1.1 Product Description<br />

The <strong>PD</strong>/<strong>CTX</strong> TM is an intelligent current transmitter. It is used in<br />

conjunction with a pulse density signalling, <strong>PD</strong>S(IO), logic output<br />

from a series 2000 controller, to control a time proportioned Solid State<br />

Relay (SSR) or Contactor. The two logic wires which operate the SSR<br />

also carry load current and status information back to the controller.<br />

This is referred to as ‘<strong>PD</strong>S Mode 2’ operation. Mode 2 provides:<br />

1. Display of true RMS load current<br />

2. High and low current alarm<br />

3. SSR short circuit<br />

4. Heater failure<br />

An alternative capability, referred to as ‘<strong>PD</strong>S Mode 5’, allows the<br />

<strong>PD</strong>/<strong>CTX</strong> to monitor relay or triac output controllers. The <strong>PD</strong>/<strong>CTX</strong><br />

uses the logic inputs of a series 2000 controller to transfer the data to<br />

the controller. This version is used with external mechanical or<br />

mercury contactors and line voltage SSRs. Mode 5 provides the same<br />

features as mode 2 but it can also monitor the <strong>PD</strong>/<strong>CTX</strong> for open or<br />

short circuit conditions and initiate an alarm in the controller.<br />

The <strong>PD</strong>/<strong>CTX</strong> must be supplied for either mode 2 or mode 5 operation.<br />

It is not field alterable. Before connecting the <strong>PD</strong>/<strong>CTX</strong> to the controller<br />

check the product type against the order code given in section 1.9.<br />

1.2 Compatible SSRs<br />

The SSR must have AC output and DC logic drive input. The output<br />

drive signal on the flying leads from the <strong>PD</strong>/<strong>CTX</strong> has a specification of<br />

5-7Vdc at 7mA maximum. Most SSRs are typically rated at 3-32Vdc<br />

but only those with input current requirements of less than 7mA are<br />

suitable.


1.3 Load Current Signalling<br />

The <strong>PD</strong>/<strong>CTX</strong> measures the AC current (45 to 65Hz) in the AC feed<br />

wire passing through the unit. The RMS value of this current is sent to<br />

the controller for display. The minimum resolvable current for a single<br />

turn through the <strong>PD</strong>/<strong>CTX</strong> is 2A. Should you wish to read currents<br />

lower than this it is necessary to increase the number of turns through<br />

the <strong>PD</strong>/<strong>CTX</strong>. Please refer to the relevant controller manuals for further<br />

details.<br />

1.4 Mechanical Details<br />

In Mode 2 operation, the <strong>PD</strong>/<strong>CTX</strong> is designed to be attached to a low<br />

DC control voltage SSR mounted on a suitable heat sink. The bracket<br />

on the <strong>PD</strong>/<strong>CTX</strong> is intended to be mounted underneath the SSR<br />

mounting screw on the high current side of the SSR as indicated in<br />

Figure 2. Do not fit the mounting bracket under the SSR itself.<br />

Alternatively, the <strong>PD</strong>/<strong>CTX</strong> can be mounted to a flat plate, using the<br />

attached bracket. This method of mounting is designed for use with an<br />

external contactor or relay.<br />

1cm<br />

0.4in<br />

7.2cm<br />

1.68in<br />

2.3cm<br />

1.02in<br />

4cm<br />

1.58in<br />

5cm<br />

1.97in<br />

5cm<br />

1.97in<br />

1.5cm<br />

0.6in<br />

4.4cm<br />

1.74in<br />

Diameter<br />

1.27cm<br />

0.5in<br />

Figure 1: Dimensions<br />

3 x 0.3cm<br />

(0.12in)


1.5 Example Wiring Diagram (mode 2)<br />

Compatibility – All series 2200e and 2400 controllers<br />

External logic input SSR as defined in 1.2.<br />

L<br />

N<br />

Heater power fuse<br />

(rating load dependent)<br />

Controller<br />

Fuse 2A(T)<br />

+<br />

1A<br />

L<br />

-<br />

+<br />

CTx<br />

Intelligent<br />

CT<br />

-<br />

1B<br />

1C<br />

1D<br />

2A<br />

M<br />

ODU<br />

L<br />

E<br />

1<br />

N<br />

LA<br />

LB<br />

2B<br />

LC<br />

- Black<br />

+ Red<br />

Logic<br />

input<br />

SSR<br />

2C<br />

2D<br />

3A<br />

3B<br />

AA<br />

AB<br />

AC<br />

VI<br />

Note:- A CTx can supply one<br />

SSR. If more than one SSR is<br />

used, e. g. in a three phase<br />

system, a CTx amplifier is<br />

required<br />

3C<br />

3D<br />

+<br />

PV<br />

-<br />

V+<br />

V-<br />

T/C<br />

Heater<br />

Figure 2: Connections for Mode 2


1.6 Example Wiring Diagram (mode 5)<br />

Compatibility - Models 2204e, 2208e, 2404 and 2408 controllers<br />

External mechanical or mercury contactor<br />

External line voltage SSR<br />

L<br />

N<br />

Controller<br />

Fuse 2A(T)<br />

1A<br />

L<br />

1B<br />

1C<br />

1D<br />

2A<br />

2B<br />

2C<br />

2D<br />

3A<br />

3B<br />

M<br />

ODUL<br />

E<br />

1<br />

Digital<br />

inputs<br />

N<br />

LA<br />

LB<br />

LC<br />

AA<br />

AB<br />

AC<br />

VI<br />

Terminal LA for 2404/08<br />

Terminal LB for 2204/08<br />

Contactor<br />

+ CTx<br />

mode 5<br />

-<br />

Heater power<br />

fuse<br />

(rating load<br />

dependent)<br />

+<br />

3C<br />

3D<br />

+<br />

PV<br />

-<br />

V+<br />

V-<br />

T/C<br />

Heater<br />

The controller will have the order code M5 in the Logic Input position.<br />

Figure 3: Example Wiring Connections for Mode 5


1.7 Connections<br />

The <strong>PD</strong>/<strong>CTX</strong> input terminals are provided with a polarised plug-in<br />

connector.<br />

There is internal protection against reverse connection.<br />

1.8 Technical Specification<br />

Range<br />

2 - 100A (using single primary turn)<br />

Accuracy 2% (typically at reference conditions)<br />

Temperature Operating 0 to 55 o C (32 to 131 o F)<br />

Storage -10 to 70 o C (14 to 158 o F)<br />

RH<br />

5 to 90% non-condensing<br />

Minimum 2A (0.5A when using multiple turns)<br />

working current<br />

Dimensions 49mm wide<br />

46mm high without connector and mounting bracket<br />

94mm with connector and mounting bracket<br />

41mm deep with mounting bracket<br />

Maximum 13mm<br />

conductor sheath<br />

diameter<br />

Mode 2 SSR 5V, 7mA (max) – flying leads<br />

drive level Note: The SSR must be able to switch on from the<br />

<strong>PD</strong>/<strong>CTX</strong> 5V drive signal and draw a maximum of<br />

7mA


1.9 Product Coding<br />

Basic<br />

Product<br />

<strong>PD</strong>S<br />

Mode<br />

Mounting<br />

<strong>PD</strong>/<strong>CTX</strong> 1 2<br />

C5<br />

Manual<br />

3<br />

1 <strong>PD</strong>SIO Mode<br />

M2 <strong>PD</strong>SIO mode 2<br />

M5 <strong>PD</strong>SIO mode 5<br />

2 Mounting<br />

C5 Standard<br />

Example<br />

3 Language<br />

XXX No manual<br />

ENG English<br />

<strong>PD</strong>/<strong>CTX</strong>/M5/C5/ENG


1.10 International Sales and Service<br />

EUROTHERM<br />

CONTROLS LTD<br />

Faraday Close,<br />

Durrington,<br />

Worthing, West<br />

Sussex BN13 3PL<br />

Telephone<br />

Sales:<br />

(01903) 695888<br />

Technical:<br />

(01903) 695777<br />

Service:<br />

(01903) 695444<br />

Fax<br />

(01903) 695666<br />

For countries not<br />

listed<br />

enquiries/orders to:<br />

Eurotherm Controls<br />

Limited,<br />

Export Dept,.<br />

Faraday Close,<br />

Durrington,<br />

Worthing, West<br />

Sussex, BN13 3PL<br />

Telephone<br />

(01903) 268500<br />

Fax<br />

(01903) 265982<br />

AUSTRALIA<br />

Eurotherm Pty. Ltd.<br />

Telephone Sydney<br />

(+61 2) 9477 7022<br />

Fax<br />

(+61 2) 9477 7756<br />

AUSTRIA<br />

Eurotherm GmbH<br />

Telephone Vienna<br />

(+43 1) 798 7601<br />

Fax<br />

(+43 1) 798 7605<br />

Telex 047 1132000<br />

EIAUT A<br />

BELGIUM<br />

Eurotherm B.V.<br />

Telephone Antwerp<br />

(+32 3) 322 3870<br />

Fax<br />

(+32 3) 321 7363<br />

DENMARK<br />

Eurotherm A/S<br />

Telephone<br />

Copenhagen<br />

(+45 31) 871622<br />

Fax<br />

(+45 31) 872124<br />

FRANCE<br />

Eurotherm<br />

Automation SA<br />

Telephone Lyon (+33<br />

478) 664500<br />

Fax<br />

(+33 478) 352490<br />

GERMANY<br />

Eurotherm Regler<br />

GmbH<br />

Telephone Limburg<br />

(+49 6431) 2980<br />

Fax<br />

(+49 6431) 298119<br />

Also regional offices<br />

HONG KONG<br />

Eurotherm Limited<br />

Telephone Hong<br />

Kong<br />

(+852) 2873 3826<br />

Fax<br />

(+852) 2870 0148<br />

Telex 0802 69257<br />

EIFEL HX<br />

INDIA<br />

Eurotherm India<br />

Limited<br />

Telephone Chennai<br />

(+9144) 4961 129<br />

Fax<br />

(+9144) 4961 831<br />

IRELAND<br />

Eurotherm Ireland<br />

Limited<br />

Telephone Naas<br />

(+353 45) 879937<br />

Fax<br />

(+353 45) 875123<br />

ITALY<br />

Eurotherm SpA<br />

Telephone Como<br />

(+39 31) 975111<br />

Fax<br />

(+39 31) 977512<br />

Telex 380893<br />

EUROTH I<br />

JAPAN<br />

Eurotherm Japan<br />

Limited<br />

Telephone Tokyo<br />

(+81 3) 33702951<br />

Fax<br />

(+81 3) 33702960<br />

KOREA<br />

Eurotherm Korea<br />

Limited<br />

Telephone Seoul<br />

(+82 2) 5438507<br />

Fax<br />

(+82 2) 545 9758<br />

Telex EIKOR<br />

K23105<br />

NETHERLANDS<br />

Eurotherm B.V.<br />

Telephone Alphen<br />

a/d Ryn<br />

(+31 172) 411752<br />

Fax<br />

(+31 172) 417260<br />

NEW ZEALAND<br />

Eurotherm Limited<br />

Telephone Auckland<br />

(+64 9) 2635900<br />

Fax:<br />

(+64 9) 2635901<br />

NORWAY<br />

Eurotherm A/S<br />

Telephone Oslo (+47<br />

66) 803330<br />

Fax<br />

(+47 66) 803331<br />

SPAIN<br />

Eurotherm España<br />

SA<br />

Telephone<br />

(+34 91) 6616001<br />

Fax<br />

(+34 91) 6619093<br />

SWEDEN<br />

Eurotherm AB<br />

Telephone Malmo<br />

(+46 40) 384500<br />

Fax<br />

(+46 40) 384545<br />

SWITZERLAND<br />

Eurotherm Produkte<br />

(Schweiz) AG<br />

Telephone Zurich<br />

(+41 55) 4154400<br />

Fax<br />

(+41 55) 4154415<br />

UNITED<br />

KINGDOM<br />

Eurotherm Controls<br />

Limited<br />

Telephone Worthing<br />

(+44 1903) 269888<br />

Fax<br />

(+44 1903) 269666<br />

http://www.eurother<br />

m.co.uk<br />

U.S.A<br />

Eurotherm Controls<br />

Inc.<br />

Telephone Reston<br />

(+1 703) 787 3405<br />

Fax<br />

(+1 703) 787 3436<br />

Informações sobre programação<br />

www.soliton.com.br - e-mail: soliton@soliton.com.br<br />

SOLITON CONTROLES INDUSTRIAIS LTDA<br />

Rua Alfredo Pujol, 1010 - Santana - São Paulo - SP.<br />

Tel:11 - 6950-1834 / Fax: 11 - 6979-8980 - e-mail: vendas@soliton.com.br<br />

Wiring and Installation Instructions HA027158 Issue 1