AIR HANDLING SYSTEM CONTROL APPLICATIONSECONOMIZER CYCLE DECISION—OUTDOOR AIR/RETURN AIRENTHALPY COMPARISONFunctional DescriptionENTHALPYBTU PER POUND29.0 678 454 5EARA83 10OA1 2MA49 5216.8ENTHALPYBTU PER POUND83ECONOMIZER MODE SELECTOR91CONTROLPROGRAM11OTHER INPUTSAND OUTPUTS3 822OA MINIMUM SETPOINT(NOTE: THE TEST ANDBALANCE INITIALVALUE FOR PROPERVENTILATION IS 22)1 = AUTO BASED UPON OA/RAENTHALPY COMPARISON.72 = AUTO BASED UPON OA DBBELOW 72.0 DEGREES3 = MANUAL, ECONOMIZER ON.4 = MANUAL, ECONOMIZER OFF.NOTE:THE SYSTEM IS LOCKED OUT OF THE ECONOMIZERMODE ANYTIME THE OA DRY BULB ISABOVE 81.0 DEGREES.M10456ItemNo.Function1 Sensor senses OA temperature.2 Sensor senses OA humidity.3 OA enthalpy calculated from OA temperatureand humidity.4 Sensor senses RA temperature.5 Sensor senses RA humidity.6 RA enthalpy calculated from OA temperatureand humidity.7 Economizer mode selector and commandschedule.8 Setpoint for minimum OA damper position.9 Actuator positions OA and RA dampers.10 Actuator positions EA dampers.11 Control program coordinates occupancy,temperature, smoke control, and ventilationcontrols.ENGINEERING MANUAL OF AUTOMATIC CONTROL201