Types of Terminals (continued)<br />

Fan Powered, Series Type<br />

(Constant Volume)<br />

The fan runs continuously, fed by a<br />

mixture of primary and plenum air.<br />

The more primary air is forced in, the<br />

less plenum air is drawn in. The result<br />

is variable volume from the central<br />

system, constant volume (and sound)<br />

to the room. Because the central<br />

system need only deliver air as far<br />

as the fan, the inlet static pressure<br />

Low Temperature<br />

Fan Terminals<br />

The fan terminal, with its inherent<br />

mixing, is well suited to handle the<br />

very cold air delivered by systems<br />

designed for air much colder than with<br />

conventional 55°F supply systems.<br />

In order to use standard diffusers,<br />

the primary air must be raised to<br />

Fan Powered, Low Profile<br />

This series or parallel type terminal<br />

has a vertical dimension of only 10.5”<br />

for all sizes, to minimize the depth<br />

of ceiling space required. Notice in<br />

the diagram at the right that the<br />

recirculating fan is laid flat on its<br />

side, shaft vertical. In localities where<br />

building heights are limited, the low<br />

profile terminal saves enough space<br />

to allow extra floors to be included<br />

Fan Powered, Access Floor<br />

Profile (Constant Volume)<br />

This series type terminal is designed to<br />

fit around the pedestal support grid of<br />

access, or raised, floor systems. In a<br />

typical access floor the grid is<br />

24” x 24”.<br />

ENGINEERING GUIDELINES<br />

Engineering Guidelines | Terminals, Controls and Accessories<br />

can be lower than in the parallel flow<br />

terminal (above). The fan, however,<br />

is sized to handle the total airflow.<br />

These are often used in applications<br />

where constant background sound and<br />

continuous airflow are desired.<br />

a conventional supply temperature<br />

before it enters the room. A<br />

commonly utilized solution is to mix<br />

it with recirculated air with a fan<br />

powered terminal. The most common<br />

application uses a Series Flow unit, but<br />

many applications have been utilized<br />

with Parallel units with a constant<br />

running fan.<br />

in a high-rise structure. Ceiling space<br />

can be as little as 12” to 14” deep.<br />

The low profile terminal is also useful<br />

in buildings constructed with precast<br />

concrete channel floors. The terminal<br />

can fit into the channel space with<br />

no extra depth required (Series type<br />

shown).<br />

The terminal can fit into the floor<br />

plenum without any modifications to<br />

the pedestal system.<br />

Primary<br />

Recirc.<br />

Figure 52. Plan View - Fan Powered,<br />

Series Type (Constant Volume)<br />

Primary<br />

Figure 53. Plan View - Fan Powered,<br />

Low Profile<br />

Primary<br />

Fan<br />

Recirculated<br />

<strong>Air</strong><br />

Fan<br />

Recirculated<br />

<strong>Air</strong><br />

Fan<br />

To<br />

Outlets<br />

To<br />

Outlets<br />

To<br />

Recirc. Outlets<br />

Figure 54. Plan View - Fan Powered,<br />

Access Floor Profile (Constant Volume)<br />

B<br />

B41<br />

<strong>Titus</strong> <strong>2008</strong> - <strong>2009</strong> <strong>Product</strong> <strong>Catalog</strong> | <strong>www</strong>.<strong>titus</strong>-hvac.com<br />

TERMINAL CONTROLS AND ACCESSORIES