gets controlled via three digital outputs -<br />
DO1, DO2 & DO3<br />
* During the normal operation, the series fan will<br />
always on.<br />
%<br />
Options<br />
100<br />
Heating<br />
Cooling<br />
Vmax<br />
- AI External temp. sensor, NTC 10k@25°C sensor<br />
- DI Remote setpoint shift, e.g. Occupancy sensor (NO)<br />
Open - Normal mode, Close - Economy mode<br />
Vmin<br />
T [ 0 C]<br />
<strong>Operation</strong>s - MMI<br />
#52:<br />
Cool + 3-point reheat<br />
DB<br />
W<br />
3-point reheat<br />
Econ mode<br />
- T24-MP with user interface, LCD display<br />
- TG-R10000 without user interface, No display<br />
28