T24-V42(-V02)...+T24-MP<br />
<strong>Operation</strong> and setting<br />
Controller operation<br />
The T24-V42(-V02)... room control module offers the advantages of network control via the high performance network protocol.<br />
This controller features clear LED’s indication, analogue input, digital input, analogue output, 3 x AC 24V digital outputs. MP-Bus<br />
interface for connection to the <strong>Belimo</strong> VAV Compact and optional T24-MP room unit or TG-R10000 room sensor. Suitable for new<br />
or existing VAV system installations.<br />
Functions of T24-V42(-V02)LON and wiring diagram<br />
External<br />
sensor (AI)<br />
NTC 10k<br />
Analogue<br />
output (AO)<br />
2-10Vdc<br />
AC 24V<br />
Power<br />
supply<br />
MP-Bus (MP1~3)<br />
LonWorks<br />
(TG-R10000)<br />
External<br />
sensor<br />
NTC 10k<br />
*Power<br />
supply<br />
M<br />
Modulating<br />
reheat valve<br />
T24-MP<br />
1 2 5<br />
1A fuse<br />
AC 24V<br />
~ <br />
1 A<br />
1 2 3 5<br />
1 2 3 5<br />
VAV Compact<br />
VAV Compact<br />
LonWorks®<br />
AI<br />
Com<br />
AO<br />
Com<br />
24V<br />
Com MP1 MP2 MP3<br />
ac<br />
LON LON<br />
A B<br />
DI<br />
Com<br />
DO1 Com DO2 Com DO3 Com<br />
1 2 3<br />
AC 24V<br />
Power DO1 DO2 DO3 Signal<br />
MP<br />
BUS <br />
Occupancy<br />
sensor<br />
M<br />
*Relay supplied<br />
by others<br />
3-point<br />
reheat<br />
valve<br />
Caution: live voltage<br />
Digital input<br />
(DI)<br />
Electrical heaters,<br />
parallel/series fan<br />
(3 x DO)<br />
System<br />
reset<br />
LonWorks<br />
service pin<br />
xxx<br />
Heater<br />
1<br />
Only available for T24-V42LON<br />
Heater<br />
2<br />
Fan<br />
System<br />
reset<br />
LonWorks<br />
service pin<br />
Functions of T24-V42(-V02)BAC and wiring diagram<br />
Electrical heaters,<br />
parallel/series fan<br />
(3 x DO)<br />
AC 24V<br />
Power<br />
supply<br />
MP-Bus (MP1~3)<br />
M<br />
Heater<br />
1<br />
Heater<br />
2<br />
Fan<br />
1A fuse<br />
AC 24V<br />
~ <br />
1 A<br />
1 2 3 5<br />
3-point<br />
reheat<br />
valve<br />
Com DO1 Com DO2 Com<br />
DO3<br />
*Relay<br />
supplied<br />
by others<br />
AC 24V<br />
Caution: live voltage<br />
1 2 5<br />
1 2 3 5<br />
VAV Compact<br />
24V<br />
Com MP1 MP2 MP3<br />
ac<br />
VAV Compact<br />
1 2 3<br />
AO Com AI<br />
Com DI Com<br />
D+<br />
D-<br />
Com SHLD<br />
Subject to technical change V2.0 01042010<br />
Software<br />
reflash<br />
System<br />
reset<br />
Power DO1 DO2 DO3 Signal<br />
Analogue<br />
output (AO)<br />
2-10Vdc<br />
External<br />
sensor (AI)<br />
NTC 10k<br />
Input & output assignment<br />
Inputs<br />
- AI External temp. sensor TG-R10000 *<br />
- DI Remote setpoint shift, e.g. Occupancy sensor *<br />
Open - Normal mode, Close - Economy mode<br />
MP<br />
Digital input<br />
(DI)<br />
BUS <br />
BACnet<br />
xxx<br />
M<br />
*Power<br />
supply<br />
* Optional Outputs<br />
External<br />
sensor<br />
NTC 10k<br />
(TG-R10000)<br />
Only available for T24-V42BAC<br />
Occupancy<br />
sensor<br />
To<br />
From<br />
MS/TP<br />
Next Device Last Device<br />
BACnet®<br />
System<br />
reset<br />
- AO Modulating reheat control DC 2...10V<br />
- DO1 Heating output I AC 24V ON/OFF<br />
- DO2 Heating output II AC 24V ON/OFF<br />
- DO3 Parallel or series fan output AC 24V ON/OFF<br />
31