Custom Control PanelsApplication• PLC, Motor Control or DistributionFeatures• Dimensions: To suit customer requirements• Main busbars: Top or bottom, fully extendible• Dropper busbars: To suit design requirements• Cable entry: Top and / or bottom• Access: Front and / or back• Construction: From 1 up to form 4 - fixed or demountablepattern• Protection standard: Up to IP55• Handling: Lifting plates or eye bolts• <strong>Equipment</strong>: Compatible with all makesTechnical dataRated Insulation <strong>Voltage</strong>1000 Volt AC at 50HzMain busbarsNumber of conductors4 conductors - L1, L2, L32, Earth5 conductors - L1, L2, L3, N, EarthRated currentsShort-time withstandup to 4000 AmpsUp to 100kA RMS / 1 Sec, 220kA PeakDropper busbarsRated CurrentsShort-time withstandUp to 1000 AmpsUp to 75kA RMS / 1 Sec, 165kA PeakAuxilliary busbars Number of conductors Up to 4 conductorsConstruction Forms or separation Up to FormProtective coating14Metal treatmentPowder coatingDe-rust, De-grease, Iron Phosphate and passivateEpoxy polyester (Interior)Polyurethan (Exterior)