30.11.2012 Views

POWERTRAB Type 1 Lightning arrester High ... - Phoenix Contact

POWERTRAB Type 1 Lightning arrester High ... - Phoenix Contact

POWERTRAB Type 1 Lightning arrester High ... - Phoenix Contact

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Further information on the products<br />

presented here and on the world of solutions<br />

from <strong>Phoenix</strong> <strong>Contact</strong> can be found at<br />

www.phoenixcontact.net/catalog<br />

Or contact us directly.<br />

PHoENix CoNTACT GmbH & Co. KG<br />

D-32823 Blomberg, Germany<br />

Phone: +49/5235/3-00<br />

Fax: +49/5235/3-4 12 00<br />

www.phoenixcontact.com<br />

industrial Connection Technology,<br />

Marking Systems and Mounting Material<br />

CLiPLinE<br />

Components and Systems<br />

AuTOmATiOn<br />

Connection Technology for<br />

Field Devices and Field Cabling<br />

PLusCOn<br />

Device Connection Technology<br />

and Electronic Housings<br />

COmBiCOn<br />

Power and Signal Quality<br />

TRABTECH<br />

Signal Converters, Switching<br />

Devices, Power Supplies<br />

inTERfACE<br />

MNR 52006470/22.02.2011-00 Printed in Germany © PHoENix CoNTACT 2011<br />

Power & Signal Quality TRABTECH<br />

<strong>POWERTRAB</strong> <strong>Type</strong> 1<br />

<strong>Lightning</strong> <strong>arrester</strong><br />

<strong>High</strong> performance for<br />

industrial AC applications


Full performance: PoWERTRAB PWT<br />

The high-performance lightning <strong>arrester</strong><br />

for industrial applications<br />

The lightning protection power pack<br />

The performance data of the new<br />

PoWERTRAB <strong>Type</strong> 1 <strong>arrester</strong> is<br />

impressive. The enormous rated voltage<br />

of 800V AC is especially interesting for<br />

applications with 690 V iT networks,<br />

among others. The PoWERTRAB can<br />

withstand temporary voltage peaks of up<br />

to 1,960 V for several hundred milliseconds<br />

without stress.<br />

At home in rough environments<br />

The robust housing design of the<br />

PoWERTRAB already shows its<br />

applicability in extreme environments at<br />

first sight.<br />

According to EN 60068, it is shock-tested<br />

up to 25 g and vibration-tested up to 5 g.<br />

Long-lasting and reliable<br />

The high power reserves as well as the<br />

extremely robust setup provide for a long<br />

service life and are synonymous for the<br />

availability of your system.<br />

PHoENix CoNTACT<br />

Characteristics<br />

• Encapsulated setup without emissions<br />

• Free of line follow currents and leakage currents<br />

• integrated multi-level function monitoring<br />

• optical status display and remote indication contact<br />

• Shock- and vibration-tested according to EN 60068<br />

• installation height up to 4,000 m<br />

Connection cross section up to 100 mm²<br />

Every PWT is equipped with two<br />

terminal points each for conductor cross<br />

sections from 16 to 50 mm². The inside<br />

hexagon screwing provides for high<br />

traction and safe handling.<br />

Rated voltage of the <strong>arrester</strong> 800 V AC<br />

Protection level ≤ 4,5 kV<br />

immunity to short circuit 50 kA<br />

Arrester backup fuse up to 400 A<br />

Branch line: 2x50mm 2<br />

impulse current i imp per position 35kA (10/350)µs<br />

Branch wiring 3-channel system<br />

Surge current capability up to 100kA (8/20)µs<br />

Two-level status monitoring with remote indication contact<br />

LED green: <strong>arrester</strong> OK, no indication via<br />

switching contacts<br />

LED red: <strong>arrester</strong> with previous damage,<br />

remote indication via first switching<br />

contact (opener)<br />

11 12 21 22<br />

<strong>Contact</strong> assignment:<br />

= auxiliary power remote indication circuit<br />

11, 12 = opener contact pre-damage<br />

21, 22 = opener contact defect<br />

Connection cross section: 6 x 1,5 mm²<br />

The <strong>POWERTRAB</strong> PWT in figures (iEC-test class / En-<strong>Type</strong>: i, ii / T1, T2)<br />

Feed-through: 50mm 2<br />

Feed-through wiring 3-channel system<br />

The PWT <strong>arrester</strong> possesses a multilevel<br />

signaling system in case of overload.<br />

A pre-damage is signaled via the<br />

status LED as well as reported via the<br />

first switching contact of the remote<br />

indication connection to the system<br />

controller. As the PWT still possesses<br />

the full protective power in this status,<br />

a replacement is only required during<br />

the next routine maintenance. in case<br />

of further overload events, the PWT<br />

will send this status via the second<br />

remote indication contact. in this case,<br />

a replacement should take place at short<br />

notice in order not to put the lightning<br />

protection of the system at risk.<br />

Dielectric strength up to 1500 V for 5 s<br />

ToV-capability 1960 V AC for 200 ms<br />

Applications<br />

iT system 500 V AC … 690 V AC<br />

TN system 400 / 690 V AC and 554 / 960 V AC<br />

Product range<br />

Arrester set 3-channel<br />

PWT 100-800AC-FM<br />

Art. No. 2800531<br />

(3 <strong>arrester</strong>s with connection set)<br />

Arrester 1-channel<br />

PWT 35-800AC-FM<br />

Art. No. 2800419<br />

Connection set<br />

PWT CCT-SET<br />

Art. No. 2800532