Heating Line Product Guide 435.0<strong>Ignition</strong> <strong>Controls</strong> SectionProduct Bulletin <strong>G73x</strong>Issue Date 0300<strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong>The CE compliant <strong>G73x</strong> family of controls aredesigned for indirect ignition of natural gas, LiquefiedPetroleum (LP) gas, manufactured gas, mixed gas, orLP gas-air mixtures.Figure 1: <strong>G73x</strong> <strong>Intermittent</strong> <strong>Pilot</strong><strong>Ignition</strong> ControlFeatures and Benefits❑ Microprocessor-basedDesign❑ Multiple Safety Times andWaiting Times (optional)❑ Optional DiagnosticLight-Emitting Diode (LED)❑ CE CompliantProvides precise timing and sequencingfunctionsOffers selectability of timing functions that willbest suit the applianceReduces troubleshooting time by visuallyinforming service technicians of current statusBroadens applications to include markets inEurope, Australia, etc.© 2000 Johnson <strong>Controls</strong>, Inc. 1Code No. LIT-4350425www.johnsoncontrols.com


Application RequirementsFollowing are the application requirements of the <strong>G73x</strong>control.• The <strong>G73x</strong> can be used on gas-fired equipmentwith a maximum firing rate of 117 kW(400,000 Btu/hr). Any application greater than117 kW (400,000 Btu/hr) must have writtenapproval in advance from the Johnson <strong>Controls</strong>Heating Products Engineering Department.• All <strong>G73x</strong> applications must use a redundant gasvalve system with the pilot and main valve seats inseries.• The control cannot be used on applications with apilot rating greater than 250 watts (850 Btu/hr).• The control does not directly monitor the pressureswitch. External circuitry is required on applicationsthat require proof of an open pressure switchbefore energizing the inducer.• All <strong>G73x</strong> controls have volatile lockout.• The <strong>G73x</strong> control does not contain an independentmanual reset function. The application of this typeof control is restricted to those appliances whereresetting by switching off the heat demand isallowed by European standards. Reset of anappliance in lockout must occur by means of aconscious manual action and not by means of(automatic) devices like thermostats or timers.• The ignition connections are not safe to touch.Additional protection against electric shock shouldbe provided by the appliance.Operating Mode DefinitionsThe following definitions describe operating conditions:●●●Start Signal--The signal from a thermostat thatbegins the ignition program.Waiting Time--The initial delay between the startsignal and the safety time to allow ventilation of thecombustion chamber and flue passages todisplace any unburned gas and/or products ofcombustion.Inter-waiting Time--The delay following a failedignition attempt or loss of flame signal to allowventilation of the combustion chamber and fluepassages to displace any unburned gas and/orproducts of combustion.• Safety Time--The time between energizing the pilotgas valve and de-energizing the pilot gas valve ifthe flame signal is not detected.●●●●●●Spark Restoration--The process of energizing thespark following the loss of flame signal within thefirst 5 seconds of the running position without totalinterruption of the gas supply.Running Position--The main valve and pilot valveremain energized and the spark is de-energized.The appliance is in normal operation under thesupervision of the ignition control and its flamedetector device.Retrial--Failing an ignition attempt, the controlenters the inter-waiting time and than startsanother safety time (models with optional retrials).Recycling--The process of automatically repeatinga full startup sequence after a safety shutdown(removing the power to the gas valve and igniter).Startup Sequence--The sequence of actionsexecuted by the system that brings the burner fromthe start to the running position.Volatile Lockout--The safety shutdown of thesystem where a startup sequence can only beginafter the thermostat contacts or main power iscycled.Normal Sequence of OperationFigure 2 illustrates the normal sequence of operationof the <strong>G73x</strong> control.The <strong>G73x</strong> control is energized upon receiving a startsignal from the system thermostat.1. Waiting Time--If the control has an optional waitingtime, the appliance fan or relay is energizedthrough the thermostat contacts. The controldelays for the waiting time before continuing to thesafety time.2. Safety Time--The control simultaneously energizesthe spark igniter and pilot valve in an attempt tolight the pilot burner. During the safety time, thespark igniter is energized until a flame signal issensed or the safety time has elapsed, whicheveroccurs first.3. Running Position--Once a flame signal is sensed,the control energizes the main valve. The controlcontinues to energize the pilot and main valvesuntil the start signal is removed.2 <strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin


! WARNING: Personal Injury Hazard. Avoid personal injury.The <strong>G73x</strong> ignition control has volatile lockout.The control restarts operation if the thermostator main power is cycled.StartFlame Present whenNot ExpectedDetected FaultStart SignalNoFlame signalpresent for30 seconds?YesVolatile Lockout(optional LEDturns off)Waiting TimeSafety Time<strong>Pilot</strong>flamesensed?YesEnergizemain valveRunningPositionNoYesInter-waitingTimeNoMaximumnumber of retrialsattempted?Loss offlame signal?YesNoStart SignalNoYesVolatile Lockout(optional LEDflashes)YesFifth lossof flamesignal?De-energizeControl and ValvesNoEndNoDoes the controluse separate spark/senseand is it less than5 seconds of enteringrunning position?Spark RestorationYesFigure 2: <strong>G73x</strong> Sequence of Operation<strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin 3


Mounting and WiringChoose a location that provides the shortest, directcable route to the spark electrode, pilot burner/ignitersensorassembly. Easy access to the terminals isdesired for wiring and servicing.The control may be mounted in any position. Refer toFigure 3 for mounting dimensions, and Figures 4 and 5for wiring diagrams.80.311562.2260.25 Spade Terminals582.281Add 13 mm (0.50 in.) forRajah type connector.783.0660.22341.33200.771164.571204.704.10.162 Two Holesfor Mounting Screws60.22672.63512.00Figure 3: Mounting Dimensions, mm (in.)4 <strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin


<strong>Pilot</strong> BurnerAssemblyIntegralIgniter/SensorMain BurnerGround<strong>Pilot</strong>Gas SupplyGROUND5LEDTHS 2RemoteLEDLimits in ThermostatLine OnlyALARMPV 1MV 3<strong>Ignition</strong> Control<strong>Pilot</strong>ValveMainValveHighLimitThermostat2 Ampere FuseTransformerPowerSupplyIMPORTANT:The <strong>G73x</strong> ignition control does not respondto a high limit fault with non-volatile lockout.Therefore, a manually resettable high limitswitch must be used with the control to meetEuropean agency operating requirements.Figure 4: Wiring Diagram for Integral Spark/Sense<strong>Pilot</strong> BurnerAssemblyFlame SensorMain BurnerGround<strong>Pilot</strong>Gas SupplyGROUND5LEDTHS 2Limits in ThermostatLine OnlyPV 1MV 3SENSE 4<strong>Ignition</strong> Control<strong>Pilot</strong>ValveMainValveHighLimitThermostat2 Ampere FuseTransformerPowerSupplyIMPORTANT: The <strong>G73x</strong> ignition control does not respondto a high limit fault with non-volatile lockout.Therefore, a manually resettable high limitswitch must be used with the control to meetEuropean agency operating requirements.Figure 5: Wiring Diagram for Separate Spark/Sense<strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin 5


Ordering InformationSafetyG 7 3 _ _ _ _ - _ _Customer-specific RequirementsWaiting TimeA = 0 SecondB = 30 SecondsD = 15 SecondsDamper PlugG = NoH = YesTimeA = Three 8-second Safety TimesB = Three 25-second Safety TimesC = Three 50-second Safety TimesD = Three 85-second Safety TimesE = Three 120-second Safety TimesK = One 8-second Safety TimeL = One 25-second Safety TimeM = One 50-second Safety TimeN = One 85-second Safety TimeP = One 120-second Safety TimeT = Five 8-second Safety TimesU = Five 25-second Safety TimesV = Five 50-second Safety TimesW = Five 85-second Safety TimesY = Five 120-second Safety TimesSpark/Sense0 = Separate7 = IntegralThe presence of a particular construction in this information does not guaranteeits availability. Consult Johnson <strong>Controls</strong> for available constructions.Figure 6: Ordering Matrix6 <strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin


Specifications (Cont.)PackagingBulk Pack Quantity 50Bulk Pack WeightAgency ListingBulk pack supplied to original equipment manufacturer (individual pack optional)15 kg (33 lb)EC Certification Number 0063AU1371Specification Standards EN 298Standards Complying with the EMC DirectiveClassification Code ATOVXN**Enclosure Degree ofProtectionIP00*Timings listed are for 50 Hz operation.**The G730 control uses a combination of spark restoration and recycling. A failed ignition attempt always uses recycling.A loss of flame signal within the first 5 seconds of ignition causes spark restoration. After 5 seconds, a loss of flame signalcauses recycling.The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyondthese specifications, consult the local Johnson <strong>Controls</strong> office. Johnson <strong>Controls</strong>, Inc. shall not be liable for damages resultingfrom misapplication or misuse of its products.Refer to the <strong>G73x</strong> <strong>Series</strong> Technical Bulletin (LIT-121248) for necessary information on the installation, use, and servicing of this product.<strong>Controls</strong> Groupwww.johnsoncontrols.com507 E. Michigan Street FAN 435.0P.O. Box 423Heating Line Product GuideMilwaukee, WI 53201Printed in U.S.A.8 <strong>G73x</strong> <strong>Series</strong> <strong>Intermittent</strong> <strong>Pilot</strong> <strong>Ignition</strong> <strong>Controls</strong> Product Bulletin