01.07.2015 Views

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

I&O Manual - ECCS Control System - Categories On Thermal ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

INSTALLATION, OPERATING AND<br />

SERVICE INSTRUCTIONS<br />

<strong>ECCS</strong> CONTROL SYSTEM<br />

ON/OFF & MODULATION<br />

Price - $3.00<br />

For service and repairs to the heating plant, or this panel call your heating contractor. When seeking<br />

information from the manufacturer, provide boiler model and serial number as shown on rating label.<br />

<strong>ECCS</strong> <strong>Control</strong><br />

<strong>System</strong><br />

Serial<br />

Number<br />

Type <strong>System</strong><br />

Heating Contractor<br />

Address<br />

Phone Number<br />

Your Local <strong>Thermal</strong> Solutions Representative:<br />

81456003R2-12/05


IMPORTANT INFORMATION - READ CAREFULLY<br />

NOTE: The equipment shall be installed in accordance with those installation regulations required in the area where the<br />

installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction<br />

shall be consulted before installations are made.<br />

All wiring on boilers installed in the USA shall be in accordance with the National Electrical Code and/or local regulations.<br />

All wiring on boilers installed in Canada shall be in accordance with the Canadian Electrical Code and/or local regulations.<br />

The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to<br />

important information concerning product life.<br />

DANGER<br />

Indicates an imminently hazardous situation<br />

which, if not avoided, will result in death,<br />

serious injury or substantial property<br />

damage.<br />

CAUTION<br />

Indicates a potentially hazardous situation<br />

which, if not avoided, may result in<br />

moderate or minor injury or property<br />

damage.<br />

WARNING<br />

Indicates a potentially hazardous situation<br />

which, if not avoided, could result in death,<br />

serious injury or substantial property<br />

damage.<br />

NOTICE<br />

Indicates special instructions on<br />

installation, operation, or maintenance<br />

which are important but not related to<br />

personal injury hazards.<br />

2


Parameter Limits and Factory Defaults<br />

Initial Setup<br />

Parameter<br />

Range<br />

Factory Setting<br />

Password<br />

Level<br />

Total<br />

Boilers<br />

2 - 6<br />

3 5 25<br />

Boiler<br />

Type, Mod or <strong>On</strong>/Off<br />

1 - 2<br />

1 5 25<br />

Proportional<br />

0 - 25<br />

25<br />

5 25<br />

Integral<br />

0 - 2<br />

1 5 25<br />

Derivative<br />

0 - 1<br />

0 5 25<br />

Start<br />

Trigger (% of firing rate)<br />

50<br />

- 100<br />

90<br />

2 21<br />

Stop<br />

Trigger (% of firing rate)<br />

1 - 50<br />

25<br />

2 21<br />

<strong>On</strong> Point (degrees below setpoint) 1 - 15<br />

5 2 21<br />

Off<br />

Point (degrees above setpoint) 1 - 15<br />

5 2 21<br />

Start<br />

Time Delay (seconds)<br />

90<br />

- 900<br />

120<br />

2 21<br />

Stop<br />

Time Delay (seconds)<br />

0 - 1200<br />

120<br />

2 21<br />

Setpoint<br />

(degrees Fahrenheit)<br />

140<br />

- 230<br />

180<br />

1 20<br />

DHW Priority<br />

140<br />

- 230<br />

180<br />

1 20<br />

Local/Remote<br />

Switch<br />

Local/Remote<br />

Page<br />

Local<br />

0 23<br />

Rotation Time (hrs)<br />

8 - 720<br />

24<br />

2 22<br />

Rotation Enable/Disable<br />

<strong>On</strong>-Of<br />

f<br />

Off<br />

2 22<br />

Customer<br />

Setting<br />

Change Sequence<br />

Lead<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

Lag<br />

#1<br />

#2<br />

#3<br />

#4<br />

#5<br />

1 - total blr<br />

1 2 22<br />

1 - total blr<br />

2 2 22<br />

1 - total blr<br />

3 2 22<br />

1 - total blr<br />

4 2 22<br />

1 - total blr<br />

5 2 22<br />

1 - total blr<br />

6 2 22<br />

Change<br />

Sequence Button<br />

2 22<br />

Enter<br />

Lead/Lag Sequence<br />

2 22<br />

Outdoor Reset & WWSD<br />

Low Air Temp<br />

-60<br />

- 50<br />

10<br />

3 23<br />

High Water Temp<br />

150<br />

- 240<br />

180<br />

3 23<br />

High Air Temp<br />

50<br />

- 120<br />

55<br />

3 23<br />

Low Water Temp<br />

140<br />

- 180<br />

140<br />

3 23<br />

WWSD <strong>System</strong> Pumps <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Boilers <strong>On</strong>/Off<br />

0 - 1<br />

0 3 25<br />

WWSD Enable/Disable<br />

Outdoor<br />

Switch<br />

Reset Enable/Dis Switch<br />

<strong>On</strong> - Off<br />

<strong>On</strong> - Off<br />

Off<br />

3 25<br />

Off<br />

2 23<br />

3


Table of Contents<br />

i. Programmable Ranges.................................................... 3<br />

Section 1. Component Description .................................... 5<br />

Section 2. Principles of Operation ..................................... 6<br />

2.1. <strong>System</strong> Description<br />

2.2. Lead Lag<br />

2.3. Unavailable Boilers<br />

2.4. Auto Rotate .................................................. 7<br />

2.5. Outdoor Reset<br />

2.6. Warm Weather Shutdown & Enable/Disable<br />

2.7. Modbus Communication<br />

2.8. Trending<br />

2.9. Local/Remote Operation<br />

2.10 Domestic Hot Water Priority............................. 8<br />

2.11 Alarms<br />

Section 3. Installation.......................................................... 9<br />

3.1.Unpacking ....................................................... 9<br />

3.1.1. Inspection<br />

3.2. Mounting ....................................................... 9<br />

3.2.1. Panel<br />

3.2.2. <strong>System</strong> Water Temp Sensor<br />

3.2.3. Outdoor Air Temp Sensor<br />

Figure 3.1: Panel Mounting Layout .... 10<br />

3.3. Electrical ....................................................... 11<br />

3.3.1. General<br />

3.3.2. Wiring Power Supply to Panel<br />

3.3.3. Wiring Panel to Boilers<br />

3.3.4. Wiring Panel to Sensors<br />

Figure 3.2: Panel Layout ............................ 12<br />

Figure 3.3: <strong>System</strong> Wiring .......................... 13<br />

Figure 3.4: <strong>ECCS</strong> Panel Wiring ................... 14<br />

Figure 3.5: Boiler Wiring Diagram .............. 15<br />

Section 5. Touch Screen Programming .............................. 19<br />

5.1. Screen Description ....................................... 19<br />

5.2. General Guidelines for Using the<br />

Touchscreen ................................................. 19<br />

Figure 5.1 Touch Screen Login .................. 19<br />

Figure 5.2 Main Screen .............................. 20<br />

Figure 5.3 <strong>System</strong> Setup Screen................. 20<br />

Figure 5.4 Lead Lag Trigger Setup Screen . 21<br />

Figure 5.5 Sequence and Rotation Screen . 22<br />

Figure 5.6 Outdoor Reset Setup Screen ..... 23<br />

Figure 5.7 Boiler Parameters Screen ........... 23<br />

Figure 5.8 Alarm History Screen ................ 24<br />

Figure 5.9 Alarm Pop Up Screen ................ 24<br />

Figure 5.10 Warm Weather Shutdown<br />

Screen ....................................... 25<br />

Figure 5.11 Initial Setup Screen ................. 25<br />

Figure 5.12 Trend Screen ........................... 26<br />

Figure 5.13 Trend Screen Zoom <strong>Control</strong> .... 26<br />

Figure 5.14 Time/Date Screen ...................... 27<br />

Section 6. Troubleshooting Guide .................................... 28<br />

Section 7. Appendix ......................................................... 30<br />

7.A. Temperature <strong>Control</strong>ler Operation for<br />

Modulating Boilers (Modbus) ....................... 30<br />

7.1. Description ................................................... 30<br />

7.2. Setup ............................................................ 30<br />

7.3. Modbus Version Used on Boilers<br />

<strong>Control</strong>led by the <strong>ECCS</strong> <strong>System</strong> ..................... 30<br />

Figure 7.1 Process Data ............................. 30<br />

7.4. Adjustments ................................................. 31<br />

7.5. <strong>System</strong> Specifications .................................. 31<br />

Section 4. Setting the Modbus Module Address ............. 16<br />

4.1. Communication Setup for Boilers ................. 16<br />

4.2. Setting the Address of the Honeywell<br />

Modbus Module .......................................... 16<br />

4.3. Setting the Modbus Address of the Fireye<br />

Micro M ........................................................ 16<br />

Figure 4.1: Honeywell S7810M Modubus<br />

Module Mounting ..................................... 17<br />

Figure 4.2: S7810M Address Switches and<br />

Baud Rate Jumper ...................................... 18<br />

4


Section 1: Component Description<br />

COMPONENT DESCRIPTION Part #<br />

1) <strong>ECCS</strong> <strong>Control</strong> Panel– houses the touch screen, PLC, analog input/output card, and terminal strips. ...................... 60156400<br />

Built to UL 508A Standard. Refer to Figure 2, Panel Layout<br />

2) <strong>System</strong> water temperature sensor with Thermowell .................................................................................................. 80160721<br />

RTD Pt 1000<br />

3) Outdoor air temperature sensor ................................................................................................................................. 80160722<br />

RTD Pt. 1000<br />

4) Touch Screen ............................................................................................................................................................. 80160912<br />

5.7” monochromatic<br />

5) PLC 226XM 120Vac in, 24 Vac out ......................................................................................................................... 80160910<br />

24 Inputs<br />

16 Outputs<br />

6) RTD Module ............................................................................................................................................................. 80160917<br />

2 RTD Inputs<br />

7) Analog Input Module ............................................................................................................................................................... 80160911<br />

4 (4-20 ma or 0-10 Vsignal inputs)<br />

1 (output)<br />

8) PLC Memory Cartridge ............................................................................................................................................................. 80160925<br />

9) PLC Battery Cartridge ............................................................................................................................................................... 80160924<br />

Components in the boiler that interface with the <strong>ECCS</strong> panel.<br />

10) Modbus version of the boiler temperature controller ................................................................................................ 80160908<br />

11) Honeywell Modbus Module for the Flamesafeguard. ............................................................................................... 80160909<br />

5


Section 2: Principles of Operation<br />

2.1 SYSTEM DESCRIPTION<br />

The <strong>ECCS</strong> (Electronic <strong>Control</strong>s and Communication<br />

<strong>System</strong>) is a Lead Lag sequencer for modulating and<br />

on/off boilers capable of auto rotation, Outdoor reset,<br />

and communication using a Modbus protocol.<br />

All the control signals between the boiler and the <strong>ECCS</strong><br />

panel are transmitted over a 3 wire shielded cable using<br />

the Modbus protocol. This includes the enable/disable<br />

signal, the modulating signal, and the local/remote<br />

signal.<br />

<strong>System</strong> water temperature is continuously monitored<br />

through the header water temperature sensor. The<br />

system compares this temperature to the setpoint which<br />

is fixed or generated from the outdoor reset curve. If<br />

the system water temperature falls below the adjustable<br />

system ON POINT set on the screen (refer to Figure<br />

5.3) the lead boiler will turn on via a signal from the<br />

<strong>ECCS</strong> system. For a modulating boiler, The PID<br />

control will generate a signal and send it to the boilers<br />

via the MODBUS. If the firing rate goes above the<br />

START TRIGGER Point set on the screen for the<br />

amount of time set in the START DELAY, the first lag<br />

boiler will start. <strong>On</strong>ce the lag boiler starts it will drive<br />

to the same firing rate as the lead boiler. Both boilers<br />

will fire in tandem, at the same firing rate. Additional<br />

lag boilers will start by the same criteria in the order<br />

that set as the LEAD LAG SEQUENCE. Boilers will<br />

be shed in the reverse order of which they came on<br />

(AKA: First <strong>On</strong>, Last Off). As load is shed the boilers<br />

will use the STOP TRIGGER point and the STOP<br />

DELAY parameters set on the screen.<br />

For <strong>On</strong>/Off boilers, additional boilers will be added<br />

when the system water temperature drops below the<br />

system ON POINT for the time set in the boiler START<br />

DELAY. Boilers will be shed in reverse order using<br />

the OFF POINT and STOP DELAY parameters.<br />

The Lead Lag (LL) system will be capable of running a<br />

maximum number of 6 boilers. Parameters in the<br />

temperature controller and flame safeguard are<br />

transmitted via the Modbus connection to the PLC and<br />

Touch screen.<br />

2.2 LEAD LAG<br />

2.2.1. In a Lead Lag (LL) system (refer to Figure 5.4),<br />

one boiler is designated as a lead boiler. The lead<br />

boiler will always be the first boiler to come on and the<br />

last boiler to shut off. The lag boilers will always<br />

come on after the lead in order of their number. The<br />

first lag (lag#1) will always be the second boiler to<br />

come on, the second lag (lag#2) will always be the<br />

third to come on, etc. They will turn off in reverse<br />

order.<br />

6<br />

2.2.2. There is a sequence preprogrammed from the<br />

factory as a default of: Lead = boiler 1, Lag #1 =<br />

boiler 2, Lag #2 = boiler 3, etc., in sequential order.<br />

Sequence can be changed to any order that is<br />

desired. Numbers cannot be duplicated or out of<br />

range.<br />

2.2.3. To change the lead lag sequence go to the<br />

SEQUENCE AND ROTATION SCREEN<br />

(Figure 5.5). From the main screen press the system<br />

setup button, then the Enter Lead Lag Sequence<br />

button.<br />

2.2.4. The system will turn on the lead boiler when the<br />

temperature drops below the <strong>System</strong> ON POINT. The<br />

boiler will turn the lead off only if it is the only<br />

boiler running and the temperature is above the<br />

<strong>System</strong> OFF POINT.<br />

The <strong>ECCS</strong> system turns on additional boilers when the<br />

firing rate of the lead boiler rises above the START<br />

TRIGGER (See Figure 5.4: Lead Lag Trigger Setup<br />

Screen) point for the length of time in the BOILER<br />

START DELAY box. The START TRIGGER is the<br />

percentage of the firing rate that a modulating boiler<br />

must reach in order to start the delay timer. <strong>On</strong>ce the<br />

delay timer finishes timing, the next boiler in the<br />

sequence will start. If the firing rate drops below the<br />

START TRIGGER before the timer is complete, the<br />

timer will reset.<br />

ON/OFF boilers will sequence in accordance with the<br />

<strong>System</strong> ON and OFF POINTS. See Figure 5.4 under<br />

Setpoint differential.<br />

2.3. UNAVAILABLE BOILERS<br />

2.3.1. If a boiler is unavailable for any one of the<br />

following reasons the LL sequence will remove them<br />

and adjust the sequence until they become available<br />

again. The purpose of this is to save time between<br />

stages if there is an unavailable boiler. If the<br />

desired lead boiler is unavailable, Lag #1 will<br />

become the lead and other boilers will shift<br />

accordingly. The program will rotate based on the<br />

sequence that has been entered onto the screen.<br />

Flame fail – If the boiler has a flame failure the boiler<br />

will be removed from the LL sequence until the unit<br />

has been reset.<br />

Boiler in Local mode – If the Local/Remote switch is<br />

in Local the boiler will be removed from the LL<br />

sequence until the unit has been placed back in<br />

Remote.


2.3.3. When a boiler becomes available again (fault<br />

cleared, switch from local to remote, etc.) the system<br />

will put it back in the sequence. If the desired lead<br />

becomes available it will start immediately and may<br />

shut down the last boiler running in the sequence<br />

depending on how many boilers are required.( EX: In a<br />

3 boiler system, if 2 boilers are running and only 2 are<br />

required when the lead comes back in service it will<br />

shut down the last lag boiler. If 2 are running and 3 are<br />

required it will not shut down the last lag boiler.)<br />

2.4 AUTO ROTATE<br />

When this function is selected by pressing the Auto<br />

Rotate button (refer to Figure 5.5) the sequence will<br />

automatically rotate based on how long the lead boiler<br />

runs. The rotation time will be set by the operator.<br />

After rotation time is reached, the Lead boiler will move<br />

to the end of the sequence and the second boiler will<br />

become the lead.<br />

When the rotation time is reached, the next boiler in the<br />

sequence will start. After the unit is running for a few<br />

minutes the sequence will rotate, dropping out the old<br />

lead boiler. This will insure the same amount of boilers<br />

are running before and after rotation occurs.<br />

If the sequence is changed manually, the rotation timer<br />

will start from the beginning.<br />

2.5 OUTDOOR RESET<br />

The outdoor reset function (refer to Figure 5.6)<br />

generates a setpoint based on a curve programmed on<br />

the screen and the outdoor air temperature. Two points<br />

are entered and a linear curve is generated.<br />

An RTD temperature sensor will send a signal to the<br />

RTD module for the PLC.<br />

If outdoor reset is enabled through a switch on the<br />

screen, the setpoint will be generated by the curve for<br />

outdoor reset programmed on the screen.<br />

2.6 WARM WEATHER SHUTDOWN/ENABLE<br />

DISABLE<br />

The Warm Weather Shutdown (WWSD) (refer to<br />

Figure 5.10) function will shutdown either the boilers,<br />

the system pumps or both depending on the selections<br />

on the WWSD screen. When the outdoor air<br />

temperature goes above the temperature set in the high<br />

outdoor air temperature box on the outdoor reset<br />

screen, shutdown will occur.<br />

The outputs for energizing a relay for controlling the<br />

system pumps, O:0.0 and O:0.1 (Refer to figure 3.5) will<br />

energize when the system goes into a WWSD<br />

condition. This is a fail-safe condition. If power is lost<br />

to the <strong>ECCS</strong> panel the pumps will still operate.<br />

7<br />

<strong>On</strong>ce the OAT>HAT setting, a 60 sec timer starts. If the<br />

condition is still true at the end of the 60 seconds the<br />

WWSD function will energize. If both the boilers and<br />

the pumps are selected to shut down, the boilers will<br />

shut down first and 30 seconds later the system pumps<br />

will shut down. This is done to minimize cycling around<br />

the HAT, which triggers the WWSD function.<br />

The WWSD function (or can be used as an Enable/<br />

Disable signal for all boilers) can also be activated with<br />

an external contact closure between terminals L+ and<br />

I:0.1 (Refer to figure 3.5). Ensure that the WWSD<br />

function is not enabled on the <strong>ECCS</strong> panel. This will<br />

function only when the boilers are in the remote mode<br />

and being controlled by the <strong>ECCS</strong> panel. If the boilers<br />

are in the local mode they will not be shut down<br />

by this function. There will be a 1 minute delay before<br />

shutdown once the contact is closed.<br />

2.7 MODBUS COMMUNICATION<br />

The <strong>ECCS</strong> Panel uses the Modbus protocol to<br />

communicate with all the boilers in the system. The<br />

Flame Safeguard and the temperature controller both<br />

have Modbus communication capability. Information<br />

such as faults, alarms, flame signal, cycles, hours,<br />

setpoint, and on/off points can all be communicated to<br />

the touch screen.<br />

2.8 TRENDING<br />

<strong>System</strong> water temperature and outdoor air temperature<br />

are trended for total of 8 hrs (refer to Figure 5.13). The<br />

standard screen shows one hour of time and that trend<br />

can be zoomed in or out from 7.5 minutes to 8 hours.<br />

Points on trend are recorded every 30 seconds.<br />

2.9 LOCAL/REMOTE OPERATION<br />

A Local/Remote switch is located on the Boiler<br />

Parameter screen on the touch screen (refer to Figure<br />

5.7). Some boilers may have an optional physical<br />

selector switch on the front of the boiler.<br />

The Local/Remote selector switch enables the boilers<br />

to be controlled from either the temperature sensor on<br />

the individual boiler (Local) or controlled from the<br />

<strong>System</strong> water temperature sensor (Remote). If the boiler<br />

is in the remote mode, the display on the individual<br />

boiler temperature control will flash Re F (Remote Firing<br />

Rate) and the remote setpoint. If in the local mode, the<br />

display will show the local setpoint without flashing.<br />

*Fail-safe Operation*<br />

If power is lost to the <strong>ECCS</strong> panel, the boilers will<br />

automatically revert back to the local mode.


2.10 DOMESTIC HOT WATER (DHW) PRIORITY<br />

Domestic hot water priority is accomplished by<br />

providing a contact closure to the <strong>ECCS</strong> panel from a<br />

domestic hot water tank. The <strong>ECCS</strong> panel sends out<br />

24V on terminal L+ and receives voltage back on<br />

terminal I0:0 when DHW priority is called for. When<br />

I0:0 receives a signal the following sequence occurs:<br />

1.) The control compares the DHW setpoint (which is<br />

set on the <strong>System</strong> Setup Screen, See Figure: 5.3.) to the<br />

system generated by Outdoor reset curve or fixed<br />

setpoint. If the DHW setpoint is higher, the DHW<br />

setpoint will become the new setpoint. If the DHW<br />

setpoint is lower than the existing setpoint it will not<br />

change the setpoint.<br />

2.) If the system is in the WWSD mode, the system<br />

will be taken out of the WWSD mode and start<br />

boilers until the system water temperature is brought<br />

up to the DHW setpoint.<br />

NOTICE<br />

The <strong>ECCS</strong> <strong>System</strong> WILL NOT start any<br />

pumps or open valves in the DHW piping.<br />

This must be provided by others.<br />

2.11 ALARMS<br />

a. The ECCs will annunciate and record alarms on the<br />

screen that come from the individual boilers. Any of<br />

the faults from the flamesafeguard are annunciated<br />

through Modbus communication to the <strong>ECCS</strong> panel.<br />

The format for the alarms can be viewed in Fig 5.9.<br />

The alarm will indicate which boiler is in alarm, the<br />

fault code #, and a description of the 7 most common<br />

faults. This includes Main Flame Failure, Main Flame<br />

Ignition Failure, Pilot flame failure, Air flow failure,<br />

lockout interlock, Running interlock and Flame<br />

detected. If it is one of the other 100+ possible<br />

alarms it will just display the fault code for the Flame<br />

safeguard. In addition there are alarms for High water<br />

temperature(above 230F), Low water temperature<br />

(below 120F), and communication failure.<br />

A communication failure occurs when the<br />

communication over the Modbus is interrupted by<br />

either losing power to the boiler or there is a break in<br />

the wiring.<br />

b. The <strong>ECCS</strong> stores 100+ alarms in the history<br />

screen. Every alarm is time and date stamped when it<br />

Occurs, when it was Acknowledged, and when it was<br />

Cleared. See Fig 5.8. The screen does not have any<br />

permanent memory so if the power is turned off to the<br />

panel the alarm history is lost.<br />

c. As long as an alarm is active, there will be a small<br />

box with an exclamation point in it at the bottom of<br />

the screen. This will also have the # of active<br />

alarms at the bottom of the box.<br />

d. External alarm indication – A 24vdc relay(supplied<br />

by others) can be power by the <strong>ECCS</strong> between<br />

terminals O:0.7 and M for an alarm indication. Refer<br />

to Fig 3.4.<br />

2.12 EXTERNAL ENABLE/DISABLE<br />

See 2.6 Warm Weather Shut Down on page 7.<br />

8


Section 3: Installation<br />

3.1 UNPACKING<br />

3.1.1. Inspection<br />

CAUTION<br />

Do not lay panel down on touch screen.<br />

Panel weighs approximately 25 lbs.<br />

Use proper lifting techniques when handling.<br />

a. Inspect the shipment carefully for any signs of<br />

damage. All equipment is carefully manufactured,<br />

inspected and packed before shipment. Our<br />

responsibility ceases upon delivery of the <strong>ECCS</strong><br />

panel to the carrier in good condition. The<br />

consignee must file any claims for damage or<br />

shortage in shipment immediately against the<br />

carrier. <strong>Thermal</strong> Solutions Products, LLC will<br />

allow noclaims for variances or shortages unless<br />

presented within thirty (30) days after receipt of<br />

equipment.<br />

b. The <strong>ECCS</strong> system will include:<br />

(1) Panel with touch screen mounted in front door.<br />

PLC inside with terminal strips and breaker.<br />

(1) <strong>System</strong> water temperature sensor and<br />

thermowell.<br />

(1) Outdoor air temperature sensor.<br />

WARNING<br />

Carefully read all instructions before<br />

installing panel. Failure to follow all<br />

instructions in proper order can cause<br />

personal injury or death.<br />

3.2 MOUNTING<br />

3.2.1. Panel<br />

a. The <strong>ECCS</strong> system must be installed to conform<br />

with the requirements of the local and state<br />

authority having jurisdiction, or in the absence of<br />

such requirements, to the latest release of the<br />

National Electric Code, ANSI/NFPA 70.<br />

b. Provide clearance around panel for wiring conduit<br />

and access to panel.<br />

Allow 26" in front of panel to allow door to be<br />

opened and personnel access to touch screen.<br />

Allow 4” on bottom, top and sides to allow<br />

clearance for conduit.<br />

c. Mount in the vertical position. Door hinges on left<br />

side with touch screen facing out. See Figure 3.1<br />

for physical size and details on mounting holes.<br />

d. Panel is rated for NEMA 12 service. When<br />

attaching conduit, enter from bottom of panel to<br />

prevent water from gravitating down the conduit<br />

into the box.<br />

3.2.2. <strong>System</strong> Water Temperature Sensor<br />

a. Mount the thermowell and sensor in a 3/4"<br />

coupling in the common header downstream of all<br />

boiler connections. Maintain a minimum distance<br />

of 10 pipe diameters for connections. See Figure<br />

3.3 <strong>System</strong> Wiring.<br />

3.2.3. Outdoor Air Temperature Sensor<br />

a. Mount the temperature sensor on an outside wall<br />

out of direct sunlight, preferably a north facing<br />

wall.<br />

b. Do not mount sensor near exhausts of any kind,<br />

this may affect readings.<br />

WARNING<br />

Installation of this panel should be<br />

undertaken only by trained and skilled<br />

personnel from a qualified service agency.<br />

9


Figure 3.1: Panel Mounting Layout<br />

10


3.3.ELECTRICAL<br />

NOTICE<br />

3.3.1. General<br />

DANGER<br />

Always positively assure electrical power<br />

is disconnected before attempting work<br />

on or near electrical components or<br />

systems. Electrical shock will/can cause<br />

death or serious injury.<br />

Never work on or near electrical<br />

components when the possibility of<br />

water contact exists. Electrical shocks<br />

will/can result.<br />

Power may need to be disconnected at<br />

more than one location on one or more<br />

voltage supplies.<br />

Electrical work must be performed by<br />

licensed, skilled and experienced<br />

personnel.<br />

Always follow the electrical diagrams<br />

provided with the <strong>ECCS</strong> system. Consult<br />

manufacturer if problems or questions<br />

arise.<br />

Always positively assure electrical work<br />

is performed correctly according to the<br />

authority having jurisdiction before<br />

connecting the power supply.<br />

a. The <strong>ECCS</strong> system must be installed to conform<br />

with the requirements of the local and state<br />

authority having jurisdiction, or in the absence of<br />

such requirements, to the latest release of the<br />

National Electric Code, ANSI/NFPA 70.<br />

b. Panel is built and labeled to UL508A standards.<br />

c. Refer to the wiring diagram supplied with the<br />

panel, the wiring diagram for the boiler, the<br />

system wiring diagram, and the Panel layout<br />

diagram for wiring information.<br />

d. Do not route the communication cable in conduit<br />

with line voltage circuits.<br />

e. Maximum wire length:<br />

Communication bus, 4000 ft.<br />

Low voltage conductors are not to be routed<br />

with line voltage conductors.<br />

3.3.2. Wiring Power Supply to Panel<br />

a. The <strong>ECCS</strong> panel requires 120Vac brought into<br />

the panel. Connect the 120V leg directly to the 4-<br />

amp breaker on the terminal strip. The Neutral<br />

wire connects to the N terminal. The ground wire<br />

connects to the green/yellow terminal.<br />

b. 120Vac supply to the panel must be protected by<br />

a fused disconnect, maximum 20A (by others).<br />

3.3.3. Wiring Panel to Boilers<br />

a. All the wiring going from the <strong>ECCS</strong> panel to the<br />

boilers is low voltage DC, 24V or less. Use<br />

minimum 22ga., 3 wire shielded cable. Belden<br />

Part# 8771 or equivalent.<br />

b. Modbus Signal - 3 wire, 22ga. shielded cable run<br />

from terminals A, B, C in the panel to terminals A,<br />

B, C in THE CLOSEST BOILER. The wire must<br />

be wired from the closest boiler to the next boiler<br />

and repeated until the last boiler is reached. In<br />

other words this must be a continuous chain (daisy<br />

chain configuration). A 120-ohm resistor must be<br />

added to the last device. (See Figure 3.3 <strong>System</strong><br />

Wiring). The resistor is taped to the inside of the<br />

panel for shipping.<br />

3.3.4. Wiring Panel to Sensors<br />

a. <strong>System</strong> water temperature sensor - Run a 2 wire,<br />

22 ga. shielded cable from terminals a+ and a- in<br />

the <strong>ECCS</strong> panel to the wire leads on the<br />

temperature sensor. Attach shield at panel to<br />

terminal marked shield. See Figure 3.4 <strong>ECCS</strong><br />

Panel Wiring Diagrams.<br />

b. Outdoor air temperature sensor - Run a 2 wire, 22<br />

ga. shielded cable from terminals b+ and b- in the<br />

<strong>ECCS</strong> panel to the wire leads on the outdoor<br />

temperature sensor. Attach shield at panel to<br />

terminal marked shield. See Figure 3.4 <strong>ECCS</strong><br />

Panel Wiring Diagram.<br />

NOTICE<br />

Sensor wiring is susceptible to electrical<br />

interference. Insure the shield on cable is<br />

grounded on one end only.<br />

11


12<br />

Figure 3.2: Panel Layout


13<br />

Figure 3.3: <strong>System</strong> Wiring


Figure 3.4: <strong>ECCS</strong> Panel Wiring Diagram<br />

14


15<br />

Figure 3.5: Boiler Wiring Diagram


Section 4: Setting the Modbus Addresses<br />

4.1 COMMUNICATION SETUP FOR BOILERS<br />

Each Modbus device in each boiler must be addressed to<br />

properly communicate with the <strong>ECCS</strong> system. The<br />

Temperature <strong>Control</strong>ler must be addressed through the<br />

configuration level and the flame safeguard will be<br />

addressed according to the following instructions. Refer to<br />

Appendix A, system wiring, or individual component<br />

manuals.<br />

4.2 SETTING THE ADDRESS OF THE HONEYWELL<br />

MODBUS MODULE<br />

Addressing for the HW Modbus Module correlates to the<br />

Temp <strong>Control</strong>lers Modbus addressing on the same unit.<br />

There are 2 dials on the bottom of the module that need to<br />

be set and a jumper that needs to be removed. Refer to<br />

Figure 4.1: Honeywell S7810M Modbus Module Mounting<br />

and 4.2: S7810M Address Switches and Baud Rate Jumper.<br />

4.3 SETTING THE MODBUS ADDRESS OF THE<br />

FIREYE MICRO M<br />

Addressing for the Fireye correlates to the Temperature<br />

<strong>Control</strong>lers Modbus addressing on the same unit. Refer to<br />

MicroM manual for instructions.<br />

Fireye MicroM<br />

Fireye<br />

Temperature Parameter<br />

<strong>Control</strong>ler Baud Rate @<br />

(C113)<br />

19,200<br />

Unit Address<br />

Boiler<br />

1 0160<br />

11<br />

Boiler<br />

2 0260<br />

12<br />

Boiler<br />

3 0360<br />

13<br />

Boiler<br />

4 0460<br />

14<br />

Boiler<br />

5 0560<br />

15<br />

Boiler<br />

6 0660<br />

16<br />

Honeywell<br />

Temperature<br />

<strong>Control</strong>ler<br />

(C113)<br />

S7810M<br />

Modbus<br />

Module<br />

Baud Rate @<br />

19,200<br />

remove<br />

jumper<br />

10"s<br />

Dial<br />

1"s<br />

Dial<br />

Boiler<br />

1<br />

0160<br />

1 1<br />

Boiler<br />

2<br />

0260<br />

1 2<br />

Boiler<br />

3<br />

0360<br />

1 3<br />

Boiler<br />

4<br />

0460<br />

1 4<br />

Boiler<br />

5<br />

0560<br />

1 5<br />

Boiler<br />

6<br />

0660<br />

1 6<br />

16


Figure 4.1: Honeywell S7810M Modbus TM Module Mounting<br />

17


Note: View from bottom of module<br />

Figure 4.2: S7810M Address Switches and Baud Rate Jumper<br />

18


Section 5: Touch Screen Programming<br />

5.1. SCREEN DESCRIPTION<br />

The touch screen is 116x87mm or (5.7"). The display uses<br />

CCFL(cold cathode Florescence Lamps) back lighting with<br />

320x240 pixels. Resistive/analog touch screen technology.<br />

5.2. GENERAL GUIDLENES FOR USING THE<br />

TOUCH SCREEN<br />

1) Touching the screen with the nail of the finger, an<br />

eraser on a pencil, or a pen cap is more effective<br />

than the skin on the tip of the finger.<br />

2) All inputs will have boxes around the value. A value<br />

without a box around it is for display only and<br />

cannot be changed.<br />

3) When you touch an input box, a keypad will be<br />

displayed for entering the desired value.<br />

4) Some inputs are password protected. If an input<br />

box is pressed and a Login box is displayed asking<br />

for a password, press the area where the password<br />

should be. A keypad will be displayed to enter the<br />

password. (See below.)<br />

5) When the correct password is entered the box<br />

will disapear and the desired value can now be<br />

entered into the input box by pressing it again and<br />

using the keypad that is displayed.<br />

6) Entering the password once will disable the need<br />

to enter it again on that security level and lower<br />

for 5 minutes.<br />

Press this area to<br />

enter password<br />

Figure 5.1: Touch Screen Login<br />

19


B1 = Boiler #1<br />

Bar graph shows<br />

firing rate as % of<br />

modulation<br />

Shows Firing rate<br />

as a numerical %<br />

of modulation.<br />

100% - Highfire<br />

1% - Low fire<br />

0% - Off<br />

Indicates if the boiler<br />

is the lead boiler, has<br />

a fault, or is operating<br />

in manual<br />

Boiler water outlet<br />

temperature<br />

Press button to access alarm history<br />

Figure 5.2: Main Screen<br />

Press input box to enter Setpoint<br />

Press button to enter a<br />

curve for outdoor reset<br />

<strong>On</strong>/off points set by<br />

the differential on<br />

the trigger points<br />

Press button to go to<br />

the trigger points<br />

screen<br />

Domestic Hot Water<br />

Setpoint<br />

Press button to<br />

enter a Lead<br />

Lag sequence<br />

Figure 5.3: <strong>System</strong> Setup Screen<br />

20


SETTING THE TRIGGERS AND THE START /STOP TIME DELAYS FOR THE LEAD LAG SYSTEM<br />

The value entered in this box will be subtracted from the setpoint to create<br />

the boiler <strong>On</strong> point. This <strong>On</strong> point has two separate functions–<br />

1)If the system has ON/OFF boilers, it will use the ON POINT as a trigger<br />

to turn on the next boiler.<br />

2)If the system is using modulating boilers only the lead boiler will use<br />

the on point to turn on.<br />

0% of firing rate =<br />

low fire<br />

100% of firing rate<br />

= high fire<br />

Input box. Firing rate of<br />

the running boiler<br />

which when reached<br />

will start the timer to<br />

start the next boiler in<br />

sequence. The limits of<br />

this value are between<br />

50 and 100.<br />

Input box. Firing<br />

rate of the running<br />

boiler which when<br />

reached will start<br />

the timer to stop the<br />

last boiler in the<br />

sequence. The<br />

limits of this value<br />

are 0 - 50.<br />

Adjustable start time<br />

delay which delays<br />

the starting of the next<br />

boiler in the sequence<br />

once the start trigger<br />

is made. The limits of<br />

this value are 90-900.<br />

Adjustable stop time<br />

delay which delays<br />

the stopping of the last<br />

running boiler in the<br />

sequence once the stop<br />

trigger is made. The<br />

limits of this value are<br />

0-1200.<br />

Figure 5.4: Lead Lag Trigger Setup Screen<br />

The value entered in this<br />

box will be added to the<br />

setpoint to create the<br />

boiler Off point. This<br />

Offpoint has two separate<br />

functions–<br />

1)If the system has<br />

ON/OFF boilers, it<br />

will use the Off point<br />

as a trigger to turn<br />

off the last running<br />

boiler.<br />

2)If the system is using<br />

modulating boilers<br />

only the lead boiler<br />

will use the the Off<br />

point to turn off.<br />

Example, using the values above (Modulating boilers) :<br />

Boiler 1 is on and reaches 90% of firing rate. The firing rate<br />

will have to stay above 90% for 120 sec for the next boiler<br />

in the sequence to start. If it drops below 90% before the 120<br />

second time delay is complete, the timer will reset.<br />

Example (<strong>On</strong>/Off boilers) : Assume a setpoint of 180 °F.<br />

The <strong>On</strong> and Off points are programmed on the screen at 5<br />

and 5. Therefore the boilers will turn on a 175 °F and off at<br />

185 °F. The boilers have a differential of 10°F.<br />

Boiler 1 is on and the temp at the system water temperature<br />

sensor drops below 175 °F for 120 sec., the next boiler in the<br />

sequence will start. If the system water temperature rises to<br />

175 °F before the time is complete, the timer will reset.<br />

21


ENTERING THE LEAD LAG SEQUENCE AND ROTATION TIME<br />

NOTICE<br />

Some boilers may shut down depending<br />

on the new sequence entered.<br />

The input boxes must<br />

be pressed and a<br />

keypad will be displayed<br />

on the screen to enter<br />

a new value.<br />

When the CHANGE SEQUENCE button is pressed,<br />

the input boxes and the sequence enter button will be<br />

displayed.<br />

Press and drag the<br />

AUTO ROTATE<br />

switch to turn on/off<br />

the automatic<br />

rotation of the<br />

sequence.<br />

Press the input box to<br />

set rotation time. Range<br />

is between 8 hours and<br />

720 hours. When in the<br />

auto rotate mode the<br />

sequence will<br />

automatically rotate as<br />

follows:<br />

Before rotation 1 (lead),<br />

2, 3, 4, 5.<br />

After rotation 2 (lead), 3,<br />

4, 5, 1.<br />

Figure 5.5: Sequence and Rotation Screen<br />

22


Outdoor Reset Switch.<br />

Press and drag toggle<br />

switch from OFF to ON.<br />

The setpoint will now<br />

be generated by the<br />

curve entered above.<br />

Entering temperatures in these 4 input<br />

boxes will generate a linear curve in<br />

which a setpoint based on outdoor air<br />

temperature will be generated.<br />

This is the setpoint which<br />

is generated based on the<br />

outdoor air curve entered<br />

and the outdoor air<br />

temperature.<br />

Pressing this button will<br />

go to the screen to set<br />

up the Warm Weather<br />

Shutdown Options.<br />

CAUTION<br />

This system cannot protect the boiler from cold water returning back to the boiler as is the case<br />

when coming out of a warm weather shutdown scenario. In order to protect the boiler from<br />

condensing, a primary/secondary piping arrangement or mixing valve must be installed in the<br />

piping.<br />

Figure 5.6: Outdoor Reset Setup Screen<br />

This is the setpoint of the boiler water at the outlet of<br />

the boiler. When in local the boiler will use this as its<br />

operating setpoint.<br />

The values for Setpoint,<br />

<strong>On</strong> point and Off point are<br />

for display only and come<br />

directly from the boiler<br />

temperature controller via<br />

a Modbus connection.<br />

These values come<br />

directly from the Flame<br />

Safeguard via a Modbus<br />

connection.<br />

Pressing and dragging this<br />

switch with your finger will<br />

change control from local to<br />

remote operation.<br />

Figure 5.7: Boiler Parameters Screen<br />

23


Pressing the Alarm History button<br />

on the main screen will get you to<br />

this screen<br />

Records Date and time the fault<br />

occurs(O), was Acknowledged(A),<br />

and cleared(C).<br />

Buffer can hold<br />

up to 110 fault<br />

messages.<br />

Figure 5.8: Alarm History Screen<br />

THIS BOX WILL AUTOMATICALLY APPEAR OVER ANY SCREEN WHEN A FAULT OCCURS<br />

Boiler # fault occured on<br />

Description<br />

fault<br />

of<br />

Fault code<br />

The Alarm Indicator will stay at the bottom of all<br />

screens until all faults have been cleared. The # at<br />

the bottom of the box indicates how many faults are<br />

active. Pressing this button will bring up a screen<br />

showing all the active alarms.<br />

Pressing the ACK button<br />

Acknowledges the alarm and<br />

makes the box disappear.<br />

Figure 5.9: Alarm Pop-up Screen<br />

24


Figure 5.10: Warm Weather Shutdown Screen<br />

Figure 5.11: Initial Setup Screen<br />

25


Figure 5.12: Trend Screen<br />

This trend will record header temperature and outdoor air temperature for up to 8 hours. Screen normally shows a one hour<br />

snapshot. Using the – and the + keys will zoom out to 8 hours or zoom in to 7.5 minutes (refer to Figure 5.13 Trend Screen Zoom<br />

<strong>Control</strong>). Each time a button is pressed, the graph will double or half (depending on button pressed) the time increment. Data is<br />

recorded every 30 seconds.<br />

Figure 5.13: Trend Screen Zoom <strong>Control</strong><br />

26


Figure 5.14 Time/Date Screen<br />

In order to access the time/date screen, press an invisible button in the<br />

upper right hand corner of the Boiler 1 Parameter Screen (figure 5.7)<br />

27


Section 6: Trouble Shooting Guide<br />

PROBLEM<br />

No boilers running<br />

Temperature<br />

OFF POINT.<br />

POSSIBLE CAUSE<br />

of water higher than the<br />

Boilers in local mode and boiler water<br />

temperature is above OFF POINT.<br />

POSSIBLE REMEDY<br />

Boilers will come on automatically when system<br />

water temperature drops below ON POINT.<br />

Switch to remote or wait for temperature to drop<br />

below ON POINT.<br />

B reaker in <strong>ECCS</strong> Panel in OFF or tripped. Turn on breaker in <strong>ECCS</strong> Panel.<br />

Touch Screen is not lit<br />

Power feeding <strong>ECCS</strong> Panel is OFF or<br />

tripped.<br />

Improper power supply to panel.<br />

Power<br />

to screen is not connected.<br />

Improper power supply to screen.<br />

Turn on breaker feeding <strong>ECCS</strong> Panel.<br />

Check power voltage and correct as needed.<br />

Panel requires 120VAC wired to 4 amp circuit<br />

breaker inside panel.<br />

Check wiring and correct as needed, 24VDC<br />

Screen uses 24VDC from PLC. Check voltage<br />

and correct if needed.<br />

B ad touch screen.<br />

Replace screen.<br />

No data being<br />

displayed on screen<br />

and no communication<br />

error or data on<br />

screen is not updating<br />

Modbus communication wires shorted<br />

together on any temperature controller or<br />

flame safeguard.<br />

Check Modbus wires A & B on all controllers for<br />

location where wires are touching each other<br />

and separate.<br />

P LC not in run mode.<br />

Flip switch on front of PLC to run position.<br />

P ower off to boiler.<br />

Turn power on to boiler.<br />

Alarm "Boiler #<br />

Communication<br />

Failure"<br />

Alarm "Boiler # Main<br />

Flame Failure"<br />

Modbus wiring disconnected on boiler<br />

showing alarm.<br />

Shield on wire not grounded properly.<br />

Baud rate setting on Fireye or Honeywell<br />

controller is wrong.<br />

Incorrect baud rate set on temperature<br />

controller.<br />

Modbus wiring A, B, C is not consistent<br />

throughout boiler devices.<br />

Boiler address not correct on flame<br />

safeguard or temperature controller.<br />

Boiler has faulted on a flame failure while<br />

in run mode.<br />

Connect Modbus wiring (3 wire shielded cable)<br />

to terminals A, B, C on devices.<br />

Shield should be grounded on one end of<br />

daisy chain only (panel end). Shields at wire<br />

junctions should be tied together.<br />

Set baud rate to 19,200.<br />

Configuration parameter check C113. Second<br />

value from right shall be a 6. Adjust as needed.<br />

Insure same wire is daisy chained to all A<br />

terminals, B to B terminals, and C to C<br />

terminals.<br />

Check appendix for correct setting on Modbus<br />

devices. See Section 4.<br />

Check controller manual. Reset flame<br />

safeguard controller.<br />

Alarm "Boiler # Pilot<br />

Flame Failure"<br />

Alarm "Boiler #<br />

Airflow Switch"<br />

B oiler has faulted while lighting pilot. Refer to boiler manual troubleshooting guide.<br />

F an did not energize.<br />

Refer to boiler manual troubleshooting guide.<br />

A ir flow switch set wrong or not working. Adjust or replace switch.<br />

F an running too slow.<br />

Check VFD to determine cause and correct.<br />

28


Section 7: Appendix A – Temperature <strong>Control</strong>ler Operation for Modulating<br />

Boilers (Modbus)<br />

7.1. DESCRIPTION<br />

The microprocessor based temperature<br />

controller is utilized for all modulating<br />

<strong>Thermal</strong> Solutions water boilers. The basic<br />

function of the controller is to modulate the<br />

firing rate of the burner in response to the<br />

boiler heat load. The controller monitors the<br />

boiler water temperature through the use of<br />

a sensor located in the boiler pressure<br />

vessel. The controller compares the boiler<br />

water temperature to the controller’s user<br />

defined operating set-point temperature.<br />

An output signal from the microprocessor<br />

varies the blower speed through the use of a<br />

variable frequency drive (VFD). The gas<br />

valve regulates an appropriate amount of<br />

gas flow for a given air flow or blower<br />

speed. The user may adjust the operating<br />

set-point temperature for a given<br />

application. In addition, the controller has the ability to<br />

change to an alternate set-point through an external signal<br />

for low load conditions (i.e. weekend use, night setback).<br />

Outdoor reset is another standard feature, allowing the<br />

boiler operating temperature to vary based on the outdoor<br />

ambient temperature. The typical result is a higher seasonal<br />

efficiency.<br />

7.2. SET-UP<br />

All of the control parameters have been set at the<br />

factory. There are a few parameters called “Process<br />

Parameters” that must be defined by a qualified<br />

operator. The table below will help serve as a<br />

reference and record when making adjustments.<br />

To alter any of these process parameters follow the<br />

following steps:<br />

• To obtain access into the programming mode<br />

of the controller, briefly press the button<br />

“PGM”.<br />

• You will see “SP1” displayed on the second<br />

line in green LEDs. The previously set<br />

operating temperature will be displayed on the<br />

first line in red LEDs. To increase or decrease<br />

the setpoint 1 value (SP1) use the up and<br />

down arrow keys respectively (st).<br />

• To set the value for “SP2”, briefly press the<br />

“PGM” key and follow the same instructions<br />

above.<br />

• To return to the operating mode press<br />

“EXIT”, otherwise the unit will automatically<br />

return to the operating mode after 30 seconds<br />

of no activity.<br />

To make other adjustments, contact your local<br />

representative or consult the factory.<br />

7.3. MODBUS VERSION USED ON BOILERS CONTROLLED BY THE <strong>ECCS</strong> SYSTEM<br />

The <strong>ECCS</strong> control system communicates with the temperature controller using a Modbus communication system. A three wire<br />

shielded cable is connected in a daisy chain configuration to each temperature controller at the CA,CB,CG terminals. This<br />

controller accepts modulating, enable/disable, and local/remote commands from a remote source. Information such as setpoint,<br />

water temperature, frequency feedback, on/off points, etc can also be transmitted back to the control panel.<br />

Parameter<br />

Display<br />

Value<br />

Range<br />

Factory<br />

Setting<br />

User Setting<br />

Setpoint<br />

1<br />

SP1<br />

125-200<br />

180<br />

Setpoint<br />

2<br />

SP2<br />

125-200<br />

0<br />

Digital Setpoint Shift<br />

(optional)<br />

dSP<br />

125-200<br />

0<br />

Outside Temperature<br />

(optional)<br />

Pre-definition of External<br />

Setpoint (optional)<br />

TA<br />

SP.E<br />

C onsult Factory<br />

—<br />

C onsult Factory<br />

—<br />

Figure 7.1 Process Data<br />

30


Actual Boiler Water<br />

Temperature (red display)<br />

Setpoint value (green display)<br />

Solid–local mode<br />

Flashing Ref–(Remote firing rate)<br />

Burner <strong>On</strong><br />

Call for Heat<br />

Decrease Value<br />

Indicates <strong>Manual</strong><br />

Operation<br />

Limit Comparator<br />

Increase Value<br />

Programming Key<br />

EXIT Key<br />

7.4 ADJUSTMENTS<br />

Often during troubleshooting conditions it may become<br />

necessary to manually adjust the firing rate. Follow the<br />

instructions below to make manual firing rate adjustments.<br />

• Press “EXIT” button and hold for 5 -10<br />

seconds.<br />

• The red light above manual operation (hand)<br />

symbol illuminates.<br />

• Press s button to raise firing rate. Press t<br />

button to lower firing rate.<br />

• 0 = 50% of Maximum firing rate and 100 =<br />

100% of Maximum firing rate<br />

• Press “EXIT” button and hold for 5 –10<br />

seconds to return to automatic firing rate<br />

control.<br />

• Automatic mode has been re-activated once<br />

the red light above the manual operation<br />

symbol goes out.<br />

7.5 SYSTEM SPECIFICATIONS<br />

Input voltage ....................................... 100-240vac 48/63hz<br />

Operating temperature ........................................... 0-120° F<br />

Environmental ........................................ NEMA 4 external,<br />

Internal 95%rh noncondensing<br />

Transducer supply ........................................ 24VDC, 30ma<br />

Analog Input 1 ..................Pt100,Ni100, PT1000, Ni 1000,<br />

... Thermocouple (J, K, T or N),4-20ma and Analog 0-10v<br />

Analog Input 2 ........... 1k pot,4-20ma, 0-1VDC, 0-10 VDC<br />

Analog Input 3 ............................................. Pt1000,Ni1000<br />

Output 1 release to modulate...... 24-240VAC 2Amps max<br />

Output 2 and 3 open/close .......... 24-240VAC 2Amps max<br />

Output 4 programmable ............. 24-240VAC 2Amps max<br />

Output 5 analog output ..... 0-10 VDC (500 ohm load min),<br />

....................................0-20 or 4-20ma (500ohm load max)<br />

Modbus RTU port ... 4800 Baud, 9600 Baud, 19,200 Baud<br />

................................................................ unit Address 1-99<br />

Size ................................... 1/8 din, 130mm mounting depth<br />

Data storage ......................................................... EEPROM<br />

Approvals ...................................................... UL, CSA, CE<br />

31


NOTES


NOTES


THERMAL SOLUTIONS PRODUCTS, LLC.<br />

(“Seller”)<br />

LIMITED WARRANTY<br />

LIMITED WARRANTY<br />

Subject to the terms and conditions herein and except as provided<br />

below with respect to products or parts not manufactured by<br />

<strong>Thermal</strong> Solutions Products, LLC, Seller warrants to the original<br />

owner at the original installation site that products manufactured<br />

by Seller (“Products”) comply, at the time of manufacture, with<br />

recognized hydronics industry regulatory agency standards and<br />

requirements then in effect and will be free from defects in<br />

materials and workmanship for a period of 3 years from date of<br />

shipment (the “Warranty Period”) SPECIAL NOTE: The<br />

warranty of any boiler found to be operating as a “Water Heater”<br />

shall revert back to <strong>Thermal</strong> Solution’s standard water heater<br />

warranty.<br />

For products or parts not manufactured by <strong>Thermal</strong> Solutions,<br />

the warranty obligations of <strong>Thermal</strong> Solutions shall, in all<br />

respects, be limited to one year.<br />

REMEDY<br />

A. The sole remedy for breach of this warranty is expressly<br />

limited to the repair or replacement of any part found to be<br />

defective under conditions of normal use within the<br />

Warranty Period. Labor for removal and/or installation is<br />

not included.<br />

B. Warranty - The owner must notify the original installer of<br />

the Product and Seller (Attention: <strong>Thermal</strong> Solutions<br />

Products, LLC, P.O. Box 3244, Lancaster, PA 17604-<br />

3244), in writing, within the Warranty Period, providing a<br />

detailed description of all claimed defects. Transportation to<br />

a factory or other designated facility for repairs of any<br />

products or items alleged defective shall, in all events, be the<br />

responsibility and at the cost of the owner.<br />

EXCLUSIONS<br />

Seller shall have no liability for and this warranty does not cover:<br />

A. Incidental, special or consequential damages, such as loss of<br />

the use of products, facilities or production, inconvenience,<br />

loss of time or labor expense involved in repairing or<br />

replacing the alleged defective Product.<br />

B. The performance of any Product under conditions varying<br />

materially from those under which such Product is usually<br />

tested under industry standards as of the time of shipment.<br />

C. Any damage to the Product due to abrasion, erosion,<br />

corrosion, deterioration, abnormal temperatures or the<br />

influence of foreign matter or energy.<br />

D. The design or operation of owner’s plant or equipment or of<br />

any facility or system of which any Product may be made a<br />

part.<br />

E. The suitability of any Product for any particular application.<br />

F. Any failure resulting from misuse, modification not<br />

authorized by Seller in writing, improper installation or lack<br />

of or improper maintenance.<br />

G. Equipment furnished by the owner, either mounted or<br />

unmounted, or when contracted for by the owner to be<br />

installed or handled.<br />

H. Leakage or other malfunction caused by:<br />

1. Defective installations in general and specifically, any<br />

installation which is made:<br />

a. in violation of applicable state or local plumbing<br />

housing or building codes,<br />

b. without a certified ASME, pressure relief valve, or<br />

c. contrary to the written instructions furnished with the<br />

unit<br />

2. Adverse local conditions in general and, specifically,<br />

sediment or lime precipitation in the tubes and/or headers<br />

or corrosive elements in the atmosphere.<br />

3. Misuse in general and, specifically, operation and<br />

maintenance contrary to the written instructions<br />

furnished with the unit, disconnection, alteration or<br />

addition of components or apparatus, not approved by<br />

seller, operation with fuels or settings other than those<br />

set forth on the rating plate or accidental or exterior<br />

damage.<br />

I. Production of noise, odors, discoloration or rusty water.<br />

J. Damage to surrounding area or property caused by leakage<br />

or malfunction.<br />

K. Costs associated with the replacement and/or repair of the<br />

unit including: any freight, shipping or delivery charges, any<br />

removal, installation or reinstallation charges, any material<br />

and/or permits required for installation reinstallation or<br />

repair, charges to return the boiler and or components.<br />

Seller’s liability under this warranty shall not in any case exceed<br />

the amount paid for the Product found to be defective.<br />

THIRD-PARTY WARRANTIES<br />

For goods or components not manufactured by Seller, the<br />

warranty obligations of Seller shall, in all respects, conform and<br />

be limited to one year from the date of shipment<br />

SEVERABILITY<br />

To the extent that any provision of this warranty would be void or<br />

prohibited under applicable law, such provisions shall be limited<br />

in effect to the minimum extent necessary to render the remaining<br />

provisions hereof enforceable.<br />

NO OTHER WARRANTIES<br />

Seller makes no implied warranty of merchantability or<br />

fitness for a particular purpose, or other warranties with<br />

respect to any products or services except as expressly set<br />

forth in this limited warranty.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!