Section 4: Setting the Modbus Addresses<br />
4.1 COMMUNICATION SETUP FOR BOILERS<br />
Each Modbus device in each boiler must be addressed to<br />
properly communicate with the <strong>ECCS</strong> system. The<br />
Temperature <strong>Control</strong>ler must be addressed through the<br />
configuration level and the flame safeguard will be<br />
addressed according to the following instructions. Refer to<br />
Appendix A, system wiring, or individual component<br />
manuals.<br />
4.2 SETTING THE ADDRESS OF THE HONEYWELL<br />
MODBUS MODULE<br />
Addressing for the HW Modbus Module correlates to the<br />
Temp <strong>Control</strong>lers Modbus addressing on the same unit.<br />
There are 2 dials on the bottom of the module that need to<br />
be set and a jumper that needs to be removed. Refer to<br />
Figure 4.1: Honeywell S7810M Modbus Module Mounting<br />
and 4.2: S7810M Address Switches and Baud Rate Jumper.<br />
4.3 SETTING THE MODBUS ADDRESS OF THE<br />
FIREYE MICRO M<br />
Addressing for the Fireye correlates to the Temperature<br />
<strong>Control</strong>lers Modbus addressing on the same unit. Refer to<br />
MicroM manual for instructions.<br />
Fireye MicroM<br />
Fireye<br />
Temperature Parameter<br />
<strong>Control</strong>ler Baud Rate @<br />
(C113)<br />
19,200<br />
Unit Address<br />
Boiler<br />
1 0160<br />
11<br />
Boiler<br />
2 0260<br />
12<br />
Boiler<br />
3 0360<br />
13<br />
Boiler<br />
4 0460<br />
14<br />
Boiler<br />
5 0560<br />
15<br />
Boiler<br />
6 0660<br />
16<br />
Honeywell<br />
Temperature<br />
<strong>Control</strong>ler<br />
(C113)<br />
S7810M<br />
Modbus<br />
Module<br />
Baud Rate @<br />
19,200<br />
remove<br />
jumper<br />
10"s<br />
Dial<br />
1"s<br />
Dial<br />
Boiler<br />
1<br />
0160<br />
1 1<br />
Boiler<br />
2<br />
0260<br />
1 2<br />
Boiler<br />
3<br />
0360<br />
1 3<br />
Boiler<br />
4<br />
0460<br />
1 4<br />
Boiler<br />
5<br />
0560<br />
1 5<br />
Boiler<br />
6<br />
0660<br />
1 6<br />
16