BT07C006GB-01(EC1)TERMINALS7 - <strong>41</strong>(MAUXX)AUXILIARY AIR OUTLET FITTINGTwo air outlets are provided on the side of the unit for connection to separate supply air outlets.They can be used to supply air from the fan coil unit to distant areas of a room or even to a different room.The total air flow does not change. The air flow at high speed depending on the air duct pressure drop is shown in the tables below.Note: all air ducts must be insulated in order to avoid condensation.N. 1 used outletsdP = pressure dropQ = water flowN. 2 used outletsdP = pressure dropQ = water flowThis is used to introduce primary air into the environment directly throughthe diffuser. The kit includes a flow separator to be fitted inside thecassette, and a circular fitting for connection to the flexible system ducting.The flow of air is sent directly to just one of the outlet louvers, withoutpassing through the coil. The air flow of fresh air introduced into theenvironment depend on the inlet static pressure.7-11-15 21-31-<strong>41</strong>Ø 150 mmØ 180 mmQ m³/h Pa Q m³/h Pa80 3 160 3120 8 200 8160 15 300 15200 25 400 25240 36 500 3612