Parameter Settings at the Installation Level 13Record your specific settings at the installation level on this page for future reference. Observe that not allentries listed may actually be accessible as it depends on the modules inserted in the HS2105 and the valueof certain parameters.Parameter Range Factory Setting Actual SettingLanguageDeutschReference Temperature PERIM-HTG 86˚F - 194˚F 167˚FReference Temperature FLOOR-HTG* 86˚F - 140˚F 113˚FFreeze Protection 0˚F - 50˚F 34˚FRoom Sensor OFF / ON OFFRoom Compensation OFF / 1 - 18˚F 5˚FNight Setback Modes Outside Setback OASETBACKSetbackRoom SetbackBoiler OffMaximum Circuit 1 Temperature 158 - 210˚F 176˚FMaximum Circuit 2 Temperature* 68 - 140˚F 122˚F for FLOOR-HTG68 - 194˚F 194˚F for PERIM-HTGFlue Gas Temperature** OFF/120˚F - 480˚F OFFOffset : Vertical Shift of Heating Curve -9˚F - 9˚F 0˚FHeating Circuit 1 NO SYSTEM/PERIM-HTG PERIM-HTGHeating Circuit 2* NO SYSTEM/PERIM-HTG FLOOR-HTGFLOOR-HTGDHW Production ON/OFF ONDHW recirculation Pump OFF/1/2/3/4/6/ON 2Burner System*** 1 stage/2 stage /modulating ONE-STAGEModulation Range*** 10% - 60% 30%Modulating Valve Operating Time*** 5 sec. - 60 sec. 12 sec.Pumplogic (Condensate Protection) 59˚F - 140˚F 104˚FBuilding Response 1/2/3 2DHW Prior ON/OFF ON*Requires Mixing Module FM 241**Requires Communications Module KM 271***Requires Burner Module FM 24237