Section 8: PI Controller81-PRGNO (PI Control Characteristics)Level = L1This parameter selects the characteristics of the PI Controller. By selecting the appropriate datacode, you may select direct- or reverse-acting loop, slow or fast rate of integration, whether feedforwardis active, and whether on/off control is via PS3 (see page 73 for more information). Thevalues shown here replace those given on page 67.Data Code Type of Loop Integration Rate Feed-ForwardPI Enabledby PS3?80 Direct Slow Active No81 Direct Fast Active No82 Reverse Slow Active No83 Reverse Fast Active No84 Direct Slow Active Yes85 Direct Fast Active Yes86 Reverse Slow Active Yes87 Reverse Fast Active Yes88 Direct Slow Inactive No89 Direct Fast Inactive No90 Reverse Slow Inactive No91 Reverse Fast Inactive No92 Direct Slow Inactive Yes93 Direct Fast Inactive Yes94 Reverse Slow Inactive Yes95 Reverse Fast Inactive Yes© 1998 TB Wood’s All Rights Reserved 81