Ground Fault Monitor RCMA470
Ground Fault Monitor RCMA470
Ground Fault Monitor RCMA470
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Residual current monitor <strong>RCMA470</strong>LYAccessoriesExternal measuring current transformersType Inside diameter (mm) Art. No.W35B ø 35 B 9808 0013W60B ø 60 B 9808 0021External measuring instrumentType Display range Size (mm) Art. No.9604-4241 0…100 % 96 x 96 B 986 807Measuring converterConditions of operation according to IEC 62020, IEC 60755 amendment 2, Type BType Input Output Art. No.RK170 0…400 μA 0…10 V/0/4…20 mA B 9804 1500Type of current Wave form Tripping current4.2Alternating currents (50 Hz)0.5…1 x I ΔnPulsed DC residual currents(positive and negative half waves)half-wave current0.5…1.4 x I ΔnPhase-controlled half-wave currentsCurrent delay angle 90° el / 135° el0.5…1.4 x I ΔnHalf-wave current superimposed bya smooth direct current of 6 mA0.5…1.4 x I ΔnSmooth DC residual current0.5…2 x I ΔnDimension diagram X470Dimensions in mmMain catalogue part 4 – 04.2007 / Residual current monitors, Residual current monitoring systems 61