<strong>PD</strong>/<strong>CTX</strong><br />
<strong>INTELLIGENT</strong><br />
<strong>CURRENT</strong><br />
<strong>TRANSMITTER</strong><br />
ENG<br />
Installation and<br />
operation handbook
1.1 Product Description<br />
The <strong>PD</strong>/<strong>CTX</strong> TM is an intelligent current transmitter. It is used in<br />
conjunction with a pulse density signalling, <strong>PD</strong>S(IO), logic output<br />
from a series 2000 controller, to control a time proportioned Solid State<br />
Relay (SSR) or Contactor. The two logic wires which operate the SSR<br />
also carry load current and status information back to the controller.<br />
This is referred to as ‘<strong>PD</strong>S Mode 2’ operation. Mode 2 provides:<br />
1. Display of true RMS load current<br />
2. High and low current alarm<br />
3. SSR short circuit<br />
4. Heater failure<br />
An alternative capability, referred to as ‘<strong>PD</strong>S Mode 5’, allows the<br />
<strong>PD</strong>/<strong>CTX</strong> to monitor relay or triac output controllers. The <strong>PD</strong>/<strong>CTX</strong><br />
uses the logic inputs of a series 2000 controller to transfer the data to<br />
the controller. This version is used with external mechanical or<br />
mercury contactors and line voltage SSRs. Mode 5 provides the same<br />
features as mode 2 but it can also monitor the <strong>PD</strong>/<strong>CTX</strong> for open or<br />
short circuit conditions and initiate an alarm in the controller.<br />
The <strong>PD</strong>/<strong>CTX</strong> must be supplied for either mode 2 or mode 5 operation.<br />
It is not field alterable. Before connecting the <strong>PD</strong>/<strong>CTX</strong> to the controller<br />
check the product type against the order code given in section 1.9.<br />
1.2 Compatible SSRs<br />
The SSR must have AC output and DC logic drive input. The output<br />
drive signal on the flying leads from the <strong>PD</strong>/<strong>CTX</strong> has a specification of<br />
5-7Vdc at 7mA maximum. Most SSRs are typically rated at 3-32Vdc<br />
but only those with input current requirements of less than 7mA are<br />
suitable.
1.3 Load Current Signalling<br />
The <strong>PD</strong>/<strong>CTX</strong> measures the AC current (45 to 65Hz) in the AC feed<br />
wire passing through the unit. The RMS value of this current is sent to<br />
the controller for display. The minimum resolvable current for a single<br />
turn through the <strong>PD</strong>/<strong>CTX</strong> is 2A. Should you wish to read currents<br />
lower than this it is necessary to increase the number of turns through<br />
the <strong>PD</strong>/<strong>CTX</strong>. Please refer to the relevant controller manuals for further<br />
details.<br />
1.4 Mechanical Details<br />
In Mode 2 operation, the <strong>PD</strong>/<strong>CTX</strong> is designed to be attached to a low<br />
DC control voltage SSR mounted on a suitable heat sink. The bracket<br />
on the <strong>PD</strong>/<strong>CTX</strong> is intended to be mounted underneath the SSR<br />
mounting screw on the high current side of the SSR as indicated in<br />
Figure 2. Do not fit the mounting bracket under the SSR itself.<br />
Alternatively, the <strong>PD</strong>/<strong>CTX</strong> can be mounted to a flat plate, using the<br />
attached bracket. This method of mounting is designed for use with an<br />
external contactor or relay.<br />
1cm<br />
0.4in<br />
7.2cm<br />
1.68in<br />
2.3cm<br />
1.02in<br />
4cm<br />
1.58in<br />
5cm<br />
1.97in<br />
5cm<br />
1.97in<br />
1.5cm<br />
0.6in<br />
4.4cm<br />
1.74in<br />
Diameter<br />
1.27cm<br />
0.5in<br />
Figure 1: Dimensions<br />
3 x 0.3cm<br />
(0.12in)
1.5 Example Wiring Diagram (mode 2)<br />
Compatibility – All series 2200e and 2400 controllers<br />
External logic input SSR as defined in 1.2.<br />
L<br />
N<br />
Heater power fuse<br />
(rating load dependent)<br />
Controller<br />
Fuse 2A(T)<br />
+<br />
1A<br />
L<br />
-<br />
+<br />
CTx<br />
Intelligent<br />
CT<br />
-<br />
1B<br />
1C<br />
1D<br />
2A<br />
M<br />
ODU<br />
L<br />
E<br />
1<br />
N<br />
LA<br />
LB<br />
2B<br />
LC<br />
- Black<br />
+ Red<br />
Logic<br />
input<br />
SSR<br />
2C<br />
2D<br />
3A<br />
3B<br />
AA<br />
AB<br />
AC<br />
VI<br />
Note:- A CTx can supply one<br />
SSR. If more than one SSR is<br />
used, e. g. in a three phase<br />
system, a CTx amplifier is<br />
required<br />
3C<br />
3D<br />
+<br />
PV<br />
-<br />
V+<br />
V-<br />
T/C<br />
Heater<br />
Figure 2: Connections for Mode 2
1.6 Example Wiring Diagram (mode 5)<br />
Compatibility - Models 2204e, 2208e, 2404 and 2408 controllers<br />
External mechanical or mercury contactor<br />
External line voltage SSR<br />
L<br />
N<br />
Controller<br />
Fuse 2A(T)<br />
1A<br />
L<br />
1B<br />
1C<br />
1D<br />
2A<br />
2B<br />
2C<br />
2D<br />
3A<br />
3B<br />
M<br />
ODUL<br />
E<br />
1<br />
Digital<br />
inputs<br />
N<br />
LA<br />
LB<br />
LC<br />
AA<br />
AB<br />
AC<br />
VI<br />
Terminal LA for 2404/08<br />
Terminal LB for 2204/08<br />
Contactor<br />
+ CTx<br />
mode 5<br />
-<br />
Heater power<br />
fuse<br />
(rating load<br />
dependent)<br />
+<br />
3C<br />
3D<br />
+<br />
PV<br />
-<br />
V+<br />
V-<br />
T/C<br />
Heater<br />
The controller will have the order code M5 in the Logic Input position.<br />
Figure 3: Example Wiring Connections for Mode 5
1.7 Connections<br />
The <strong>PD</strong>/<strong>CTX</strong> input terminals are provided with a polarised plug-in<br />
connector.<br />
There is internal protection against reverse connection.<br />
1.8 Technical Specification<br />
Range<br />
2 - 100A (using single primary turn)<br />
Accuracy 2% (typically at reference conditions)<br />
Temperature Operating 0 to 55 o C (32 to 131 o F)<br />
Storage -10 to 70 o C (14 to 158 o F)<br />
RH<br />
5 to 90% non-condensing<br />
Minimum 2A (0.5A when using multiple turns)<br />
working current<br />
Dimensions 49mm wide<br />
46mm high without connector and mounting bracket<br />
94mm with connector and mounting bracket<br />
41mm deep with mounting bracket<br />
Maximum 13mm<br />
conductor sheath<br />
diameter<br />
Mode 2 SSR 5V, 7mA (max) – flying leads<br />
drive level Note: The SSR must be able to switch on from the<br />
<strong>PD</strong>/<strong>CTX</strong> 5V drive signal and draw a maximum of<br />
7mA
1.9 Product Coding<br />
Basic<br />
Product<br />
<strong>PD</strong>S<br />
Mode<br />
Mounting<br />
<strong>PD</strong>/<strong>CTX</strong> 1 2<br />
C5<br />
Manual<br />
3<br />
1 <strong>PD</strong>SIO Mode<br />
M2 <strong>PD</strong>SIO mode 2<br />
M5 <strong>PD</strong>SIO mode 5<br />
2 Mounting<br />
C5 Standard<br />
Example<br />
3 Language<br />
XXX No manual<br />
ENG English<br />
<strong>PD</strong>/<strong>CTX</strong>/M5/C5/ENG
1.10 International Sales and Service<br />
EUROTHERM<br />
CONTROLS LTD<br />
Faraday Close,<br />
Durrington,<br />
Worthing, West<br />
Sussex BN13 3PL<br />
Telephone<br />
Sales:<br />
(01903) 695888<br />
Technical:<br />
(01903) 695777<br />
Service:<br />
(01903) 695444<br />
Fax<br />
(01903) 695666<br />
For countries not<br />
listed<br />
enquiries/orders to:<br />
Eurotherm Controls<br />
Limited,<br />
Export Dept,.<br />
Faraday Close,<br />
Durrington,<br />
Worthing, West<br />
Sussex, BN13 3PL<br />
Telephone<br />
(01903) 268500<br />
Fax<br />
(01903) 265982<br />
AUSTRALIA<br />
Eurotherm Pty. Ltd.<br />
Telephone Sydney<br />
(+61 2) 9477 7022<br />
Fax<br />
(+61 2) 9477 7756<br />
AUSTRIA<br />
Eurotherm GmbH<br />
Telephone Vienna<br />
(+43 1) 798 7601<br />
Fax<br />
(+43 1) 798 7605<br />
Telex 047 1132000<br />
EIAUT A<br />
BELGIUM<br />
Eurotherm B.V.<br />
Telephone Antwerp<br />
(+32 3) 322 3870<br />
Fax<br />
(+32 3) 321 7363<br />
DENMARK<br />
Eurotherm A/S<br />
Telephone<br />
Copenhagen<br />
(+45 31) 871622<br />
Fax<br />
(+45 31) 872124<br />
FRANCE<br />
Eurotherm<br />
Automation SA<br />
Telephone Lyon (+33<br />
478) 664500<br />
Fax<br />
(+33 478) 352490<br />
GERMANY<br />
Eurotherm Regler<br />
GmbH<br />
Telephone Limburg<br />
(+49 6431) 2980<br />
Fax<br />
(+49 6431) 298119<br />
Also regional offices<br />
HONG KONG<br />
Eurotherm Limited<br />
Telephone Hong<br />
Kong<br />
(+852) 2873 3826<br />
Fax<br />
(+852) 2870 0148<br />
Telex 0802 69257<br />
EIFEL HX<br />
INDIA<br />
Eurotherm India<br />
Limited<br />
Telephone Chennai<br />
(+9144) 4961 129<br />
Fax<br />
(+9144) 4961 831<br />
IRELAND<br />
Eurotherm Ireland<br />
Limited<br />
Telephone Naas<br />
(+353 45) 879937<br />
Fax<br />
(+353 45) 875123<br />
ITALY<br />
Eurotherm SpA<br />
Telephone Como<br />
(+39 31) 975111<br />
Fax<br />
(+39 31) 977512<br />
Telex 380893<br />
EUROTH I<br />
JAPAN<br />
Eurotherm Japan<br />
Limited<br />
Telephone Tokyo<br />
(+81 3) 33702951<br />
Fax<br />
(+81 3) 33702960<br />
KOREA<br />
Eurotherm Korea<br />
Limited<br />
Telephone Seoul<br />
(+82 2) 5438507<br />
Fax<br />
(+82 2) 545 9758<br />
Telex EIKOR<br />
K23105<br />
NETHERLANDS<br />
Eurotherm B.V.<br />
Telephone Alphen<br />
a/d Ryn<br />
(+31 172) 411752<br />
Fax<br />
(+31 172) 417260<br />
NEW ZEALAND<br />
Eurotherm Limited<br />
Telephone Auckland<br />
(+64 9) 2635900<br />
Fax:<br />
(+64 9) 2635901<br />
NORWAY<br />
Eurotherm A/S<br />
Telephone Oslo (+47<br />
66) 803330<br />
Fax<br />
(+47 66) 803331<br />
SPAIN<br />
Eurotherm España<br />
SA<br />
Telephone<br />
(+34 91) 6616001<br />
Fax<br />
(+34 91) 6619093<br />
SWEDEN<br />
Eurotherm AB<br />
Telephone Malmo<br />
(+46 40) 384500<br />
Fax<br />
(+46 40) 384545<br />
SWITZERLAND<br />
Eurotherm Produkte<br />
(Schweiz) AG<br />
Telephone Zurich<br />
(+41 55) 4154400<br />
Fax<br />
(+41 55) 4154415<br />
UNITED<br />
KINGDOM<br />
Eurotherm Controls<br />
Limited<br />
Telephone Worthing<br />
(+44 1903) 269888<br />
Fax<br />
(+44 1903) 269666<br />
http://www.eurother<br />
m.co.uk<br />
U.S.A<br />
Eurotherm Controls<br />
Inc.<br />
Telephone Reston<br />
(+1 703) 787 3405<br />
Fax<br />
(+1 703) 787 3436<br />
Informações sobre programação<br />
www.soliton.com.br - e-mail: soliton@soliton.com.br<br />
SOLITON CONTROLES INDUSTRIAIS LTDA<br />
Rua Alfredo Pujol, 1010 - Santana - São Paulo - SP.<br />
Tel:11 - 6950-1834 / Fax: 11 - 6979-8980 - e-mail: vendas@soliton.com.br<br />
Wiring and Installation Instructions HA027158 Issue 1