Types of Terminals (continued)<br />
Fan Powered, Series Type<br />
(Constant Volume)<br />
The fan runs continuously, fed by a<br />
mixture of primary and plenum air.<br />
The more primary air is forced in, the<br />
less plenum air is drawn in. The result<br />
is variable volume from the central<br />
system, constant volume (and sound)<br />
to the room. Because the central<br />
system need only deliver air as far<br />
as the fan, the inlet static pressure<br />
Low Temperature<br />
Fan Terminals<br />
The fan terminal, with its inherent<br />
mixing, is well suited to handle the<br />
very cold air delivered by systems<br />
designed for air much colder than with<br />
conventional 55°F supply systems.<br />
In order to use standard diffusers,<br />
the primary air must be raised to<br />
Fan Powered, Low Profile<br />
This series or parallel type terminal<br />
has a vertical dimension of only 10.5”<br />
for all sizes, to minimize the depth<br />
of ceiling space required. Notice in<br />
the diagram at the right that the<br />
recirculating fan is laid flat on its<br />
side, shaft vertical. In localities where<br />
building heights are limited, the low<br />
profile terminal saves enough space<br />
to allow extra floors to be included<br />
Fan Powered, Access Floor<br />
Profile (Constant Volume)<br />
This series type terminal is designed to<br />
fit around the pedestal support grid of<br />
access, or raised, floor systems. In a<br />
typical access floor the grid is<br />
24” x 24”.<br />
ENGINEERING GUIDELINES<br />
Engineering Guidelines | Terminals, Controls and Accessories<br />
can be lower than in the parallel flow<br />
terminal (above). The fan, however,<br />
is sized to handle the total airflow.<br />
These are often used in applications<br />
where constant background sound and<br />
continuous airflow are desired.<br />
a conventional supply temperature<br />
before it enters the room. A<br />
commonly utilized solution is to mix<br />
it with recirculated air with a fan<br />
powered terminal. The most common<br />
application uses a Series Flow unit, but<br />
many applications have been utilized<br />
with Parallel units with a constant<br />
running fan.<br />
in a high-rise structure. Ceiling space<br />
can be as little as 12” to 14” deep.<br />
The low profile terminal is also useful<br />
in buildings constructed with precast<br />
concrete channel floors. The terminal<br />
can fit into the channel space with<br />
no extra depth required (Series type<br />
shown).<br />
The terminal can fit into the floor<br />
plenum without any modifications to<br />
the pedestal system.<br />
Primary<br />
Recirc.<br />
Figure 52. Plan View - Fan Powered,<br />
Series Type (Constant Volume)<br />
Primary<br />
Figure 53. Plan View - Fan Powered,<br />
Low Profile<br />
Primary<br />
Fan<br />
Recirculated<br />
<strong>Air</strong><br />
Fan<br />
Recirculated<br />
<strong>Air</strong><br />
Fan<br />
To<br />
Outlets<br />
To<br />
Outlets<br />
To<br />
Recirc. Outlets<br />
Figure 54. Plan View - Fan Powered,<br />
Access Floor Profile (Constant Volume)<br />
B<br />
B41<br />