AC MOTORS<br />
explosion-proof<br />
for hazardous locations<br />
EXPLOSION-PROOF MOTORS<br />
THREE PHASE • C FACE<br />
Underwriters Laboratories<br />
and Canadian Standards<br />
Association Listed<br />
General Specifications:<br />
These explosion-proof motors<br />
are designed and approved<br />
for application in hazardous<br />
environments having certain<br />
explosive gases or materials<br />
present.<br />
Features:<br />
Rugged mechanical construction meeting all requirements<br />
for safety. UL and CSA listed.<br />
Double shielded, pre-lubricated ball bearings are standard.<br />
All motors have inherent automatic overload protection.<br />
NEMA 1.0 Service Factor except as noted.<br />
Explosion-proof conduit box included at no extra cost.<br />
Division I areas are environments where a hazard is present<br />
continuously or would be subject to fire or explosion if the<br />
hazard was present as a result of an accident or un<strong>com</strong>mon<br />
occurrence.<br />
Division II areas are environments where the threat of fire or<br />
explosion is not normally present and not likely to result in<br />
the event of an abnormal occurrence.<br />
Application Notes:<br />
These motors must be applied in accordance with the<br />
National Electrical Code, Article #500. A partial listing of<br />
explosive agents is noted below. Consult NFPA Publication<br />
497M for a <strong>com</strong>plete listing. Please note subheads above<br />
each column for qualifications of <strong>LEESON</strong> motors.<br />
NOTE: No <strong>LEESON</strong> motors are listed for Class I, Group<br />
A or B.<br />
Class I<br />
Group A: Acetylene<br />
Group B: Butadiene, ethylene<br />
oxide, hydrogen, propylene<br />
oxide, manufactured gases<br />
containing more than 30%<br />
hydrogen by volume.<br />
Group C: Acetaldehyde,<br />
cyclopropane, diethyl ether,<br />
ethylene.<br />
Group D: Acetone, acrylonitrile, ammonia, benzene,<br />
butane, ethanol, ethylene dichloride, gasoline, hexane,<br />
isoprene, methane (natural gas), methanol, naphtha,<br />
propane, propylene, styrene, toluene, vinyl acetate, vinyl<br />
chloride, xylene.<br />
Class II<br />
Group E: Aluminum, magnesium and other metal dusts with<br />
similar characteristics.<br />
Group F: Carbon black, coke or coal dust.<br />
Group G: Flour, starch or grain dust.<br />
EXCEPT AS NOTED, STEEL FRAME<br />
EXPLOSION-PROOF MOTORS ARE NOT<br />
INVERTER-RATED AND MUST NOT<br />
BE USED WITH AN INVERTER<br />
THREE Phase • C Face WITH Base<br />
division i, division ii, Class I, Groups C & D —<br />
Class II, Groups F & G • W/CONDUIT BOX<br />
SYN App. Over- F.L. % “C”<br />
RPM NEMA <strong>Catalog</strong> Wgt. load Amps F.L. Dim.<br />
HP 60 Hz Frame Number (lbs.) Voltage Prot. 230V Eff. (Inches)<br />
1/3 3600 56C 114625.00sl 33 208-230/460 Auto. 1.2 77.0 11.97<br />
1800 56C 114626.00sl 38 208-230/460 Auto. 1.3 76.0 11.97<br />
1/2 3600 56C 114627.00lH 35 208-230/460 Auto. 1.6 82.5 12.47<br />
1800 56C 114628.00sl 35 208-230/460 Auto. 1.7 75.0 12.47<br />
1800 56C 116190.00v 34 208-230/460 T-Stat 2.4 68.0 13.44<br />
3/4 3600 56C 114629.00 33 208-230/460 Auto. 2.4 75.5 13.44<br />
1800 56C 114630.00 42 208-230/460 Auto. 2.6 75.0 13.94<br />
1800 56C 116191.00v 38 208-230/460 T-Stat 3.0 75.5 13.44<br />
1 3600 56C 114631.00 34 208-230/460 Auto. 3.2 77.0 13.44<br />
1800 56C 114632.00 48 208-230/460 Auto. 3.2 85.5 14.50<br />
1800 143TC 121919.00v 44 208-230/460 T-Stat 3.0 82.5 14.50<br />
1 1 ⁄2 3600 56C 114633.00 42 208-230/460 Auto. 4.2 81.5 13.94<br />
1800 56C 114634.00 45 208-230/460 Auto. 4.4 80.0 15.94<br />
1800 145TC 121920.00v 58 208-230/460 T-Stat 4.8 86.5 16.00<br />
2 3600 56C 114635.00 51 208-230/460 Auto. 5.6 78.8 13.94<br />
1800 145TC 121921.00 w 62 208-230/460 Auto. 5.8 86.5 15.02<br />
1800 145TC 121922.00v w 66 208-230/460 T-Stat 5.8 86.5 16.50<br />
3 3600 56C 114636.00® 62 208-230/460 Auto. 7.6 84.0 15.44<br />
® <strong>Catalog</strong> #114636 is approved for Class I, Group C & D – Class II, Group F service only.<br />
s These motors are satisfactory for operation on 50 Hz power supply at full rated horsepower.<br />
l These motors are totally enclosed, non-ventilated — Others are fan cooled.<br />
H These motors have 1.15 Service Factors.<br />
v These motors are inverter-rated and suitable for use with an inverter. Others are not!<br />
w Premium efficiency WATTSAVERe® <strong>Motor</strong>s. See page 19 for details.<br />
C Face WITH RIGID BASE • Three Phase<br />
ALL Cast Iron CONSTRUCTION<br />
division i, division ii, Class I, Group D — Class II, Groups F & G<br />
with conduit Box AND NORMALLY-CLOSED THERMOSTATS<br />
SYN App. F.L. % “C”<br />
RPM NEMA <strong>Catalog</strong> Wgt. Amps F.L. Dim.<br />
HP 60 Hz Frame Number (lbs.) Voltage 460 V. Eff. (Inches)<br />
3 3600 182TC 825125.00H 95 230/460 7.6 86.5 17.62<br />
1800 182TC 825126.00H 96 230/460 7.8 89.5 17.60<br />
5 3600 184TC 825127.00H 130 230/460 12.0 88.5 17.62<br />
1800 184TC 825071.00H 130 230/460 12.8 89.5 17.60<br />
7 1 ⁄2 3600 213TC 825072.00H 143 230/460 18.0 89.5 20.68<br />
1800 213TC 825073.00H 143 230/460 18.6 91.7 20.68<br />
10 3600 215TC 825074.00H 160 230/460 23.0 90.2 20.68<br />
1800 215TC 825075.00H 160 230/460 25.0 91.7 20.68<br />
15 3600 254TC 825076.00H 245 230/460 34.6 91.0 24.02<br />
1800 254TC 825077.00H h 246 230/460 36.0 92.4 24.02<br />
20 3600 256TC 825078.00H h 271 230/460 46.0 91.0 25.77<br />
1800 256TC 825079.00H h 273 230/460 49.0 93.0 25.77<br />
25 3600 284TSC 825080.00H h 373 230/460 56.8 91.7 24.44<br />
1800 284TC 825081.00H h A 375 230/460 59.0 93.6 26.80<br />
30 1800 286TC 825082.00H h A 395 230/460 70.0 93.6 28.30<br />
40 1800 324TC 825083.00H h A 563 230/460 92.0 94.1 29.37<br />
h<br />
50 1800 326TC 825084.00 A 585 230/460 117.0 94.5 30.87<br />
H These motors have 1.15 Service Factors.<br />
h Explosion-proof motors are Class I, Groups C & D—Class II, Groups F & G.<br />
A Subject to Availability.<br />
122<br />
SHADED FRAME INDICATES CAST IRON CONSTRUCTION<br />
WATTSAVERe <strong>Motor</strong>s Meet NEMA MG1 part 30 & 31.<br />
Specifications are subject to change without notice